P/N PM000223A • Rev. 1 • ISS 9 August 2017
117
Installation Manual
NU-Series Hardware
Room Modules
2 of 3
P/N PM000119A • Rev.
• ISS
-81
2017
To make the connections to the module:
1. Pull the cables from the backbox or spacer, and then slide
them though the module’s frame.
Passive Customizable Module Connections and Jumper
The module connects to a passive room bus using an 8-pole
connector. It can also be daisy-chained with other peripheral
devices on same bus. The connector carries 5.5VDC power,
input, and output lines.
The module includes a jumper to activate and End-of-Line
resistor (EOL) when the module is last module on the passive
bus.
Legend
(1) Buzzer
(2) Jumper for end-of-line (EOL)
(3) 8-pole connector for a passive room bus
8-pole Passive Bus Connection Pinouts
To connect a passive customizable button module:
1. Slide the cables with their connectors through a module
frame.
2. If this is the last device on the passive room bus, move the
EOL jumper to the pins labeled EOL; otherwise, leave the
jumper in its default position (OFF). See the previous
figure, item 2.
Note:
EOL must also be configured in the system using the
System Configuration Tool.
Pin #
Pin
Description
Color
1
+V
Positive power
Orange/White
2
R
Reset
Orange
3
L_RD
LED Red
Blue/White
4
S
Set
Blue
5
C
C-line
Green/White
6
L_GR
LED Green
Green
7
L_YL
LED Yellow
Brown/White
8
GND
Ground
Brown
3. Attach the 8-pole room bus connector cable to the 8-pin
terminal. See item 3. Ensure the connector is seated
properly on the pins.
To attach the module on the adapter:
1. Place the module against the frame, ensuring that the
module is facing up.
2. Place the module’s upper snap fasteners against the
upper edge of the adapter (see item 1 in the following
figure).
.
3. Press the module firmly against the adapter so that the
module’s bottom fasteners (see item 3 in the previous
figure) snap closed on the adapter.