Ascon Tecnologic - e33B - OPERATING INSTRUCTIONS - PAG. 15
Parameter
Description
Range
Def.
Note
30
ddL
Display Lock during defrost
oF
Not active;
on
Active at last measure;
Lb
Active with label (
dEF
during defrost and
at defrost).
oF
31
dcd
Defrost activation time for continuous compressor
operating
oF
Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h)
oF
32
dde
Max. defrost duration
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
33
dtd
Compressor delay after defrost (drainage time)
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min)
20
34
ddt
Defrosting Type
EL
Electrical heating/stop compressor;
in
Hot gas/reverse cycle;
no
Without compressor output condictioning;
Et
Electrical heating with evaporator temperature control.
EL
35
ddC
Defrosting starting mode
rt
Real time intervals;
ct
“ot” output on time intervals;
cS
defrost every “ot” switching off (+ rt intervals);
cL
Do not use.
rt
36
ddi
Defrosting interval
oF
Function disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
37
dSd
Delay first defrost after power-on
oF
Defrost at power-on;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
38
ddd
Dynamic Defrost Percentage reduction
0 ÷ 100%
0
39
dEi
Defrosting interval for evaporator probe error
oF
Function disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h)
6
40
dEE
Lengh of defrost cycle for evaporator probe error
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
10
41
Ftn
Fan time activation with
ot
output (compressor)
OFF
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
5
42
FtF
Fan time deactivation with
ot
output (compressor)
OFF
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
43
FFL
High temperature fan deactivation
- 99.9 ÷ 999 °C/°F
10.0
44
FLF
Low temperature fan deactivation
- 99.9 ÷ 999°C/°F
-99.9
45
FdF
Differential fan control
0.0 ÷ 30.0°C/°F
1.0
46
FFE
Fan status during defrost
oF - on
oF
47
FFd
Fan delay after defrost
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
48
PP1
ot
output delay at switching
ON
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
49
PP2
ot
output delay after switching
OFF
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
50
PP3
Min. time between two
ot
output switching
ON
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
51
Pod
Outputs delay at power
ON
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
52
AAy
Temperature Alarm 1 type
1
Absolute for
Pr1
with label
Hi
or
Lo
;
2
Relative to
Pr1
with label
Hi
or
Lo
;
3
Absolute for
Au
with label
Hi
or
Lo
;
4
Relative to
Au
with label
Hi
or
Lo
;
5
Absolute for
Pr1
with no label;
6
Relative to
Pr1
with no label;
7
Absolute for
Au
with no label;
8
Relative to
Au
with no label.
1
53
AHA
High temperature Alarm threshold
oF
Function disabled;
-99.9 ÷ +999°C/°F.
oF
54
ALA
Low temperature Alarm threshold
oF
Function disabled;
-99.9 ÷ +999°C/°F
oF
55
AAd
Temperature Alarms Differential
0.0 ÷ 30.0°C/°F
1.0
56
AAt
Temperature Alarms Delay
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
57
AtA
Alarms memory
oF
Alarm memory disabled;
on
Alarm memory enabled;
oF
58
APA
Temperature Alarms delay at power ON
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
2