Parameter
Description
Range
Default
Note
29
P.21
Output
r2
activation delay
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
30
P.22
Delay after output
r2
switch OFF
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
31
P.od
Outputs activation delay at power ON oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
32
d.dt
Defrost Type
EL
Not ventilated with Electrical heating/Stop Compressor;
Fn
Ventilated with Electrical heating/Stop Compressor;
no
Without compressor output conditioning.
EL
33
d.di
Defrosts interval
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
34
d.dE
Length (max.) of defrost cycle
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
35
d.cd
Defrost start for continuous com-
pressor functioning
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
36
A.y1
Temperature 1 alarms type
1
Absolute (
Pr1
);
2
Relative to
SP1
(
Pr1
);
3
Absolute (
r2
);
4
Relative to
SP2
(
r2
);
5
Absolute (
Au
).
1
37
A.H1
High temperature 1 Alarm threshold oF/-99.9 ÷ 999°C/°F
oF
38
A.L1
Low temperature 1 Alarm threshold
oF/-99.9 ÷ 999°C/°F
oF
39
A.d1
Differential alarms
A.H1
and
A.L1
0.0 ÷ 30.0°C/°F
1.0
40
A.t1
Delay alarms
A.H1
and
A.L1
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
41
A.y2
Temperature 1 alarms type
1
Absolute (
Pr1
);
2
Relative to
SP1
(
Pr1
);
3
Absolute (
r2
);
4
Relative to
SP2
(
r2
);
5
Absolute (
Au
).
3
42
A.H2
Pr2
/
Pr3
High temp. Alarm threshold
oF/-99.9 ÷ 999°C/°F
oF
43
A.L2
Pr2
/
Pr3
Low temp. Alarm threshold
oF/-99.9 ÷ 999°C/°F
oF
44
A.d2
Differential alarms
A.H2
e
A.L2
0.0 ÷ 30.0°C/°F
1.0
45
A.t2
Delay alarms
A.H2
e
A.L2
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
46
A.PA
Temperature Alarms delay at power ON oF/.01 ÷ 9.59 (h.min) ÷ 99.5 (h.min x 10)
2.00
47
A.dA
Temperature Alarms delay after defrost oF/ 0.01 ÷ 9.59 (h.min) ÷ 99.5 (h.min x 10)
1.00
48
A.oA
Open door Alarm delay
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
3.00
49
o.o1
Out1 function
r1
Controller 1;
r2
Controller 2;
dF Defroster;
Fn Fans;
Au Auxiliary;
At/-t Silenceable alarm;
AL/-L Not silenceable Alarm;
on
Output ON when instrument switched on;
oF
No function.
r1
50
o.o2
Out2 function
r2
51
o.o3
Out3 function
oF
52
o.bu
Buzzer function mode
oF Disable;d
1
Active for alarms only;
2
Active for Key pressed only;
3
Active for alarms and Key pressed.
3
53
o.Fo
Aux output operating mode
oF
No function;
1 Delayed
r1
output;
2 Delayed
r2
output;
3
Manual activation by key or digital input;
4
Internal light (OFF = door closed and ON = door open).
oF
54
o.tu
Time relative to auxiliary output
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
55
t.UF
Function mode key
oF
No function;
1
Auxiliary output command;
2
Defrost command;
3
Switch ON/OFF command (Stand-by);
4
Access the fast SP1 change procedure;
5
Access the fast SP2 change procedure.
oF
56
t.FA
Function mode key
oF
57
t.Fb
Function mode key
oF
58
t.Lo
Keyboard lock function delay
oF/0.01 ÷ 9.59 (min.s) ÷ 30.0 (min.s x 10)
oF
59
t.Ld
Aux
LED functioning mode
1
Output configured as Auxiliary;
2
Output controller
r2
when both controllers are configured
for the same operation mode (
H-H
or
C-C
).
1
60
t.Ed
Set Point visibility with the Fast SP
change procedure (key
)
oF None;
1 SP1;
2 SP2;
3
SP1 and SP2.
1
61
t.PP
Parameters protection password
oF/1 ÷ 999
oF
62
t.Ad
Serial communications instrument
address
0 ÷ 255
1