7.  OPERATIVE MODES

As we said at paragraph 5.1, when the instrument is 
powered, starts immediately to work accordingly to the 
stored parameters value.
In other words, the instrument has only one status, the “run 
time” status.
During “run time” we can force the instrument to operate in 
three different modes: Automatic mode, Manual mode or 
Stand by mode.

 

In Automatic mode the instrument drives automatically the 
control output according to the parameter value set and 
the setpoint/measured value.

 

In Manual mode the instrument shows the measured value 
and allows you to set manually the output power. 
No Automatic action will be made.

 

In stand by mode the instrument operates as an indicator. It 
shows the measured value and forces the outputs to zero.

As we have seen, it is always possible to modify the value 
assigned to a parameter independently from the operative 
mode selected.

7.1  how to enter the “Operator level”

The instrument is showing the “Standard display”.

1. 

Press the 

 button;

2. 

The instrument shows alternately the acronym of the first 
parameter promoted to this level and its value;

3. 

With the 

 and 

 buttons assign to this parameter the 

desired value;

4. 

Press the 

 button in order to store the new value and 

go to the next parameter;

5. 

When you want to reurn to the “Standard display” push 
the 

 button for more than 5 seconds.

Note: 

The parameter modification of the Operator level 
is subject to a time out.  If no button is pressed for 
more than 10 seconds, the instrument returns to 
the “Standard display” and the new value of the last 
selected parameter will be lost.

7.2  how to enter the “Limited Access Level”

The instrument is showing the “Standard display”.

1. 

Press the 

 button for more than 5 seconds;

2. 

The display alternately shows 

PASS

 and 

0

;

3. 

With the 

 and 

 buttons set the value assigned to 

[114] PAS2 (Level 2 password);

Notes: 1. 

The factory default password for configuration 
parameters is equal to 20.

2. 

All parameter modification are protected by a 
time out. If no button is pressed for more than 10 
second the instrument returns automatically to 
the Standard display, the new value of the last 
selected parameter is lost and the parameter 
modification procedure is closed.
When you desire to remove the time out (e.g. for 
the first configuration of an instrument) you can use 
a password equal to 1000 plus the programmed 
password (e.g. 1000 + 20 [default] = 1020).
It is always possible to manually End the param-
eter configuration procedure (see below).

3. 

During parameter modification the instrument 
continues to perform the control.
In certain conditions (e.g. when a parameter 
change can produces a heavy bump to the 
process) it is advisable to temporarily stop the 
controller from controlling during the program-
ming procedure (its control output will be Off). A 
password equal to 2000 + the programmed value 
(e.g. 2000 + 20 = 2020) will switch the control out 
off during configuration.  The control will restart 
automatically when the parameter modification 
procedure will be manually ended.

4. 

Press 

 button;

5. 

The instrument will show alternately the acronym of the 
first parameter promoted to this level and its value;

6. 

By 

 and 

 buttons assign to this parameter the 

desired value;

7. 

Press the 

 button in order to memorize the new value 

and go to the next parameter;

8. 

When you want to return to the “Standard display” push 
the 

 button for more than 5 seconds.

7.3  how to see but not modify the  

“Limited Access Parameters”

Sometime it is necessary to give to the operator the 
possibility to see the value assigned to the parameter 
promoted in the Limited Access level but it is important that 
all changes are made by autorized personnel only.
In this cases, proceed as follows:

1. 

Press the 

 button for more than 5 seconds;

2. 

The display alternately shows 

PASS

 and 

0

;

3. 

By 

 and 

 buttons set the value 

-181

;

4. 

Press 

 button;

5. 

The instrument shows alternately the acronym of the first 
parameter promoted to the level 2 and its value.

6. 

Using 

 button is possible to see the value assigned to 

all parameters present in level 2 but it will not be possible 
to modify it;

7. 

It is possible to return to the “Standard display” pushing 
the 

 button for more than 3 seconds or pushing no 

buttons for more than 10 seconds. 

7.4  Automatic Mode

7.4.1  Keyboard functions when the instrument 

is in Auto mode

 

Starts the action programmed by [116] uSrb (

 but-

ton function during RUN TIME) parameter.

 

Allows to enter the parameter modification procedures.

 

Starts the “Direct set point modification” function (see 
below).

 

Displays the “Additional information” (see below).

Summary of Contents for K48

Page 1: ...n 5 The ambient temperature is in accordance with the operative temperature 0 50 C 6 The relative humidity is in accordance with the instrument specifications 20 85 The instrument can be mounted on pa...

Page 2: ...ut circuit Current injection 25 A Line resistance Not compensated 2 2 5 V and mV Input mV V _ _ 2 1 Input impedance 1 M Accuracy 0 5 of Span or 1 dgt 25 C 2 2 6 mA Input 0 4 20 mA input wiring for pas...

Page 3: ...te This output is not isolated A double or reinforced isolation between instrument output and power supply must be assured by the external solid state relay 2 3 3 Output 3 OP3 Relay Output 6 5 NO C Co...

Page 4: ...splay updating time 500 ms Sampling time 130 ms Resolution 30000 counts Total accuracy 0 5 F S V 1 digit 25 C of room temperature Electromagnetic compatibility and safety requirements Compliance Direc...

Page 5: ...rol output is equal to 0 and can be manually modified by and buttons Stand by mode St bY The display alternately shows the measured value and the message St bY or od The instrument does not perform an...

Page 6: ...complete list of the default parameter is available in Appendix A 5 7 All parameters configuration In the following pages we will describe all the parameters of the instrument However the instrument...

Page 7: ...instrument will use the Zero value 2 When ON OFF control is programmed and an out of range is detected the instrument will perform the safety output value using a fixed cycle time equal to 20 seconds...

Page 8: ...tion is cyclic SP1 SP2 SP3 SP4 out Group Output parameters 12 o1F Out 1 function Available Always Range nonE Output not used With this setting Out 1 status can be driven directly from serial link H rE...

Page 9: ...Power failure indicator bo PF Out of range burn out and Power Failure indicator diF1 The output repeates the digital input 1 status diF2 The output repeates the digital input 2 status St By Stand By s...

Page 10: ...n other words when the initial alarm condition disappears PWR ON AL1 PV time off off Ab1 1 Ab1 0 off off ON ON ON 2 A Latched alarm manual reset is an alarm that remains active even if the conditions...

Page 11: ...s programmed as control output nonE Alarm not used LoAb Absolute low alarm HiAb Absolute high alarm LHAb Absolute band alarm SE br Sensor break Note The relative alarm are relative to the current set...

Page 12: ...for a time longer than 46 AL3d time but the reset is immediate 47 AL3o Alarm 3 enabling during Stand by mode and out of range indications Available When 40 AL3t ia different from nonE Range 0 Never 1...

Page 13: ...if the set point is close to the ambient temperature 2 The fast type auto tune is suitable when The process is very slow and you want to be operative in a short time When an high overshoot is not acc...

Page 14: ...oling gain The instrument uses the same PID parameter set for heat and for cool action but the efficiency of the two actions are usually different This parameter allows to define the ratio between the...

Page 15: ...imit is applied to the cooling action the soft start function will be aborted when the measured value is lower than or equal to SS tH parameter SP Group Set point parameters The SP group will be avail...

Page 16: ...lers The Slave zones use it as a set point trim The first zone is the master zone and it uses a set point equal to 210 C The second zone has a local set point equal to 45 C The third zone has a local...

Page 17: ...tatus of two events An event can drive an output and make an action during one or more specific program steps Some additional parameters allow to define the time scale the automatic RUN conditions and...

Page 18: ...t 2 00 00 off off off off 10 00 on off off off 01 00 off on off off 11 00 on on off off Display Ramp Soak Event 1 Event 2 Event 1 Event 2 00 10 off off on off 10 10 on off on off 01 10 off on on off 1...

Page 19: ...1 parameter 113 Pr St Program status Available When 89 Pr F is different from nonE Range run Program Run HoLd Program Hold rES Program reset Note This parameter allows to manage program execution by a...

Page 20: ...is equal to in finite the limit is always active and it can be used also when ON OFF control is selected 118 AdE Bargraph deviation Available Always Range oFF Bargraph not used 1 9999In engineering u...

Page 21: ...shold not used 1 999 days 1 999 hours CAL Group User calibration group This function allows to calibrate the complete measuring chain and to compensate the errors due to Sensor location Sensor class s...

Page 22: ...L1 AL2 A 6 AL2 Pb A 7 Pb Int A 8 Int dEr A 9 dEr Aut r A 10 Aut r Now proceed as follows 1 Push the button for more than 3 seconds 2 The display alternately shows PASS and 0 3 By and buttons set a pas...

Page 23: ...and the parameter modification procedure is closed When you desire to remove the time out e g for the first configuration of an instrument you can use a password equal to 1000 plus the programmed pas...

Page 24: ...preceded by a P letter P84 3 4 Push button again When the wattmeter function is running the display shows U followed by the measured energy Note The energy calculation will be in accordance with the 1...

Page 25: ...set manual modes during self tune execution the self tune function will be aborted 4 During manual mode all functions not related with the control wattmeter indipendent timer worked time etc continue...

Page 26: ...ment to our company The faulty product must be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of altern...

Page 27: ...and Under our C 0 9 oPE Safety output value 0 100 100 0 C 0 10 diF1 Digital input 1 function 0 oFF No function 1 Alarm Reset 2 Alarm acknowledge ACK 3 Hold of the measured value 4 Stand by mode 5 HEAt...

Page 28: ...k alarm 16 Sensor break burn out AL1 A 17 14 o1Ac Out 1 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse with reversed LED dir C 0 15 o2F Out 2 function 0 Non...

Page 29: ...r break burn out AL2 A 23 20 o3Ac Out 3 action 0 dir Direct action rEU Reverse action dir r Direct with reversed LED ReU r Reverse with reversed LED dir C 0 21 o4F Out 4 function 0 NonE Output not use...

Page 30: ...and by mode 0 0 Never 1 During stand by 2 During overrange and underrange 3 During overrange underrange and stand by no C 0 AL2 Group Alarm 2 Parameters no Para meter Description Dec Range Default Vis...

Page 31: ...0 LbA Group Loop Break Alarm Parameters no Para meter Description Dec Range Default Vis Promo 48 LbAt LBA time 0 From 0 oFF to 9999 s oFF C 0 49 LbSt Delta measure used by LBA during Soft start dP Fro...

Page 32: ...om 0 00 oFF to 8 00 inF hh mm oFF C 0 71 SStH Threshold for soft start disabling dP 1999 9999 E U 9999 C 0 SP Group Set Point Parameters no Para meter Description Dec Range Default Vis Promo 72 nSP Nu...

Page 33: ...e end program indication 2 From 0 00 oFF to 100 00 inF minutes and seconds oFF A 72 93 Pr S1 Set point of the first soak dP From SPLL to SPHL 0 A 73 94 Pr G1 Gradient of the first ramp 1 0 1 1000 0 in...

Page 34: ...r time down PErc Percent of the power output used during soft start when the soft start time is equal to in finite the limit is always active can be used also when ON OFF control is selected nonE A 95...

Page 35: ...urs with threshold nonE A 97 127 UoLt Nominal voltage of the load 0 1 999 Volt 230 A 98 128 cur Nominal current of the load 0 1 999 A 10 A 99 129 h Job Threshold of the worked hours days 0 From 0 oFF...