8  PROBLEMS AND MAINTENANCE

8.1 

Error messages

Error

Reason

Action

E1

 

-E1

The probe may be interrupted 

(E) or in short circuit (-E), or 

may measure a value outside 

the range allowed

Check the correct connec-

tion of the probe with the 

instrument and check the 

probe works correctly

E2

 

-E2

E3

 

-E3

EPr

Internal EEPROM memory error Press the

 

 key

Err

Fatal memory error 

Replace the instrument or 

ship to factory for repair

8.2 

Other messages

Message

Reason

od

Delay at power-on in progress

Ln

Keyboard lock

Hi1

Temperature 1 max. alarm in progress

Lo1

Temperature 1 min. alarm in progress

Hi2

Temperature 2 max. alarm in progress

Lo2

Temperature 2 min. alarm in progress

oP

Door opened

8.3 

Cleaning

We recommend  cleaning of the instrument only with a slightly 
wet cloth using water and not abrasive cleaners or solvents.

8.4 

Disposal

The appliance (or the product) must be disposed 

of separately in compliance with the local standards 

in force on waste disposal.

9  WARRANTY AND REPAIRS

The instrument is under warranty against manufacturing 
flaws or faulty material, that are found within 18 months from 
delivery date.
The guarantee is limited to repairs or to the replacement of 
the instrument.
The eventual opening of the housing, the violation of the instru-
ment or the improper use and installation of the product will 
bring about the immediate withdrawal of the warranty effects.
In the event of a faulty instrument, either within the period of 
warranty, or further to its expiry, please contact our sales de-
partment to obtain authorisation for sending the instrument 
to our company.
The faulty product must be shipped to Ascon Tecnologic with 
a detailed description of the faults found, without any fees or 
charge for Ascon Tecnologic, except in the event of alterna-
tive agreements.

10  TECHNICAL DATA

10.1  Electrical Data

Power supply: 12 VAC/DC, 12 ÷ 24 VAC/DC, 100 ÷ 240 VAC ±10%;
AC Frequency: 50/60 Hz;
Power consumption: 3.5 VA approx.
Input(s): 3 inputs for temperature probes: NTC (103AT-2, 
10k

W

 @ 25°C); 1 digital input for free of voltage contacts (as 

alternative to Pr2/Pr3 input);
Output(s): Up to 3 relay outputs:

EN 61810 EN 60730 UL 60730

Out1

 - SPST-NO - 16A -  

1HP 250V, 1/2HP 125 VAC

16 (9) A

10 (4) A

12 A Res.,  

30 LRA,  

5 FLA

Out2

 - SPDT - 8A - 1/2HP 250V, 

1/3HP 125 VAC

8 (3) A

4 (4) A

4 A Res.

Out3

 - SPST-NO - 5A -  

1/8HP 250V, 1/10HP 125 VAC

5 (2) A

2 (2) A

2 A Res.

16 A max. for outputs common (pin. 1), 12 A max. for extract-
able terminal block model.
Electrical life for relay outputs: 100000 op. (EN60730);
Action type: type 1.B (EN 60730-1);
Overvoltage category: II;
Protection class: Class II;
Insulation: Reinforced insulation between the low voltage 
part (supply H type and relay output) and front panel; Re-
inforced insulation between the low voltage section (supply 
H type and relay output) and the extra low voltage section 
(inputs); Reinforced between supply and relay output; No 
insulation between supply F or G type and inputs.

10.2  Mechanical Data

Housing: Self-extinguishing plastic, UL 94 V0;
Heat and fire resistance category: D;
Ball Pressure Test secondo EN60730: accessible parts 75°C, 
support live parts 125°C;
Dimensions: 78 x 35 mm, depth 64 mm
Weight: 130 g approx.;
Mounting: Incorporated Flush in panel  (thickness 12 mm 
max.) in 71 x 29 mm hole;
Connections:  2.5 mm

2

 screw terminals block or 2.5 mm

2

 

extractable screw terminals block for 0.2 ÷ 2.5 mm

2

AWG 24 ÷ 14 cables;
Front panel protection degree: IIP65 (NEMA 3S) mounted 
with opotional screw type bracket;
Pollution situation: 2;
Operating temperature: 0 ÷ 50°C;
Operating humidity: < 95 RH% with no condensation;
Storage temperature: -25 ÷ +60°C.

Summary of Contents for Y39W

Page 1: ...studied in particular to manage refrigeration units display cases etc typically in tended for the storage and distribution of wines and or drinks in domestic or commercial uses The instrument is equi...

Page 2: ...both loops programmed for heating action but with parameter t Ld 2 this LED shows the r1 controller status while the status of controller r2 is shown by Aux LED 8 LED Indicates Defrost in progress ON...

Page 3: ...to 0 now using the keys insert the programmed password number and press the key again If the password is correct the instrument displays the code of the first parameter and it will be possible to pro...

Page 4: ...use of the instrument for applications not expressly permitted by the above mentioned rule must adopt all the necessary protective measures The instrument MUST NOT BE USED in dangerous flamma ble or...

Page 5: ...vices ex fuses proportionate to the circulat ing currents It is strongly recommended that cables with proper insula tion according to the working voltages and temperatures are to be used Furthermore t...

Page 6: ...ables that can be displayed are Pr1 Probe Pr1 measurement Pr2 Probe Pr2 measurement on oF if set as digital input Pr3 Probe Pr3 measurement on oF if set as digital input The system automatically exits...

Page 7: ...the following functions oF Buzzer always disabled 1 The Buzzer sounds when an alarm is active 2 The Buzzer sounds when a key pressed does not signal alarms 3 The Buzzer sounds when a key pressed and...

Page 8: ...nfigured for r1 and r2 operation the LEDs still indicate the controllers status If both controllers are configured for the same action r Fc CC HH the or LEDs indicate the activation of at least one of...

Page 9: ...frost the control outputs ot and the Fanscon tinue operating while df output is enabled 5 8 1 Automatic Defrosts Start The automatic control of defrost occours by Interval times For continuous compres...

Page 10: ...s of parameters A y2 and A y2 are 1 Absolute Alarms referred to Pr1 probe 2 Alarms Relative to SP1 referred to pr1 probe 3 Absolute Alarms referred to r2 probe 4 Alarms Relative to SP2 referred to r2...

Page 11: ...e key for at least 5 s it is possible to enable disable a defrost cycle 3 Pressing the key for at least 1 s it is possible to switch the instrument from the ON status to Stand by status and vice versa...

Page 12: ...itch on off Stand by 4 Auxiliary output command 5 Door open with fan stop 6 Door open without fan stop 0 16 i ti Delay in acquiring digital input oF 0 01 9 59 min s 99 5 min s x10 oF 17 i dS Variable...

Page 13: ...H2 e A L2 oF 0 01 9 59 min s 99 5 min s x 10 oF 46 A PA Temperature Alarms delay at power ON oF 01 9 59 h min 99 5 h min x 10 2 00 47 A dA Temperature Alarms delay after defrost oF 0 01 9 59 h min 99...

Page 14: ...with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 TECHNICAL DATA 10 1 Electrical Data Power supply 12 VA...

Page 15: ...rective 2006 95 CE EN 60730 1 EN 60730 2 9 Regulation 37 2005 CE EN13485 air S A 2 50 C 90 C with probe NTC 103AT11 11 HOW TO ORDER Model Y39W Instrument with mechanical keyboard Y39SW Instrument with...

Page 16: ...Ascon Tecnologic Y39W Line Operating Instructions Pag 16...

Reviews: