8.  PROBLEMS, MAINTENANCE AND WARRANTY

8.1 

Notifications

8.1.1 

Error messages

Error

Reason

Action 

E1 -E1
E2 -E2 
E3 -E3

The probe may be interrupted 
(

E

) or in short circuit (

-E

) or 

may measure a value outside 
the range allowed

Check the probe connec-
tion with the instrument 
and check that the probe 
works correctly

epr

Internal EEPROM memory 
error

Pressthe 

 

/

 key

err

Fatal memory error

Replace the instrument or 
ship to factory for repair

8.1.2 

Other messages

Message

Reason

od

Delay at power-on in progress

Ln

Keyboard locked

Hi

Maximum temperature alarm in progress

Lo

Minimum temperature alarm in progress

AL

Digital Input alarm in progress

oP

Door Open

dEF

Defrost in progress with 

ddL

 = 

Lb

PdF

Post-defrosting in progress with 

ddL

 = 

Lb

Eco

Eco Mode in progress

trb

Turbo Mode in progress

8.2 

Cleaning

We recommend cleaning of the instrument only with a slightly 
wet cloth using water and not abrasive cleaners or solvents.

8.3 

Disposal

The appliance (or the product) must be 
disposed of separately in compliance 
with the local standards in force on 
waste disposal.

9.  WARRANTY AND REPAIRS

The instrument is under warranty against manufacturing flaws 
or faulty material, that are found within 18 months from deliv-
ery date.  The warranty is limited to repairs or to the replace-
ment of the instrument.
The eventual opening of the housing, the violation of the instru-
ment or the improper use and installation of the product will 
bring about the immediate withdrawal of the warranty effects.
In the event of a faulty instrument, either within the period 
of warranty, or further to its expiry, please contact our sales 
department to obtain authorisation for sending the instrument 
to our company.
The faulty product must be shipped to Ascon Tecnologic with 
a detailed description of the faults found, without any fees or 
charge for Ascon Tecnologic, except in the event of alternative 
agreements.

10.  TECHNICAL DATA

10.1  Electrical characteristics

Power supply:

 230 VAC, 115 VAC, 12 VAC/VDC ±10%;

AC frequency:

 50/60 Hz;

Power consumption:

 about 3.5 VA;

Inputs:

 

3 inputs

 for 

temperature probes

 

NTC

 (103AT-2, 10 k

W

 @ 25°C); 

 

1 free of voltage digital input

 as an alternative to  

 

input probe 

Pr3

;

Output:

 Up to 

3 relay outputs

:

EN 61810 EN 60730 UL 60730

Out1 (H) - SPST-NO - 30A - 2 
HP 250V, 1 HP 125 VAC

30 (15) A

15 (15) A

15 A Res., 
96 LRA,  
16 FLA

Out1 (R) - SPST-NO - 16A - 
1HP 250V, 1/2 HP 125 VAC

16 (9) A

10 (4) A

12 A Res., 
30 LRA,  
5 FLA

Out2 - SPDT - 8A -  
1/2 HP 250V, 1/3 HP 125 VAC

8 (3) A

8 (4) A

10 A Res.

Out3 - SPST-NO - 5A -  
1/10 HP 125/250 V

5 (1) A

2 (1) A

2 A Gen. 
Use

12 A max. for those with removable terminal model;

Relay output Electrical life:

 100000 operations;

Action type:

 Type 1.B (EN 60730-1);

Overvoltage category:

 II;

Rated impulse voltage:

 2500 V for 115/230 V; 500 V for 12-24 V;

Protection class:

 Class II;

Isolation:

 Reinforced insulation between the low voltage 

parts (type C or D power supply and relay output) and front 
panel; Reinforced insulation between the low voltage parts 
(type C or D power supply and relay output) and the extra 
low voltage section (inputs), No insulation between type F 
power supply and inputs.

10.2  Mechanical characteristics

Housing:

 Self-extinguishing plastic, UL 94 V0;

Ball Pressure Test as described in EN60730:

 accessible 

parts 75°C; support live parts 125°C;

Heat and fire resistance category:

 D;

Dimensions:

 78 x 35 mm, depth 64 mm;

Weight:

 About 190 g;

Mounting:

 Incorporated flush in panel (thickness max. 12 mm) 

in a 71 x 29 mm hole;

Connections:

 

Inputs:

 fixed or removable screw terminal block for  

0.2 ÷ 2.5 mm

2

/AWG 24 ÷ 14 cables;

Power supply and Outputs:

 fixed or removable screw 

terminal block or Faston 6.3 mm for 0.2 ÷ 2.5 mm

2

AWG 24 ÷ 14 cables;

Protection degree:

 IP65 mounted with gasket and screw 

type bracket (both optional);

Pollution degree:

 2;

Operating temperature:

 0 ÷ 50°C;

Operating humidity:

 < 95 RH% with no condensation;

Storage temperature:

 -25 ÷ +60°C.

Summary of Contents for e33B

Page 1: ...ration through stopping the compressor electric heating or hot gas cycle inversion The controller is equipped with special defrost optimization functions and with other functions that can be used to o...

Page 2: ...Stand by mode this is the only lighted LED In programming mode while the parameter code is displayed the dot indicates the parameter protection level not protected lit up protected flashing and hidde...

Page 3: ...ial test keeping it pressed for 5 s In this way it is possible to access all the parameters verify and modify the parameter tPP 2 4 Customized mode parameter programming parameters programming level T...

Page 4: ...d rule must adopt all the necessary protective measures The instrument MUST NOT BE USED in dangerous environ ments flammable or explosive without adequate protections The instrument used with NTC 103A...

Page 5: ...1 A Out 3 2 1 A 60730 EN UL 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different conditions ON Means that the controller uses the control functions STAND BY Means t...

Page 6: ...always closed 5 3 Measure and display configuration With parameter iuP it is possible to select the tempera ture engineering unit and the desired measure resolution C0 C 1 C1 C 0 1 F0 F 1 F1 F 0 1 The...

Page 7: ...that is NO in normal operation then closed during the alarm AL To control an alarm that cannot be silenced through a contact that is NO in normal operation then closed during the alarm An To control a...

Page 8: ...s automatic switching between the three Normal Eco Turbo modes described at the paragraph Operating modes The time protections described in the next paragraph PP1 PP2 PP3 always work on the ot configu...

Page 9: ...a chines in which is required the maximum evaporator efficiency at each compressor cycle To enable automatic defrost at intervals after setting the ddC parameter as desired between rt ct or cS with th...

Page 10: ...related to the EP probe under which defrosts are possible Therefore in the indicated modes if the temperature meas ured by the EP probe is higher than the one set at parameter dtS and also dtE defros...

Page 11: ...emperature alarms Hi and Lo External alarm AL Door open oP The alarm functions acts on LED on the internal buzzer if present and configured by the obu parameter and on the desired output if configured...

Page 12: ...The instrument can signal an alarm external to the instrument using the digital input setting iFi 4 or 5 The instrument signals the alarm turning ON the alarm LED and display ing AL label alternated...

Page 13: ...f some instruments which need to have the same parameters con figuration or to keep a copy of the parameters settings of an instrument and allow its rapid retransmission The same device allows to conn...

Page 14: ...ck 3 Open Door with Fan and Output Lock 4 External Alarm 5 External alarm with control output disabling 6 Normal Eco select 7 On Stand by select 8 Start a Turbo cycle 2 15 iti Digital Input Delay oF D...

Page 15: ...n disabled 1 59 s 1 99 min 5 42 FtF Fan time deactivation with ot output compressor OFF oF Function disabled 1 59 s 1 99 min oF 43 FFL High temperature fan deactivation 99 9 999 C F 10 0 44 FLF Low te...

Page 16: ...otu Time relative to auxiliary output oF Function disabled 1 59 s 1 99 min oF 67 tUF Key Function oF No function 1 Eco Mode direct selection turn OFF the showcase light if configured 2 Switch ON Swit...

Page 17: ...faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characteristics Power supply 230 VAC 115 VAC 12 VAC VDC 10...

Page 18: ...C 103AT11 11 INSTRUMENT ORDERING CODE MODEL e33B Instrument with mechanical keyboard a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Out1 Relay SPST NO 16A AC1 for resistive loads R...

Page 19: ...Ascon Tecnologic e33B OPERATING INSTRUCTIONS PAG 19...

Reviews: