Ascon tecnologic Z31SY Operating Instructions Manual Download Page 7

For correct functioning the instrument needs a first reference value
of the temperature difference between cell and evaporator.
Every variation of the value of the Active Set Point, of the differen-
tial "r.d", the start of a continuous cycle or the a defrost execution
delete this reference value and any reduction will be  performed un-
til the acquisition of a new reference value.

Pr1

Temp.

time

EP

SP

r.d

off

ON

Cool

(ot)

SP+r.d

DT0

DT1

1 °

DT2

DT3

ON

ON

ON

off

off

d.tE

d.di / d.Sd

Defrost

(dF)

Phase

0

1

2

3

time to defrost Ph. 0, 1

time to defrost Ph. 2

time to defrost Ph. 3

Defrost

d.tS

Example “dynamic defrost intervals system” with a reduction “d.dd”
= 40 % and end defrost by temperature.

4.8.2- MANUAL DEFROST

To start up a manual defrosting cycle, press the key UP/DEFROST
when it is not in programming mode and keep it pressed for about
5 seconds after which, if the conditions are correct, the led Defrost
will light up and the instrument will carry out a defrosting cycle.
To stop a defrosting cycle, press the key UP/DEFROST during a
defrost cycle and keep it pressed for about 5  sec.
The start up or switch off commands of a defrosting cycle can also
be given by the digital input that are correctly programmed (see Di-
gital input).

4.8.3 - DEFROST ENDS

The automatic defrosting cycle can be ended by time or, if an
evaporator probe is used (“EP” probe), when a temperature on the
evaporator is reached.
If the evaporator probe is not used or it is program the defrost
temperature control  (par. “d.dy” = Et) the duration cycle is set by
the parameter 

“d.dE”.

If instead the evaporator probe is used it is not program the defrost
temperature control (par. “d.dy” = EL, in, no) the defrost cycle end
when the temperature measured by the evaporator probe exceeds
the temperature set in the parameter 

“d.tE”.

If this temperature is not reached in the time set in the parameter
“d.dE”, defrosting is interrupted.

d.di

Temp.

dF

d.di/dSd

off

d.tS

d.tE

ON

A

off

EP

d.di

ON

d.dE

B

(NO defrost)

d.di

off

C

time

Examples:

 defrosting A ends due to reaching of temperature “dtE”,

defrosting B ends at the end of the  “d.dE” time as the temperature
“d.tE” is not reached, defrosting C does not take place as the
temperature is higher than “d.tS”.

In order to avoid pointless defrosting the parameter

 “d.tS”

 in

“d.dC” = rt, ct, cS mode is foreseen that sets the enablement
temperature for defrosting
If the temperature measured by the probe is higher than the one
set in the parameter “d.tS” and in the parameter "d.tE" the
defrosting is inhibited.

d .d i/d .S d

d .tE

d .tS

d F

o ff

O N

o ff

T e m p .

E P

1 °

tim e

d .d E

d .d i

O N

O N

Example of electric defrost with evaporator temperature control:
The defrost end after "d.dE" programmed time. During defrost the
“dF” output switch on/off to control evaporator temperature  in
heating mode with  set point “d.tE” and 1° differential (Hysteresis).

The active defrost is shown on the instrument display with the
lighting up of the DEFROST led
At the end of defrosting, it is possible to delay the new start up of
the compressor (output “ot”) at the time set in parameter 

“d.td” 

to

allow the evaporator to drain.
During this delay, the led Defrost flashes to indicate the draining
state.

4.8.4  - DEFROST DISPLAY LOCK

Through par. 

“d.dL” 

and

 “A.dA”

 it’s possible to define the display

behaviour during defrost.
The “d.dL” parameter pemits the display visualization lock on the
last Pr1 emperature reading (“d.dL” = on) during all the defrost
cycle until, at the end of defrost, the temperature has not reached
the lock value or the value [”SP” + “r.d”] or is elapsed the time
setted on par. "A.dA". 
Or it permits only the visualization of  label 

“dEF”

 (“d.dL” = Lb)

during the defrost cycle and, after the defrost, of label 

“PdF”

 until,  

at the end of defrost, the Pr1 temperature has not reached the lock
value or the value [”SP” + “r.d”] or is elapsed the time setted on
par. "A.dA".
The display will otherwise (“d.dL”= oF)  continue to visualize the
Pr1 temperature measured by the probe during the defrost cycle.

4.9 - EVAPORATOR FANS CONTROL

The control of the fans on the output configured as “Fn” depending
on determined control statuses of the instrument and the
temperature measured by the evaporator probe (E P).
In the case that the evaporator probe is not used or in error , the
output Fn is activated only depending on the parameters “F.tn”,
“F.tF” and “F.FE”.
The parameters

 “F.tn”

 e 

“F.tF”

 decides the funs functioning when

the output configured as “ot” (compressor) is off.
When output “ot” is off , it is possible to set the instrument so that
that the output “Fn”continues to work in cycles according to the
times programmed in the parameter  

“F.tn”

 (fan activation time)

and 

“F.tF” 

(fan deactivation time).

When output “ot” is switched off the instrument activates the output
“Fn for the time “F.tn”, then deactivates it for the time “F.tF” and so
on whilst the otuput “ot” remains off.
Programming “F.tn” = oF the output “Fn” in “ot” off condition will
remain switched off.
Programming instead “F.tn” to any value and “F.tF” = oF the output
“Fn” in “ot” off condition will remain switched on.
The parameter 

“F.FE

” instead decides whether the fans must

always be switched on independently of the defrosting status
(“F.FE”=on) or switched off during defrosting (“F.FE”=oF).
In this latter case, it is possible to delay the start up of the fans
even after the end of the defrosting of the time set in the parameter

“F.Fd”.

When this delay is active the led FAN flashing to signal the delay in
progress.
When the evaporator probe is used the fans, as well as being
conditioned by the parameters “F.tn”, “F.tF and “F.FE”, are also
conditioned by a temperature control.
It is possible to set the disablement of the fans when the
temperature measured by the evaporator probe is higher than the
one set in the parameter 

“F.FL”

 (temperature too hot) or when it is

ASCON TECNOLOGIC - Z31Y 

 

- OPERATING INSTRUCTIONS - Vr. 02 - 04/12 -  ISTR-MZ31YENG02 -  PAG. 7

Summary of Contents for Z31SY

Page 1: ...4 10 1 ALARM FUNCTIONS 4 10 EVAPORATOR FANS CONTROL 4 9 DEFROST DISPLAY LOCK 4 8 4 END DEFROST 4 8 3 MANUAL DEFROST 4 8 2 AUTOMATIC DEFROST STARTS 4 8 1 DEFROST CONTROL 4 8 COMPRESSOR PROTECTION FUNCT...

Page 2: ...status on off off and silenced or memorized flashing 11 Led AUX Indicates AUX output status on on off off or inhibited flashing 12 Led Stand By Indicate the Stand by status 2 PROGRAMMING 2 1 FAST PROG...

Page 3: ...identifiable by the printed code 103AT 11 visible on the sensor part is compliant with standard EN 13485 Thermometers for measuring the air and product temperature for the transport storage and distr...

Page 4: ...nt is switched off peak values are always re set However it is also possible to reset these values if the instrument is switched on by using the DOWN key hold for 3 sec during peak visualization The d...

Page 5: ...put will be on in normal mode Set Point SP active and off in economy mode operation Set Point SP2 active 4 Internal Light output managed by digital input This output will be on when door is opened i F...

Page 6: ...lts that currently used in the refrigerators systems ct intervals with counts only the compressor function time output ot switched on Mode typically used in the positive temperature refrigerators syst...

Page 7: ...1 differential Hysteresis The active defrost is shown on the instrument display with the lighting up of the DEFROST led At the end of defrosting it is possible to delay the new start up of the compre...

Page 8: ...s the alarm signal when the alarm status ends To cancel the alarm memory signal press any key It must be remembered that if an output function is desired with an alarm memory An or An it is necessary...

Page 9: ...cessary that the device or instrument are being supplied USB SUPPLY AC SUPPLY SUPPLY ADAPTER 12 VDC USB For additional info please have a look at the A01 instruction manual 4 12 2 TVRY REMOTE DISPLAY...

Page 10: ...obe Calibration i C2 10 oF oF 0 01 9 59 min sec Fan delay after defrost F Fd 37 oF oF on Fan status during defrost F FE 36 1 0 0 0 30 0 C F Differential fan control F dF 35 99 9 99 9 999 C F Low tempe...

Page 11: ...rs relative to compressor protection and power on delay 99 5 min sec x10 1 0 255 MODBUS Station address for serial communication t AS 60 oF oF 999 Access Password to parameter functions t PP 59 oF oF...

Page 12: ...21 990 25 C or NTC 103AT 2 10K 25 C 1 digital input for free voltage contacts alternative to Pr2 input Output s up to 2 relay outputs 5 A Res 6 4 A 8 3 A Out2 SPDT 8A 1 2HP 250V 1 3HP 125 VAC 12 A Res...

Page 13: ...1000 4 4 2KV supply and relay outputs 1KV inputs EN61000 4 5 supply 2KV com mode 1 KV diff mode EN61000 4 6 3V Directive 2006 95 CE EN 60730 1 EN 60730 2 9 Regulation 37 2005 CE EN13485 air S A 2 50 C...

Reviews: