Ascon tecnologic e33B Operating Instructions Manual Download Page 9

Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 9

eter 

Pod

.

During the power ON delay phase, the display shows the 
indication 

od

 alternated with the normal visualization.

All these functions are disabled if the relative parameters are 
set to 

OFF

 (

oF

).

5.8 

Defrost control

The defrost control acts on the outputs configured as 

ot

 and 

dF

.

The type of defrost is set by the parameter 

ddt

:

EL

 

With electrical heating

 (or 

By stopping compres-

sor

): while defrosting, the output 

ot

 is deactivated 

while the output 

dF

 is enabled.  The defrost will be by 

Stopping compressor if not using the 

dF

 output;

in

 

With hot gas

 or 

Cycle inversion

: while defrosting 

both the 

ot

 and 

dF

 outputs are enabled:

no

 

Without compressor output conditioning

: while de-

frosting, the output 

ot

 continuous to operate in order to 

control thetemperature, also the output 

dF

 is enabled;

Et

 

With electrical heating and defrosting temperature 
control

: during defrosting, the output 

ot

 is deactivated 

while the output 

dF

 operate as evaporator temperature 

control.  In this mode the defrost lenght is by time-out 
(time 

ddE

).  During the defrost, the 

dF

 output behaves 

as an heating mode control with Set Point = 

dtE

, dif-

ferential fixed at 1°C and operates with the values of 
the 

EP

 evaporator probe.  In this functioning mode, if 

the evaporator probe is not enabled or is in error, the 
defrost behaves as with selection 

EL

 (therefore the 

output 

dF

 during defrost must always be active).

5.8.1 

Starting automatic defrosts

The automatic control of defrost occours:

 

By interval times (regular or dynamic);

 

By Evaporator temperature;

 

By continuous compressor running time.

In order to avoid unnecessary defrosting when the evapora-
tor temperature is high the 

dtS

 parameter allows to set the 

temperature related to the evaporator probe (probe config-
ured as 

EP

) under which defrosts are possible.

Therefore, in the modes indicated, if the temperature meas-
ured by the evaporator probe is higher than the temperature 
set with 

dtS

 parameter, defrosts are inhibited.

Defrost by regular interval time

As an alternative to programmable defrosts, the instrument 
allows to execute the defrosts at programmed interval time.
Through the 

ddC

 parameter, can be set the defrost interval 

counting mode:

rt

 

At real-time power-ON intervals.  The 

ddi

 interval is 

counted as the total ignition time of the instrument. 
This mode is the one currently used in the refrigera-
tion systems.

ct

 

At time intervals of the compressor operation.  The 

ddi

 interval is counted as the sum of the operating 

times of the 

ot

 output (

ot

 output activated).  This mode 

is usually used in refrigeration systems with compres-
sor stop defrosting.

cS

 

Defrost cycle at each compressor stop. The instrument 
starts a defrost cycle every time the 

ot

 output is deac-

tivated, when the Set Point is reached or at the expira-
tion of the interval set with 

ddi

 paramreter.  If 

ddi

 = 

oF

 the defrost happens only at compressor stop.

This mode is used only on particular refrigerating ma-
chines in which is required the maximum evaporator 
efficiency at each compressor cycle.

To enable automatic defrost at intervals, after setting the 

ddC

 

parameter as desired between 

rt

ct

 or 

cS

, with the ddi pa-

rameter select the time interval between the end of a defrost 
and the beginning of the next.
The time that the instrument must wait to perform the first 
defrost after power ON can be set with parameter 

dSd

.  This 

allows to perform the first defrost to a different interval from 

ddi

 time.

To force the instrument to perform a defrost cycle at each 
power ON (as long as the conditions set with parameters 

dtS

 and 

dtE

 are satisfied) set parameter 

dSd

 = 

oF

.

This allows the evaporator to be permanently defrosted, 
even when frequent interruptions to power supply occur that 
may cause the cancellation of the various defrosting cycles.
If instead it is desired  that all the defrosts are performed at 
the same interval time, set 

dSd

 = 

ddi

.

Setting 

ddi

 = 

oF the 

Automatic defrost function by interval 

is totally disabled (including the first, regardless of the time 
set to the 

dsd

 parameter).

Dynamic Defrost Intervals System

Note: 

For this function is necessary to use the evaporator 
probe.

To enable the 

Dynamic Defrost Intervals System

, program 

ddC

 = 

rt

ct

 or 

cS

 and set 

ddd

 = 

any value

.

Setting 

ddd

 = 

0

, the defrost intervals are those set by the user 

and the 

Dynamic Defrost Intervals System

 is disabled.

This mode allows to dynamically reduce the defrost interval 
counting (

ddi

 or 

dSd

 if is the first defrost), anticipating, when 

necessary, the defrost execution, all based on an algorithm that 
detects a drop in the refrigerator thermal exchange performance.
The algorithm estimates a reduction in thermal exchange 
based on the increase in temperature difference between 

Pr1

 (cell control) and evaporator probe (probe configured as 

EP

).  The result is stored by the instrument when the tem-

perature is close to the Set Point setting.
The advantage of the 

Dynamic Defrost Interval

 is the pos-

sibility to program a defrost interval time longer than normal, 
so, when necessary, the instrument has the possibility to 
anticipate the defrost.
If the system results correctly set, it is possible to avoid 
many unnecessary defrosting cycles (and therefore to obtain 
aconsistent energy saving) that may occur with normal op-
eration when, to ensure more system efficiency, the defrost-
ing interval is programmed with a time that is often too short.
With the parameter 

ddd

 - 

Defrost interval percentage reduc-

tion

 is possible to establish the percentage of reduction of 

the remaining time to start defrost when the conditions for 
the reduction happen.
Setting 

ddd

 = 

100%

 at the first increase of the stored tem-

perature difference (

> 1°

) between cell (

Pr1

) and evaporator 

(

EP

) probes a defrost starts immediately.

For correct functioning the instrument needs a first refer-
ence value of the temperature difference between cell and 
evaporator, in this way all variations to the Active Set Point 
value, to the differential 

rd

, the start of a continuous cycle 

or a defrost execution deletes this reference value and any 
reduction cannot be performed until the acquisition of a new 
reference value.

Summary of Contents for e33B

Page 1: ...ration through stopping the compressor electric heating or hot gas cycle inversion The controller is equipped with special defrost optimization functions and with other functions that can be used to o...

Page 2: ...Stand by mode this is the only lighted LED In programming mode while the parameter code is displayed the dot indicates the parameter protection level not protected lit up protected flashing and hidde...

Page 3: ...ial test keeping it pressed for 5 s In this way it is possible to access all the parameters verify and modify the parameter tPP 2 4 Customized mode parameter programming parameters programming level T...

Page 4: ...d rule must adopt all the necessary protective measures The instrument MUST NOT BE USED in dangerous environ ments flammable or explosive without adequate protections The instrument used with NTC 103A...

Page 5: ...1 A Out 3 2 1 A 60730 EN UL 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different conditions ON Means that the controller uses the control functions STAND BY Means t...

Page 6: ...always closed 5 3 Measure and display configuration With parameter iuP it is possible to select the tempera ture engineering unit and the desired measure resolution C0 C 1 C1 C 0 1 F0 F 1 F1 F 0 1 The...

Page 7: ...that is NO in normal operation then closed during the alarm AL To control an alarm that cannot be silenced through a contact that is NO in normal operation then closed during the alarm An To control a...

Page 8: ...s automatic switching between the three Normal Eco Turbo modes described at the paragraph Operating modes The time protections described in the next paragraph PP1 PP2 PP3 always work on the ot configu...

Page 9: ...a chines in which is required the maximum evaporator efficiency at each compressor cycle To enable automatic defrost at intervals after setting the ddC parameter as desired between rt ct or cS with th...

Page 10: ...related to the EP probe under which defrosts are possible Therefore in the indicated modes if the temperature meas ured by the EP probe is higher than the one set at parameter dtS and also dtE defros...

Page 11: ...emperature alarms Hi and Lo External alarm AL Door open oP The alarm functions acts on LED on the internal buzzer if present and configured by the obu parameter and on the desired output if configured...

Page 12: ...The instrument can signal an alarm external to the instrument using the digital input setting iFi 4 or 5 The instrument signals the alarm turning ON the alarm LED and display ing AL label alternated...

Page 13: ...f some instruments which need to have the same parameters con figuration or to keep a copy of the parameters settings of an instrument and allow its rapid retransmission The same device allows to conn...

Page 14: ...ck 3 Open Door with Fan and Output Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 2 15 iti Digital Input Delay oF D...

Page 15: ...n disabled 1 59 s 1 99 min 5 42 FtF Fan time deactivation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min oF 43 FFL High temperature fan deactivation 99 9 999 C F 10 0 44 FLF Low te...

Page 16: ...otu Time relative to auxiliary output oF Function disabled 1 59 s 1 99 min oF 67 tUF Key Function oF No function 1 Eco Mode direct selection turn OFF the showcase light if configured 2 Switch ON Swit...

Page 17: ...faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characteristics Power supply 230 VAC 115 VAC 12 VAC VDC 10...

Page 18: ...C 103AT11 11 INSTRUMENT ORDERING CODE MODEL e33B Instrument with mechanical keyboard a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Out1 Relay SPST NO 16A AC1 for resistive loads R...

Page 19: ...Ascon Tecnologic e33B OPERATING INSTRUCTIONS PAG 19...

Reviews: