P/N PM000223A • Rev. 1 • ISS 9 August 2017
34
Installation Manual
NU-Series Hardware
IP Devices
5.2
Supplementary IP Devices
The Ascom Telligence System support the following supplementary IP devices. These
devices are not required to operate the system.
5.3
System Manager (NISM2)
The System Manager (NISM2) is an Ascom ELISE3 application. The ELISE3 module serves as
the interface to a 100base-T Ethernet LAN and it contains a Linux-based web server.
In installations that include NURD Room Displays and corridor displays, use the NISM2 as
the Interactive Messaging server for the displays.
A Java-based graphical user interface (GUI) comes with the NISM2. Use a web browser to
manage the system setup. Use any Internet browser that can interpret Java script 1.2
(CSS-2). We recommend that you use Microsoft Internet Explorer 7.0 or higher with Sun
Java Runtime Environment 1.6, or later.
Warning: This NISM2 System Manager does not comply with the ANSI/UL 1069 standard
for Hospital Signaling and Nurse Call equipment and is not considered to be part of a
listed system configuration.
The NISM2 has two RS232 COM ports (COM1 and COM2). Use them to connect an ESPA
(or a TAP) paging system. Support of an ESPA (or a TAP) paging system requires a license.
Figure 24 System Manager (NISM2)
The NISM2 requires 100VAC to 240VAC 50-60Hz for its internal power supply. Optionally,
you can use the 12-24VDC power connection to connect to an external power supply.