3 TECHNICAL CHARACTERISTICS
3.1 Technical specifications
Case:
Plastic, self-extinguishing degree: V-0 according to UL 94;
Front protection:
IP65 (with the optional panel gasket is
mounted) for indoor locations according to EN 60070-1;
Terminals protection:
IP20 according to EN 60070-1;
Installation:
Panel mounting;
Terminal block:
16 M3 screw terminals for cables of
0.25... 2.5 mm
2
(AWG22... AWG14) with connection diagram;
Dimensions:
48 x 96, depth 75.9 mm, (1.77 x 3.78 x 2.99 in.)
Panel cutout:
45
(+0.6)
x 89
(+0.6)
mm [1.78
(+0.023)
x 3.5
(+0.023)
in.]
Weight:
160 g max..
Power supply:
• 24 VAC/DC (±10% of the nominal value);
• 100... 240 VAC (-15... +10% of the nominal value);
Power consumption:
5 VA max.;
Insulation voltage:
• Simple insulation (models with Power supply 24 VAC/DC);
• 3000 Vrms according to EN 61010-1 (models with
100... 240 VAC/DC of Power Supply),
Display updating time:
500 ms;
Sampling time:
130 ms;
Resolution:
30000 counts;
Total Accuracy:
±0.5% F.S.V. ±1 digit @ 25°C of room
temperature;
Temperature drift:
It is part of the global accuracy;
Operating temperature:
0... 50°C (32... 122°F);
Storage temperature:
-30... +70°C (-22... +158°F);
Humidity:
20... 85% RH, not condensing.
Electromagnetic compatibility and safety requirements
Compliance:
• EMC Directive (EN 61326-1),
• Safety Directive (EN 61010-1);
Installation category:
II;
Pollution category:
2.
4 HOW TO ORDER
Model
KX5P = Controller, Programmer and set point setter
Power supply
H = 100... 240 VAC
L = 24 VAC/DC
Analoue input + Digital Input DI1 (standard)
C = J, K, R, S, T, PT100, mV, mA, V
E = J, K, R, S, T, PTC, NTC, mV, mA, V
Output 1
I = 0/4... 20 mA, 0/2... 10 V isolated linear output
O = VDC for SSR
R = Relay SPST 4 A (resistive load)
Output 3
- = Not available
M = Relay SPST 2 A
(
servomotor drive
)(note)
O = VDC for SSR
R = Relay SPST 2 A (resistive load)
Input/Output 4
D = Output 4 (VDC for SSR)/Pow. Supply/Dig. Input DI2
Serial Communications
- = TTL Modbus
S = RS485 TTL Modbus
Connection type
- = Standard (screw terminals not removable)
E = Removable screw terminals
M = Removable spring terminals
N = Removable terminals (the fixed part only)
Output 2
- = Not available
M = Relay SPST 2 A
(
servomotor drive
)(note)
O = VDC for SSR
R = Relay SPST 2 A (resistive load)
Note:
For servomotor drive, both
Output 2
and
Output 3
codes must be selected as “
M
”.