ASCON TECNOLOGIC - TLI 40 - OPERATING INSTRUCTIONS - 

PAG. 5

"Abn"

 – ALARM CONFIGURATION 

“ALn”

 – ALARM THRESHOLD  

“ALnL”

  –  LOW  ALARM  THRESHOLD  (for  band  alarm)  OR 

MINIMUM  SET  OF  ALn  ALARM  THRESHOLD  (for  low  or  high 
alarm) 

“ALnH”

  -  HIGH  ALARM  THRESHOLD  (for  band  alarm)  OR 

MAXIMUM  SET  OF  ALn  ALARM  THRESHOLD  (for  low  or  high 
alarm) 

“HALn” - 

ALARM HYSTERESIS 

“ALnd”

 – ALARM ACTIVATION DELAY (in sec.) 

"ALni"

 

– 

ALARM 

BEHAVIOUR 

IN 

THE 

EVENT 

OF 

MEASUREMENT ERROR 

"ALnt"  –  ALARM  TYPE  :

    the  alarm  output  can  behave  in  six 

different ways.

 

LoAb = ABSOLUTE LOW ALARM: The alarm is activated when the 
process  value  goes  below  the  alarm  threshold  set  on  parameter 
"ALn”. With this mode is possible to program the minimum and the 
maximum set  of  “ALn” by “ALnL” and “ALnH” parameters.

HiAb = ABSOLUTE HIGH ALARM: The alarm is activated when the 
process  value  goes  higher  than  the  alarm  threshold    set  on 
parameter  "ALn".  With  this  mode  is  possible  to  program  the 
minimum  and  the  maximum  set    of    “ALn”  by  “ALnL”  and  “ALnH” 
parameters. 

LHAb  =  ABSOLUTE  BAND  ALARM:  The  alarm  is  activated  when 
the process value goes under the alarm threshold set on parameter 
"ALnL"  or  goes  higher  than  the  alarm  threshold  set  on  parameter 
"ALnH". 

"

Abn" - ALARM CONFIGURATION:

 This parameter can assume a 

value between 0 and 15. 
The number to be set, which will correspond to the function desired, 
is  obtained  by  adding  the  values  reported  in  the  following 
descriptions : 
ALARM  BEHAVIOUR  AT  SWITCH  ON:  the  alarm  output  may 
behave in two different ways, depending on the value added to par. 
“Abn”. 
+0  =  NORMAL  BEHAVIOUR:  The  alarm  is  always  activated  when
there are alarm conditions.
+1 = ALARM NOT ACTIVATED AT SWITCH ON: If, when switched
on, the instrument is in alarm condition, the alarm is not activated. It
will  be  activated  only  when  the  process  value  is  in  non-alarm
conditions  and then back in alarm conditions.

ALARM DELAY:  the alarm output may behave in two different ways 
depending on the value added to par. “Abn”. 
+0  =  ALARM  NOT  DELAYED:  The  alarm  is  immediately  activated
when the alarm condition occurs.

+2  =  ALARM  DELAYED:  When  the  alarm  condition  occurs,  delay
counting begins, as programmed on par. “ALnd” (expressed in sec.)
and the alarm will be activated only after the elapsing of that time.
ALARM  LATCH:  :    the  alarm  output  may  behave  in  two  different
ways depending on the value added to par. “Abn”.
+ 0  =  ALARM  NOT  LATCHED:  The  alarm  remains  active  in  alarm
conditions only.
+ 4  =  ALARM  LATCHED:  The  alarm  is  active  in  alarm  conditions
and remains active even when these conditions no longer exist, until
the correctly programmed key “U”, (“USrb”=Aac) has been pushed.

ALARM  AKNOWLEDGEMENT:  :    the  alarm  output  may  behave  in 
two different ways depending on the value added to par. “Abn”. 
+ 0  =  ALARM  NOT  AKNOWLEDGED:  The  alarm  always  remains
active in alarm conditions.
+ 8  =  ALARM  AKNOWLEDGED:  The  alarm  is  active  in  alarm
conditions  and  can  be  deactivated  by  key  “U”  if  properly
programmed (“USrb”=ASi), and also if alarm conditions still exist.

"ALni"  -  ALARM  ACTIVATION  IN  CASE  OF  MEASUREMENT 
ERROR:

 This allows one to establish how the alarm have behave in 

the  event  of  a  measurement  error  (yES=alarm  active;  no=alarm 
deactivated). 

4.4.2 - ALARMS HYSTERESIS

 

The  alarm  function  depend  s  on  alarm  hysteresis    (par.  "HALn"), 
which works in asymmetric way. 
In  the  event  of  low  alarm,  the  alarm  will  be  activated  when  the 
process  value  goes  below  the  alarm  threshold  value  and  will  be 
deactivated  when  it  goes  above  the  alarm  threshold  +  "HALn"  ;  in 
case  of  high  alarm,  the  alarm  will  be  activated  when  the  process 
value goes above the alarm threshold value and will be deactivated 
when it goes below the alarm threshold  - "HALn". 

For the band alarms, the example of the low alarm is applicable to 
the  low  threshold  ("ALnL")  while  the  example  of  the  high  alarm  is 
applicable to the high threshold ("ALnH"). 

4.5 - FUNCTIONING OF KEY “U”

 

The function of key “U” can be set through par. 

“USrb”

 contained in 

the group “

]

PAn”.

The parameter can be programmed as : 

= noF

 : no function 

= Aac

 : Pushing the key for 1 sec. at least, it is possible to 

acknowledge the alarm. (see par. 4.4.1) 

= ASi 

: Pushing the key for 1 sec. at least, it is possible to 

acknowledge an active alarm (see par. 4.4.1) 

=

 

HoLd

: Pushing the key the measurement taken at that moment is 

blocked  (N.B.:  not  the  reading  on  the  display,  therefore  the 
indication may stabilise itself with a delay that is proportional to the 
measuring  filter).  With  the  hold  function  turned  on,  the  instrument 
carries  out  control  according  to  the  memorised  measurement. 

Summary of Contents for TLI40

Page 1: ...6 PROBLEMS MAINTENANCE AND GUARANTEE 6 1 ERROR SIGNALLING 6 2 CLEANING 6 3 GUARANTEE AND REPAIRS 7 TECHNICAL DATA 7 1 ELECTRICAL DATA 7 2 MECHANICAL DATA 7 3 MECHANICAL DIMENSIONS PANEL CUT OUT AND MO...

Page 2: ...value has been programmed push key P once more the new value will be memorised and the display will show only the code of the selected parameter By using the UP or DOWN keys it is then possible to se...

Page 3: ...ked as instrument disconnecting device which interrupts the power supply to the equipment It is also recommended that all the electrical circuits connected to the instrument must be protect properly u...

Page 4: ...ument is switched on by using the U key that has been suitably programmed see par U key with function USrb r Pic or through the suitably programmed digital input see par digital input with function dI...

Page 5: ...d in sec and the alarm will be activated only after the elapsing of that time ALARM LATCH the alarm output may behave in two different ways depending on the value added to par Abn 0 ALARM NOT LATCHED...

Page 6: ...eter input it is possible to set the zero value with this function By closing the contact connected to the digital input assuming the value measured in that instant as 0 r P0P For the instruments equi...

Page 7: ...tput 3 Par Description Range Def Note 20 O3F Functioning of output 3 ALno ALnc Ser OFF ALno Group O4 parameters relative to output 4 Par Description Range Def Note 21 O4F Functioning of output 4 ALno...

Page 8: ...to a high value when the material to be measured is particularly light reflective and reduce it when the surface is especially dark non reflective keeping in mind however that for most materials the r...

Page 9: ...ARM The alarm is activated when the process value goes below the alarm threshold set on parameter AL1L or goes higher than alarm set on parameter AL1H Ab1 ALARM AL1 FUNCTION This permits definition of...

Page 10: ...r the instruments equipped with potentiometer input with this function it is possible to set the points of measure of the potentiometer by means of an auto ranging procedure through which the paramete...

Page 11: ...ection class against electric shock Class II for Front panel Insulation Reinforced insulation between the low voltage section supply and relay outputs and the front panel Reinforced insulation between...

Page 12: ...99 99 99 1 999 9 999 0 50 mV HCFG UoLt SEnS 0 50 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 0 60 mV HCFG UoLt SEnS 0 60 1999 9999 199 9 999 9 19 99 99 99 1 999 9 999 12 60 mV HCFG UoLt SEnS 12 60...

Reviews: