background image

© 2020 ASCO Power Technologies. All Rights Reserved

11

IO-70071

01/2020

For access to self-service tools and chat support visit se.com/us/en/work/support  or call 1-888-778-2733 for technical assistance

ASCO Model 950 Surge Protective Device (SPD) and Fuse Box

Installation

NOTICE

HAZARD OF PERFORMANCE OPTIMIZATION

•  Mount SPD as close to panel or equipment as possible to keep leads short.

•  Coordinate the installation and location of Model 950 to include the SPD 

and fuse box components.

•  Ensure leads are as short and straight as possible (cut excess wire), 

including ground by planning the installation that will result in the 

shortest possible overall lead length.

Failure to follow these instructions can result in equipment damage.

• 

Read all Instructions.

• 

All electrical connections should be performed by a qualified electrician 

or technician.

• 

Meet all National and Local codes.

• 

Mount SPD as close to panel or equipment as possible to keep leads 

short.

• 

Coordinate the installation and location of Model 950 to include the SPD 

and fuse box components.

• 

Model 950 should be installed as close as possible to the point of 

connection with the electrical distribution system.

• 

Excessive overall wire length, from the SPD, through the fuse box to the 

point of connection with the electrical distribution system will adversely 

affect the performance of the SPD.

• 

Ensure leads are short and straight as possible (cut excess wire), 

including ground by planning the installation that will result in the shortest 

possible overall lead length.

• 

Unit mounting should be in such a way that the SPD component conduit 

hub is facing downward (for weather resistance).

1. 

Remove power from panel. Confirm panel is deenergized and locked out.

2.  Identify connection, SPD & fuse box locations for shortest leads.

3.  Mount SPD and fuse box on a surface capable of supporting 100lbs 

(45.4kg) using the hardware and conduit provided along with any other 

conduit and fittings as needed, SPD must be mounted with the conduit 

hub facing downward.

4.  Install in accordance with national and local electrical codes for overcurrent 

protection recommendations and wire ampacity considerations. 

Note: Use on solidly grounded systems unless the SPD model is 

designed for installation on ungrounded/HRG systems.

5.  Thread the 3 Phase and 1 Ground conductors from the SPD through 

the 6” conduit and the top hub of the fuse box and connect to the Phase 

and Ground lugs inside the fuse box, remember to keep the leads as 

short as possible.

6.  Twist conductors 1/2 turn or more for every twelve inches of length. Do not 

loop or coil wires. Be sure to maintain adequate wire bending space per NEC.

7.  Thread the 3 Phase and 1 Ground conductors from the bottom of 

the fuse box to Phase A, B, C and Ground in the switchgear. Each 

conductor from the SPD will be labeled A, B, or C. Connect A, B & C 

Phase conductors from the SPD to Phase A, B, & C in the fuse box and 

at the point of connection with the electrical system.

8.  Label or mark conductors from the fuse box as appropriate.

9.  Replace all devices, doors, and covers before turning on power to 

the equipment. If the SPD is properly installed and functioning, the 

green LED indicators on the display will be lit and the service LED 

extinguished.

HAZARD OF ELECTRIC SHOCK, EXPLO-

SION, OR ARC FLASH

•  Prior to energizing, verify that the system is 

clear of deficiencies.

•  Maintain a safe distance from SPD and Fuse 

box when power is applied as a precaution 

against misapplication.

Failure to follow these instructions will result 

in death or serious injury.

DANGER

Figure 2:

 Typical Installation (Front View)

Note:

 If you have any questions pertaining to the 

installation of this device, chat support is available 

at se.com/us/en/work/support or call  

1-888-778-2733 for technical assistance

Summary of Contents for 950

Page 1: ...Surge Protective Devices Installation Operation Manual Model 950 SPD Fuse Box ...

Page 2: ...ating Environment Typical Installation Location Installation Mounting Dimensions Weight Audible Noise Service Clearance Overcurrent Protection Voltage Rating Wire Size Optional Monitoring Package Operation Maintenance Troubleshooting and Service Dimensional Drawings SPD Component Mechanical Drawings Fuse Box Component Mechanical Drawings 4 6 6 6 7 7 9 9 9 9 9 9 9 10 10 10 10 12 12 12 12 13 13 13 1...

Page 3: ...to potential personal injury hazards Obey all safety messages that follow this symbol to avoid possible injury or death DANGER DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION CAUTION indicates a hazardous situation which if not avoi...

Page 4: ...F ELECTRIC SHOCK EXPLOSION OR ARC FLASH This Surge Protective Device SPD Three Phase Fuse Box is for use by those who understand and accept its benefits and risks The loss of SPD protection is a symptom of system level overvoltage problems Ungrounded distribution systems are designed to float and move with respect to ground An SPD that has lost protection may escalate the initial distribution syst...

Page 5: ... testing or any other tests where surge protective device components will be subjected to voltages higher than their rated turn on voltage with the neutral and surge protective device disconnected from the power source Failure to follow these instructions will result in death or serious injury DANGER At end of life conditions Surge Protective Devices SPDs can lose their ability to block power syst...

Page 6: ...ed to replace national or local codes Follow all applicable electrical codes to ensure compliance Installation of the Model 950 should only be performed by qualified electrical personnel familiar with 1kV to 5kV systems ASCO s Medium Voltage SPDs are extensively tested in accordance with industry standards such as ANSI IEEE C62 11 This unit is a Single port Parallel connected Device Three Phase Fu...

Page 7: ...s provided with an external fuse box to provide dedicated OCP When the SPD and fuse box are installed according to this manual and the SPD reaches the end of its useful life the OCP fuses in the fuse box will disconnect the SPD from the system but maintain power to the load now unprotected If this situation is undesirable for the application follow the instructions for replacing the device Service...

Page 8: ...Per Phase kA Rating System Modes of Protection Default Connection Type Default Monitoring Options Enclosure UL 1449 Type Accessory Option s kA Rating Per Phase 950 Model 950 Product Line G NEMA 4 SPD steel fuse box polycarbonate R NEMA 3R SPD steel fuse box polycarbonate diagnostics steel 3R W Wire leads N None default R LEDs and dry contact relays R enclosure only 120kA only 0 No trailing accesso...

Page 9: ... container for damage or signs of mishandling Remove the packing materials and further inspect the unit for any obvious shipping damages If any damage was found and is a result of shipping or handling immediately file a claim with the shipping company and forward a copy to ASCO Relative Humidity Range 0 95 Non condensing Operating Frequency 50 60Hz Operating Temperature 40 F 40 C to 185 F 85 C NEM...

Page 10: ...50 on the load side of the main overcurrent protection device When selecting the installation location verify that there is enough space for both the fuse box and SPD to be installed and that their combined weight can be supported Failure to follow these instructions will result in death or serious injury HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Pre plan the installation and read and unders...

Page 11: ...3 Mount SPD and fuse box on a surface capable of supporting 100lbs 45 4kg using the hardware and conduit provided along with any other conduit and fittings as needed SPD must be mounted with the conduit hub facing downward 4 Install in accordance with national and local electrical codes for overcurrent protection recommendations and wire ampacity considerations Note Use on solidly grounded systems...

Page 12: ...must be capable of supporting 75 lbs 34 5 kg 35 lbs 15 9 kg The enclosure dimensions of the SPD are 12 x 12 x 6 in 305 x 305 x 152 mm and the fuse box are 18 x 16 x 10 in 457 x 406 x 254 mm Failure to follow these instructions can result in injury NOTICE LEAD LENGTHS MAXIMIZING SPD PERFORMANCE Model 950 must be located as close to the circuit as possible to minimize parasitic losses Surges are hig...

Page 13: ...unding conductor The system configuration is not based on how any specific load or equipment is connected to a particular power distribution system Model 950 comes pre wired with 2 feet 1 3 meters of 6 AWG stranded leads for all three phases and ground for SPD to fuse box connection and 8 feet 2 4 meters of 6 AWG stranded leads for all three phases and ground for fuse box to switchgear connection ...

Page 14: ... periods Keep the SPD free of dirt and debris The ASCO 950 surge protector has little to troubleshoot Only a nonfunctional SPD will open the fuses Opened fuses should be replaced with the same make model and amperage Do not replace with fuses under 15A due to the possibility of inadvertent nuisance tripping Do NOT replace opened fuses with ones rated 200A and higher as this will not properly disco...

Page 15: ...ols and chat support visit se com us en work support or call 1 888 778 2733 for technical assistance 12 24 6 30 2 42 0 95 0 3120 10 00 13 50 12 75 Figure 5 Model 950 SPD Component Mechanical Drawings Dimensions in ASCO Model 950 Surge Protective Device SPD and Fuse Box Dimensions Front View Side View ...

Page 16: ...While every precaution has been taken to ensure accuracy and completeness in this literature Schneider Electric assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 14550 58th Street North Clearwater Florida 33760 se com us en work support 1 888 778 2733 Figure 6 Model 950 Fuse Box Component Mechanical Drawings Dime...

Reviews: