background image

Ascon Tecnologic - K Series - ENGINEERING MANUAL - Vr. 9.0

 PAG. 11

[29] HAL1 - Alarm 1 hysteresis

Available: 

When [24] AL1t is different from 

nonE

 or  

[24] AL1t is different from 

SE.br

.

Range: 

1... 9999 engineering units.

Notes: 1. 

The hysteresis value is the difference between 
the Alarm threshold value and the point the where 
the Alarm automatically resets.

2. 

When the alarm threshold plus or minus the 
hysteresis is out from the input range, the 
instrument will not be able to reset the alarm. 

Example:

 Input range from 0 to 1000 (mBar); 

- Set point equal to 900 (mBar); 
- Deviation low alarm equal to 50 (mBar); 
- Hysteresis equal to 160 (mBar); 
the theoretical reset point is 900 - 50 + 160 = 
1010 (mBar) but this value is out of range. 
The reset can be made only by turning the instru-
ment 

OFF

, removing the condition wich generated 

the alarm and turning the instrument ON again.

3. 

All band alarms use the same hysteresis value 
for both thresholds.

4. 

When the hysteresis of a band alarm is bigger 
than the programmed band, the instrument will 
not be able to reset the alarm. 

Example:

 Input range 0... 500 (°C); 

- Set point equal to 250 (°C); 
- Relative band alarm; 
- Low threshold equal to 10 (°C); 
- High threshold equal to 10 (°C); 
- Hysteresis equal to 25 (°C).

[30] AL1d - Alarm 1 delay

Available: 

When [24] AL1t is different form 

nonE

.

Range: 

From oFF (0) to 9999 seconds.

Note: 

The alarm goes ON only when the alarm condition 
persists for a time longer than [30] AL1d time but the 
reset is immediate.

[31] AL1o - Alarm 1 enabling during Stand-by mode 

and out of range indications

Available: 

When [24] AL1t is different from 

nonE

.

Range: 

0 = 

Never;

1 = 

During stand by;

2 = 

During overrange and underrange;

3 = 

During overrange, underrange and stand-by.

]

AL2 Group - Alarm 2 parameters

[32] AL2t - Alarm 2 type

Available: 

Aways.

Range:  • 

When one or more outputs are programmed as 
control output:

nonE =  Alarm not used;
LoAb =  Absolute low alarm;
HiAb =  Absolute high alarm:
LHAb =  Absolute band alarm:
SE.br =  Sensor break;
LodE =  Deviation low alarm (relative);
HidE =  Deviation high alarm (relative);
LHdE =  Relative band alarm.

• 

When no output is programmed as control output:

nonE =  Alarm not used;
LoAb =  Absolute low alarm;
HiAb =  Absolute high alarm;

LHAb =  Absolute band alarm;
SE.br =  Sensor break.

Note: 

The relative alarm are “relative” to the current set point 
(this may be different from the Target setpoint if you 
are using the ramp to set point function).

[33] Ab2 - Alarm 2 function

Available: 

When [32] AL2t is different from 

nonE

.

Range: 

0... 15 with the following rule:
+1 = 

Not active at Power ON;

+2 = 

Latched alarm (manual reset);

+4 = 

Acknowledgeable alarm.

+8 = 

Relative alarm not active at set point change.

Example:

  Setting Ad2 equal to 5 (1 + 4) the alarm 2 will be 

“Not active at Power ON” and “Acknowledgeable”.

Note: 

For other details see [25] Ab1 parameter.

[34] AL2L - For High and low alarms, it is the low 

limit of the AL2 threshold

 

- For band alarm, it is low alarm threshold

Available: 

When [32] AL2t is different from 

nonE

 or  

[32] AL2t is different from 

SE.br

.

Range: 

From - 1999 to [35] AL2H engineering units.

[35] AL2H - For High and low alarms, it is the high 

limit of the AL2 threshold

 

- For band alarm, it is high alarm threshold

Available: 

When [32] AL2t is different from 

nonE

 or  

[32] AL2t is different from 

SE.br

.

Range: 

From [34] AL2L to 9999 engineering units.

[36] AL2 - Alarm 2 threshold

Available: 

When: 
- [32] AL2t = LoAb Absolute low alarm; 
- [32] AL2t = HiAb Absolute high alarm; 
- [32] AL2t = LodE Deviation low alarm (relative); 
- [32] AL2t = LidE Deviation high alarm (relative);

Range: 

From [34] AL2L to [35] AL2H  engineering units.

[37] HAL2 - Alarm 2 hysteresis

Available: 

When [32] AL2t is different from 

nonE

 or  

[32] AL2t is different from 

SE.br

.

Range: 

1... 9999 engineering units.

Note: 

For other details see [29] HAL1 parameter.

[38] AL2d - Alarm 2 delay

Available: 

When [32] AL2t is different form 

nonE

.

Range: 

From oFF (0) to 9999 seconds

Note: 

The alarm goes ON only when the alarm condition 
persist for a time longer than [38] AL2d time but the 
reset is immediate.

[39] AL2o  - Alarm 2 enabling during Stand-by mode 

and out of range indications

Available: 

When [32] AL2t is different from 

nonE

.

Range: 

0 = 

Never;

1 = 

During stand by;

2 = 

During overrange and underrange;

3 = 

During overrange, underrange and stand-by.

]

AL3 Group - Alarm 3 parameters

[40] AL3t - Alarm 3 type

Available: 

Always.

Range:  • 

When one or more outputs are programmed as 
control output:

nonE =  Alarm not used;

Summary of Contents for K48

Page 1: ...n 5 The ambient temperature is in accordance with the operative temperature 0 50 C 6 The relative humidity is in accordance with the instrument specifications 20 85 The instrument can be mounted on pa...

Page 2: ...ut circuit Current injection 25 A Line resistance Not compensated 2 2 5 V and mV Input mV V _ _ 2 1 Input impedance 1 M Accuracy 0 5 of Span or 1 dgt 25 C 2 2 6 mA Input 0 4 20 mA input wiring for pas...

Page 3: ...te This output is not isolated A double or reinforced isolation between instrument output and power supply must be assured by the external solid state relay 2 3 3 Output 3 OP3 Relay Output 6 5 NO C Co...

Page 4: ...splay updating time 500 ms Sampling time 130 ms Resolution 30000 counts Total accuracy 0 5 F S V 1 digit 25 C of room temperature Electromagnetic compatibility and safety requirements Compliance Direc...

Page 5: ...rol output is equal to 0 and can be manually modified by and buttons Stand by mode St bY The display alternately shows the measured value and the message St bY or od The instrument does not perform an...

Page 6: ...complete list of the default parameter is available in Appendix A 5 7 All parameters configuration In the following pages we will describe all the parameters of the instrument However the instrument...

Page 7: ...instrument will use the Zero value 2 When ON OFF control is programmed and an out of range is detected the instrument will perform the safety output value using a fixed cycle time equal to 20 seconds...

Page 8: ...tion is cyclic SP1 SP2 SP3 SP4 out Group Output parameters 12 o1F Out 1 function Available Always Range nonE Output not used With this setting Out 1 status can be driven directly from serial link H rE...

Page 9: ...Power failure indicator bo PF Out of range burn out and Power Failure indicator diF1 The output repeates the digital input 1 status diF2 The output repeates the digital input 2 status St By Stand By s...

Page 10: ...n other words when the initial alarm condition disappears PWR ON AL1 PV time off off Ab1 1 Ab1 0 off off ON ON ON 2 A Latched alarm manual reset is an alarm that remains active even if the conditions...

Page 11: ...s programmed as control output nonE Alarm not used LoAb Absolute low alarm HiAb Absolute high alarm LHAb Absolute band alarm SE br Sensor break Note The relative alarm are relative to the current set...

Page 12: ...for a time longer than 46 AL3d time but the reset is immediate 47 AL3o Alarm 3 enabling during Stand by mode and out of range indications Available When 40 AL3t ia different from nonE Range 0 Never 1...

Page 13: ...if the set point is close to the ambient temperature 2 The fast type auto tune is suitable when The process is very slow and you want to be operative in a short time When an high overshoot is not acc...

Page 14: ...oling gain The instrument uses the same PID parameter set for heat and for cool action but the efficiency of the two actions are usually different This parameter allows to define the ratio between the...

Page 15: ...imit is applied to the cooling action the soft start function will be aborted when the measured value is lower than or equal to SS tH parameter SP Group Set point parameters The SP group will be avail...

Page 16: ...lers The Slave zones use it as a set point trim The first zone is the master zone and it uses a set point equal to 210 C The second zone has a local set point equal to 45 C The third zone has a local...

Page 17: ...tatus of two events An event can drive an output and make an action during one or more specific program steps Some additional parameters allow to define the time scale the automatic RUN conditions and...

Page 18: ...t 2 00 00 off off off off 10 00 on off off off 01 00 off on off off 11 00 on on off off Display Ramp Soak Event 1 Event 2 Event 1 Event 2 00 10 off off on off 10 10 on off on off 01 10 off on on off 1...

Page 19: ...1 parameter 113 Pr St Program status Available When 89 Pr F is different from nonE Range run Program Run HoLd Program Hold rES Program reset Note This parameter allows to manage program execution by a...

Page 20: ...is equal to in finite the limit is always active and it can be used also when ON OFF control is selected 118 AdE Bargraph deviation Available Always Range oFF Bargraph not used 1 9999In engineering u...

Page 21: ...shold not used 1 999 days 1 999 hours CAL Group User calibration group This function allows to calibrate the complete measuring chain and to compensate the errors due to Sensor location Sensor class s...

Page 22: ...L1 AL2 A 6 AL2 Pb A 7 Pb Int A 8 Int dEr A 9 dEr Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds 2 The display alternately shows PASS and 0 3 By and buttons set a pas...

Page 23: ...and the parameter modification procedure is closed When you desire to remove the time out e g for the first configuration of an instrument you can use a password equal to 1000 plus the programmed pas...

Page 24: ...preceded by a P letter P84 3 4 Push button again When the wattmeter function is running the display shows U followed by the measured energy Note The energy calculation will be in accordance with the 1...

Page 25: ...set manual modes during self tune execution the self tune function will be aborted 4 During manual mode all functions not related with the control wattmeter indipendent timer worked time etc continue...

Page 26: ...ment to our company The faulty product must be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of altern...

Page 27: ...and Under our C 0 9 oPE Safety output value 0 100 100 0 C 0 10 diF1 Digital input 1 function 0 oFF No function 1 Alarm Reset 2 Alarm acknowledge ACK 3 Hold of the measured value 4 Stand by mode 5 HEAt...

Page 28: ...k alarm 16 Sensor break burn out AL1 A 17 14 o1Ac Out 1 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse with reversed LED dir C 0 15 o2F Out 2 function 0 Non...

Page 29: ...r break burn out AL2 A 23 20 o3Ac Out 3 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse with reversed LED dir C 0 21 o4F Out 4 function 0 NonE Output not use...

Page 30: ...and by mode 0 0 Never 1 During stand by 2 During overrange and underrange 3 During overrange underrange and stand by no C 0 AL2 Group Alarm 2 Parameters no Para meter Description Dec Range Default Vis...

Page 31: ...0 LbA Group Loop Break Alarm Parameters no Para meter Description Dec Range Default Vis Promo 48 LbAt LBA time 0 From 0 oFF to 9999 s oFF C 0 49 LbSt Delta measure used by LBA during Soft start dP Fro...

Page 32: ...om 0 00 oFF to 8 00 inF hh mm oFF C 0 71 SStH Threshold for soft start disabling dP 1999 9999 E U 9999 C 0 SP Group Set Point Parameters no Para meter Description Dec Range Default Vis Promo 72 nSP Nu...

Page 33: ...e end program indication 2 From 0 00 oFF to 100 00 inF minutes and seconds oFF A 72 93 Pr S1 Set point of the first soak dP From SPLL to SPHL 0 A 73 94 Pr G1 Gradient of the first ramp 1 0 1 1000 0 in...

Page 34: ...r time down PErc Percent of the power output used during soft start when the soft start time is equal to in finite the limit is always active can be used also when ON OFF control is selected nonE A 95...

Page 35: ...urs with threshold nonE A 97 127 UoLt Nominal voltage of the load 0 1 999 Volt 230 A 98 128 cur Nominal current of the load 0 1 999 A 10 A 99 129 h Job Threshold of the worked hours days 0 From 0 oFF...

Page 36: ...Ascon Tecnologic K Series ENGINEERING MANUAL Vr 9 0 PAG 36...

Reviews: