19
Chapter 3
Electrical Connections
3-1
Electric safety and electromagnetic compatibility
Class II instrument, rear panel mounting.
This instrument has been designed in compliance with:
•
Regulations on electrical equipment:
-
according to regulations on the essential protection requirements in electrical equip-
ment EN 61010-1
•
Regulations on Electromagnetic Compatibility according to:
-
Regulations on RF emissions:
EN61000-6-4 industrial environments;
-
Regulation on RF immunity:
EN61000-6-2 industrial equipment and system.
It is important to understand that it’s responsibility of the installer to ensure the compliance of
the regulations on safety requirements and EMC.
This controller has no user serviceable parts and requires special equipments and special-
ised engineers to be repaired. For this purpose, the manufacturer provides technical assist-
ance and the repair service for its Customers. Please, contact your nearest Agent for further
information.
All the information and warnings about safety and electromagnetic compatibility are marked
with the
sign, at the side of the note.
3-1-1
How to increase the electromagnetic immunity
For maximum immunity to disturbance use FIL00014 fil-
ter. Install it between the outlet and the power supply,
closest to 24 V power supply.
A good ground connection is required between the filter
case and the earth.
In addition a FIL00013 clamp filter could be placed on the
analogue inputs, outputs and communication cables posi-
tioned close to the device and winding a cable loop in the
clamp filter as illustrated.