Ascon Tecnologic - KX5P Line - ENGINEERING MANUAL - PAG. 33
no. Param.
Description
Dec.
Point
Values
Default
22
o3F
Out 3 function
0
NonE Output not used;
H.rEG Heating output;
c.rEG Cooling output;
AL
Alarm output;
P.End Program end indicator;
P.HLd Program hold indicator;
P.uit
Program wait indicator;
P.run Program run indicator;
P.Et1 Program Event 1;
P.Et2 Program Event 2;
or.bo Out-of-range or Burnout indicator;
P.FAL Power failure indicator;
bo.PF Out-of-range, Burnout and Power failure indicator;
St.bY Stand by status indicator;
diF.1 Out3 repeats the digital input 1 status;
diF.2 Out3 repeats the digital input 2 status;
on
Out3 always ON;
riSP
Inspection request.
AL
23
o3AL
Alarms linked up with the out 3
0
0... 63:
+1 Alarm 1;
+2 Alarm 2;
+4 Alarm 3;
+8 Loop break alarm;
+16 Sensor Break;
+32 Overload on output 4.
AL2
24
o3Ac
Out 3 action
0
dir
Direct action;
rEU
Reverse action;
dir.r
Direct with reversed LED;
ReU.r Reverse with reversed LED.
dir
25
o4F
Out 4 function
0
NonE Output not used;
H.rEG Heating output;
c.rEG Cooling output;
AL
Alarm output;
P.End Program end indicator;
P.HLd Program hold indicator;
P.uit
Program wait indicator;
P.run Program run indicator;
P.Et1 Program Event 1;
P.Et2 Program Event 2;
or.bo Out-of-range or Burnout indicator;
P.FAL Power failure indicator;
bo.PF Out-of-range, Burnout and Power failure indicator;
St.bY Stand by status indicator.
AL
26
o4AL
Alarms linked up with the out 4
0
0... 63:
+1 Alarm 1;
+2 Alarm 2;
+4 Alarm 3;
+8 Loop break alarm;
+16 Sensor Break;
+32 Overload on output 4.
AL1 +
L2
27
o4Ac
Out 4 action
0
dir
Direct action;
rEU
Reverse action;
dir.r
Direct with reversed LED;
ReU.r Reverse with reversed LED.
dir
]
AL1 group
no. Param.
Description
Dec.
Point
Values
Default
28
AL1t
Alarm 1 type
0
nonE Alarm not used;
LoAb Absolute low alarm;
HiAb Absolute high alarm;
LHAo Absolute band alarm, alarm ON outside the band;
LHAi Absolute band alarm, alarm ON inside the band;
SE.br Sensor Break;
LodE Deviation low alarm (relative);
HidE Deviation high alarm (relative);
LHdo Relative band alarm, alarm ON outside the band;
LHdi Relative band alarm, alarm ON inside the band.
HiAb
29
Ab1
Alarm 1 function
0
0... 15:
+1 Not active at power up;
+2 Latched alarm (manual reset);
+4 Acknowledgeable alarm;
+8 Relative alarm not active at set point change.
0