10.3 Functional Features
Temperature Control: ON/OFF mode;
Defrost control: Interval cycles or temperature by Electric
Heating/Compressor stops or hot-gas/reverse cycle;
Measurement range: NTC: -50 ÷ 109°C/-58 ÷ 228°F;
Display resolution: 1° or 0.1° (in the range -99.9 ÷ 99.9°);
Overall accuracy: ±(0.5% fs + 1 digit);
Sampling rate: 130 ms;
Display: 3 Digit Red (Blue optional) h 15.5 mm;
Software class and structure: Class A;
Compliance: Directive 2004/108/CE (EN55022: class B;
EN61000-4-2: 8kV air, 4kV cont.; EN61000-4-3: 10V/m;
EN61000-4-4: 2kV supply and relay outputs, 1kV inputs;
EN61000-4-5: supply 2kV com. mode, 1kV\ diff. mode;
EN61000-4-6: 3V),
Directive 2006/95/CE (EN 60730-1, EN 60730-2-9),
Regulation 37/2005/CE (EN13485 air, S, A, 2,- 50°C +90°C
with probe NTC 103AT11).
11 HOW TO ORDER
Model
Y39W
- = Instrument with mechanical keyboard
Y39SW
= Instrument with Sensitive Touch keyboard
a: Power supply
H
= 100... 240 VAC
G
= 12... 24 VAC/DC
F
= 12 VAC/DC
b: Output 1 (Out 1)
R
= Out1 Relay SPST-NO 16A-AC1 (resistive load)
d: Output 3 (Out 3)
-
= None
R
= Relay SPST-NO 5A-AC1 (resistive load)
e: Buzzer
-
= Not present
B
= Buzzer
f: Terminals
-
= Fixed Screw power terminals (standard)
E
= Removable screw power terminals
G
= Removable screw power terminals
(the fixed part only)
c: Output 2 (Out 2)
-
= None
R
= Relay SPDT 8A-AC1 (resistive load)
g: Display
-
= Red
B
= Blue
c
a b
d e f g h i
kk
ll
j
h, i, j
:
RESERVED CODES;
kk, ll
:
SPECIAL CODES.
Note:
To order the Optional Screw type Bracket necesary
to obtain the IP65 Front protection degree, please,
contact your Ascon Tecnologic supplier.