Ascon tecnologic TLI40 Operating Instructions Manual Download Page 9

ASCON TECNOLOGIC - TLI 40 - OPERATING INSTRUCTIONS - 

PAG. 9

=  r.Pic:By  closing  the  contact  connected  to  the  digital  input  the 
values of higher and lower peaks are reset. 
= 0.Pot: For the instruments equipped with potentiometer input, with 
this  function  it  is  possible  to  set  the  “zero”  value.  By  closing  the 
contact connected to the digital input the instrument will set as 0 the 
value measured in that instant. 
= r.P0P: For the instruments equipped with potentiometer input, with 
this function it is possible to set the “zero” value and contemporarily 
reset  the  higher  and  lower  peaks  values.  By  closing  the  contact 
connected to the digital input the instrument will set as 0 the value 
measured in that instant and resetting the memorized peaks values. 

GROUP “ 

]

 O1” (PARAMETERS RELATIVE TO OUTPUT OUT1):

They permit to program the output OUT1 functioning.

 

O1F

  –  FUNCTIONING  OF  OUTPUT  OUT  1  DIGITAL  TYPE:  This 

defines the functioning of output OUT 1 as: alarm output as normally 
open (ALno), output alarm normally closed (ALnc), output not used 
(OFF). 

Aor1

  -  BEGINNING  OF  OUTPUT  SCALE  1  ANALOGICAL  TYPE: 

This  allows  the  beginning  of  the  analogical output OUT1 to be set. 
This  parameter  will  therefore  be  set  with:  "0"  if  one  intends  to  use 
the  beginning  of  the  scale  as  being  equal  to  0  (0  mA,  or  0  V)  or 
"no_0"  if  one  intends  to  use  the  beginning  of  the  scale  as  being 
other than 0  (4 mA, or 2 V). 

Ao1F

 - ANALOGICAL OUTPUT OUT1 FUNCTION: This determines 

the  function  of  the  OUT  1  output  as:  measurement  retransmission 
output  (r.inP),  output  guided  by  the  instrument’s  serial 
communications line (rSEr), output not used (OFF). 

Ao1L - 

MINIMUM REFERENCE FOR ANALOGICAL OUTPUT OUT 

1 FOR SIGNAL RETRANSMISSION: in the event that the analogical 
output function is configured for the retransmission of the signal, set 
this  parameter  with  the  value  to  which  the  instrument  must  supply 
the minimum value in output (0/4 mA or 0/2 V) 

Ao1H  - 

MAXIMUM

 

REFERENCE  FOR  ANALOGICAL  OUTPUT 

OUT  1  FOR  SIGNAL  RETRANSMISSION:  in  the  event  that  the 
analogical output function is configured for the retransmission of the 
signal,  set  this  parameter  with  the  value  to  which  the  instrument 
must supply the maximum value in output (20 mA or 10 V). 

GROUP “ 

]

 O2” (PARAMETERS RELATIVE TO OUTPUT OUT2):

They permit to program the output OUT2 functioning.

 

O2F

 - FUNCTIONING OF OUTPUT OUT 2 DIGITAL TYPE: Equal to 

“O1F” but referred to output OUT2. 

GROUP “ 

]

 O3” (PARAMETERS RELATIVE TO OUTPUT OUT3):

They permit to program the output OUT3 functioning.

 

O3F

  –  FUNCTIONING  OF  OUTPUT  OUT  3  DIGITAL  TYPE:  Equal 

to “O1F” but referred to OUT3. 

GROUP “ 

]

 O4” (PARAMETERS RELATIVE TO OUTPUT OUT4):

They permit to program the output OUT4 functioning.

 

O4F

  –  FUNCTIONING  OF  OUTPUT  OUT  4  DIGITAL  TYPE:  Equal 

to “O1F” but referred to OUT4. 

GROUP  “ 

]

AL1” (PARAMETERS RELATIVE TO ALARM AL1):

These permit setting of the process alarm AL1 function. 
OAL1

 – OUTPUT WHERE ALARM AL1 IS ADDRESSED: It defines 

to which output the alarm AL1 has to be addressed. 

AL1t

  –  ALARM  AL1  TYPE:  permits  the  choice  of  behaviour  for 

alarm A1, by 3 different selections:   
=  LoAb  –  ABSOLUTE  LOW  ALARM  :  The  alarm  is activated when 
the process value goes below the alarm threshold set on parameter 
"AL1". 
=  HiAb  -  ABSOLUTE  HIGH  ALARM:  The  alarm  is  activated  when 
the process value goes above the alarm threshold set on parameter 
"AL1". 
=  LHAb  -  ABSOLUTE  BAND  ALARM:  The  alarm  is  activated when 
the process value goes below the alarm threshold set on parameter 
"AL1L" or goes higher than alarm set on parameter "AL1H". 

Ab1

 – ALARM AL1 FUNCTION: This permits definition of alarm AL1 

functions, by entering a number between 0 and 15. The number to 
be  programmed,  that  corresponds  to  the  desired  function,  is 
obtained adding the values reported in the following description : 

ALARM BEHAVIOUR AT SWITCH ON: 
+0  =  NORMAL  BEHAVIOUR:  The  alarm  is  always  activated  when
there are alarm conditions.
+1  =  ALARM  NOT  ACTIVATED  AT  SWITCH  ON:  If,  at  switch  on,
the instrument is in alarm condition, the alarm is not activated. It will
be  activated  only  when  the  process  value  goes  beyond  and  then
returns to alarm conditions.
ALARM DELAY:
+0  =  ALARM  NOT  DELAYED:  The  alarm  is  immediately  activated
when the alarm condition occurs.
+2  =  ALARM  DELAYED:  When  the  alarm  condition  occurs,  delay
counting  starts  as  programmed  on  par.  “ALnd”  (expressed  in  sec.)
and the alarm will be activated only after this time has elapsed.
ALARM LATCH: :
+ 0  =  ALARM  NOT  LATCHED:  The  alarm  remains  active  in  alarm
conditions only.
+ 4  =  ALARM  LATCHED:  The  alarm  is  active  in  alarm  conditions
and remains active even if these conditions no longer exist, until the
correctly programmed key “U” (“USrb”=Aac) has been pushed
ALARM AKNOWLEDGEMENT: :
+ 0  =  ALARM  NOT  AKNOWLEDGED:  The  alarm  remains  always
active in alarm conditions.
+ 8  =  ALARM  AKNOWLEDGED:  The  alarm  is  active  in  alarm
conditions  and  can  be  deactivated  through  key  “U”  if  properly
programmed (“USrb”=ASi), also if alarm conditions still exist.

AL1

 – ALARM AL1 THRESHOLD : Alarm AL1 threshold for low and

high alarms.

AL1L

  –  LOW  ALARM  AL1  :  Alarm  AL1  low  threshold  when  the

alarm  is  a band type or minimum set of AL1 alarm threshold when
the alarm is low or high type.

AL1H

  –  HIGH  ALARM  AL1:  Alarm  AL1  high  threshold  when  the

alarm is a band type or maximum set of AL1 alarm threshold when
the alarm is low or high type.

HAL1  - 

ALARM  AL1  HYSTERESIS:  Asymmetrical  semi-band

relative to alarm AL1 threshold which defines the deactivation value
of alarm AL1.

AL1d

  –  ACTIVATION  DELAY  OF  ALARM  AL1:  This  permits

definition of  alarm delay activation AL1 when the delay function on
par. “Ab1” is activated.

AL1i

  –  ALARM  AL1  ACTIVATION  IN  CASE  OF  MEASUREMENT

ERROR: This permits a definition of measurement error conditions,
i.e whether the alarm has to be active ("yES") or not ("no").

GROUP “ 

]

AL2” (PARAMETERS RELATIVE TO ALARM AL2):

These permit the setting of the process alarm AL2 functions. 
OAL2

  -  OUTPUT  WHERE  ALARM  AL2  IS  ADDRESSED:  this 

defines on which output the alarm AL2 has to be addressed. 

AL2t

  -  ALARM  AL2  TYPE:  Similar  to  “AL1t”  but  referring  to  alarm 

AL2. 

Ab2

 - ALARM AL2 FUNCTIONING: Similar to “Ab1t” but referring to 

alarm AL2

AL2

  -  ALARM  AL2  THRESHOLD  :  Similar  to  “AL1”  but  referring  to 

alarm AL2

AL2L

 - LOW ALARM AL2 : Similar to “AL1L” but referring to alarm 

AL2

AL2H

 - HIGH ALARM AL2 : Similar to “AL1H” but referring to alarm 

AL2. 

HAL2  - 

ALARM  AL2  HYSTERESIS:  Similar  to  “HAL1”  but  referring 

to alarm AL2. 

AL2d

 - ACTIVATION DELAY OF ALARM AL2: Similar to “AL1d” but 

referring to alarm AL2. 

AL2i

  -  ALARM  AL2  ACTIVATION  IN  CASE  OF  MEASUREMENT 

ERROR: Similar to “AL1i” but referring to alarm AL2. 

GROUP “ 

]

AL3” (PARAMETERS RELATIVE TO ALARM AL3):

These permit the setting of the process alarm AL3. 
OAL3

 - OUTPUT WHERE ALARM AL3 IS ADDRESSED: It defines 

on which output the alarm AL3 has to be addressed. 

AL3t

  -  ALARM  AL3  TYPE:  Similar  to  “AL1t”  but  referring  to  alarm 

AL3. 

Ab3

 - ALARM AL3 FUNCTIONING: Similar to “Ab1t” but referring to 

alarm AL3

Summary of Contents for TLI40

Page 1: ...6 PROBLEMS MAINTENANCE AND GUARANTEE 6 1 ERROR SIGNALLING 6 2 CLEANING 6 3 GUARANTEE AND REPAIRS 7 TECHNICAL DATA 7 1 ELECTRICAL DATA 7 2 MECHANICAL DATA 7 3 MECHANICAL DIMENSIONS PANEL CUT OUT AND MO...

Page 2: ...value has been programmed push key P once more the new value will be memorised and the display will show only the code of the selected parameter By using the UP or DOWN keys it is then possible to se...

Page 3: ...ked as instrument disconnecting device which interrupts the power supply to the equipment It is also recommended that all the electrical circuits connected to the instrument must be protect properly u...

Page 4: ...ument is switched on by using the U key that has been suitably programmed see par U key with function USrb r Pic or through the suitably programmed digital input see par digital input with function dI...

Page 5: ...d in sec and the alarm will be activated only after the elapsing of that time ALARM LATCH the alarm output may behave in two different ways depending on the value added to par Abn 0 ALARM NOT LATCHED...

Page 6: ...eter input it is possible to set the zero value with this function By closing the contact connected to the digital input assuming the value measured in that instant as 0 r P0P For the instruments equi...

Page 7: ...tput 3 Par Description Range Def Note 20 O3F Functioning of output 3 ALno ALnc Ser OFF ALno Group O4 parameters relative to output 4 Par Description Range Def Note 21 O4F Functioning of output 4 ALno...

Page 8: ...to a high value when the material to be measured is particularly light reflective and reduce it when the surface is especially dark non reflective keeping in mind however that for most materials the r...

Page 9: ...ARM The alarm is activated when the process value goes below the alarm threshold set on parameter AL1L or goes higher than alarm set on parameter AL1H Ab1 ALARM AL1 FUNCTION This permits definition of...

Page 10: ...r the instruments equipped with potentiometer input with this function it is possible to set the points of measure of the potentiometer by means of an auto ranging procedure through which the paramete...

Page 11: ...ection class against electric shock Class II for Front panel Insulation Reinforced insulation between the low voltage section supply and relay outputs and the front panel Reinforced insulation between...

Page 12: ...99 99 99 1 999 9 999 0 50 mV HCFG UoLt SEnS 0 50 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 0 60 mV HCFG UoLt SEnS 0 60 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 12 60 mV HCFG UoLt SEnS 12 60...

Reviews: