SECTION 2 TESTING & SERVICE

2--1

TRANSFER TEST

Test the Automatic Transfer Switch portion of the 7000

Series 7ADTB at least once a month. This procedure

checks the electrical operation of the Transfer Switch and

Controller. Put the engine–generator starting control (at

the engine–generator set) in automatic mode.

In the following test the generator will start, the load will

be transferred to the Emergency source, then back to the

Normal source. An interruption to the load will occur, un-

less the the Transfer Switch contacts are bypassed before

the test. See pages 3–1 through 3–4 for bypassing & iso-

lating instructions if no interruption of load is required.

Be sure to close the enclosure door

before proceeding to prevent personal injury

in case of electrical system fault.

Perform the five–step

Electrical Operation – Transfer

Test

procedure on page 1–4.

PREVENTIVE MAINTENANCE

Reasonable care in preventive maintenance will insure

high reliability and long life for the 7000 Series 7ADTB.

An annual preventive maintenance program is recom-

mended.

ASCO Services, Inc. (ASI) is ASCO Power

Technologies’s national service organization. In the

US ASI can be contacted at 1-800-800-2726 for in-

formation on preventive maintenance agreements.

Checklist for Yearly Inspection

Hazardous voltage capable of causing shock,

burns, or death is used in this switch.

Deenergize both Normal – Emergency power

sources before performing inspections!

Clean the 7ADTB enclosure

.

Brush and vacuum away any excessive dust accumu-

lation. Remove any moisture with a clean cloth.

Check the transfer switch contacts.

Bypass, isolate, and withdraw the transfer switch.

Then remove the transfer switch interphase barriers

and check the condition of the contacts. Replace con-

tacts when pitted or worn excessively. Reinstall the

interphase barriers carefully. See page 3–4.

Maintain transfer switch lubrication

.

If switch is subjected to severe dust or abnormal

operating conditions, renew factory lubrication on

all movements and linkages. Relubricate solenoid

operator if TS coil is replaced. Don’t use oil; order

lubrication kit 75-100

.

Check all cable connections & retighten them

.

REPLACEMENT PARTS

Replacement parts are available in kit form. When or-

dering parts provide the Serial No., Bill of Material No.

(BOM), and Catalog No. from the transfer switch name-

plate. Contact your local ASCO Power Technologies

Sales Office or ASI:

In the United States

call 1 – 800 – 800 – ASCO

( 2726 )

In Canada

call 1 – 888 – 234 – ASCO

( 2726 )

DISCONNECTING THE CONTROLLER

The harness disconnect plugs are furnished for repair

purposes only and should not have to be unplugged. If

the controller must be isolated, follow these steps:

Bypass–Isolation Switch is energized!

Do not touch isolation contact fingers;

shock, burns, or death could result!

Disconnecting the Plugs

1. Bypass and Isolate the Automatic Transfer Switch.
2. Open the upper enclosure door.
3. Separate the two quick disconnect plugs by squeez-

ing the latches. Do not pull on the harness wires.

Reconnecting the Plugs

1. The ATS should be still bypassed and isolated.
2. The two harness plugs and sockets are keyed. Care-

fully align the plugs with the sockets and press

straight in until the latches click.

3. Close the enclosure doors.
4. Follow

Return to Service

instructions on page 3–5.

MANUAL LOAD TRANSFER

This procedure manually transfers load to other source if

the Transfer Switch or Controller are out of service.

Close enclosure doors to prevent personal

injury in case of electrical system fault.

1. Bypass the connected ACTB source. Turn Bypass Han-

dle to

EMERGENCY

or

NORMAL

(see page 3–2).

2. Isolate to Test. Turn the Isolation Handle to

TEST

position (see page 3–3).

3. Turn the Bypass Handle to

OPEN

, then to the other

source (see page 3–1). The load will be interrupted.

4. Turn the Isolation Handle clockwise to the

CONN

[connected] position (see page 3–4).

Summary of Contents for 7000 Series

Page 1: ...installation and connection details and accessories Refer to Group 5 Controller User s Guide 381333 126 for ATS status display messages time delays pickup dropout settings and adjustments An experienced licensed electrician must install the 7ADTB Rating Label Each 7000 Series 7ADTB contains a rating label to define the load and fault circuit withstand closing ratings Refer to the label on the Tran...

Page 2: ...00 amp 480 V ATS in Type 1 enclosure J7ADTB C 3 600 N 5 C Phase Poles Neutral A solid Amperes Voltage Controller Enclosure B switched 5X if accessories ordered 5 standard G type 4 C type 1 F type 3R L type 12 3 three Ø 2 single Ø D 220 C 208 E 230 K 415 M 460 J 400 L 440 N 480 G 277 F 240 H 380 Q 575 P 550 R 600 600 400 260 blank none blank open type 150 A 115 B 120 Transfer Switch inside Bypass H...

Page 3: ...ne connections are in proper phase rotation Place engine gen erator starting control in the OFF position Make sure engine generator is not in operation Testing Power Conductors Do not connect the power conductors to the transfer switch until they are tested Installing power cables in conduit cable troughs and ceiling suspended hangers often requires considerable force The pulling of cables can dam...

Page 4: ...ttom of the assembly Be sure to reconnect plug J3 to the P3 receptacle for automatic transfer switch operation Auxiliary Circuits Connect auxiliary circuit wires to appropriate terminals on transfer switch terminal block TB as shown on the wiring diagram provided with this automatic transfer switch engine start connections on customer terminal block TB Figure 1 1 Customer terminal block on the top...

Page 5: ...lack square means light is on White square means light is off If necessary adjust voltage regulator on generator per the manufacturer s recommendations The 7ADTB will respond only to rated voltage specified on the nameplate Now continue to 2 Electrical Operation on next page 1 Close the normal source circuit breaker The Transfer Switch Connected To Normal and the Normal Source Accepted lights shou...

Page 6: ...Isolation Handle clockwise to the CONN connected position 4 Turn Bypass Handle clockwise to the OPEN position This completes the Functional Test of the 7ADTB 1 Turn and hold Transfer Control switch clockwise to Transfer Test until the engine starts and runs within 15 sec The Emergency Source Accepted light should come on Load Disconnect Active 2 Transfer switch CN opens and the Transfer Switch Con...

Page 7: ...ee page 3 4 Maintain transfer switch lubrication If switch is subjected to severe dust or abnormal operating conditions renew factory lubrication on all movements and linkages Relubricate solenoid operator if TS coil is replaced Don t use oil order lubrication kit 75 100 Check all cable connections retighten them REPLACEMENT PARTS Replacement parts are available in kit form When or dering parts pr...

Page 8: ...witches Gen does not stop after load retransfer to normal source Wait for Feature 2E time delay to time out Starting control must be in the automatic position Load Disconnect Active light comes on Wait for load disconnect time delay to time out Explanation Transfer switch in delayed transition transfer mode Load disconnect time delay is adjustable from 0 to 5 min 59 sec Load Disconnect Active ligh...

Page 9: ...positions ALL POWER MUST BE OFF Transfer Switch Position Interlocked Shafts Maintenance Handle Shaft Indicators Normal E t t h ft shaft extension up E O upper contacts open Normal N link contact shafts shaft extension up N C lower contacts closed Load E up E O upper contacts open Load Disconnected N down N O lower contacts open Emergency E down E C upper contacts closed Emergency N down N O lower ...

Page 10: ...that the Transfer Switch is connected Solenoid interlock prevents incorrect operation 1 Observe which Transfer Switch Connected To light is on Normal or Emergency on the door This is the position of the transfer switch see Figure 3 2 2 Follow the directions on next page to Bypass to the same source as connected to transfer switch select Normal or Emergency Window indicator shows green when the ATS...

Page 11: ... Bypass to Normal diagram BYPASS SWITCH BYPASSED TO NORMAL BYPASSED TO EMERGENCY Upper green light comes on Lower window indicator NORMAL shows yellow Figure 3 6 Status light and window indicator for Bypassed to Normal Source Turn the Bypass Handle clockwise until Bypass Switch Position shows closed on EMERGENCY yellow window indicator The red lightBypassed toEmergency willcome on and the amber li...

Page 12: ...on TS TEST TS ISOLATED position window CONN TEST ISOLATE counterclockwise draws out the transfer switch Figure 3 10 Isolation Handle turned to TEST NOTE In the TEST position the transfer switch solenoid operator circuit is energized through secondary disconnects Hazardous voltage capable of causing electrical shock burns or death do not touch any control circuit terminals 3 Continue turningIsolati...

Page 13: ...ould be checked annually Discoloration is normal Do not file contacts because it wastes material Instead use light emery paper to clean up the contact surfaces The non replaceable main contacts are designed to last the life of the transfer switch To prevent the possibility of fatal electrical shocks and burns bypass isolate and withdraw the transfer switch before working on it 1 Deenergize transfe...

Page 14: ...n the transfer switch Figure 3 17 Isolation Handle turned to TEST 3 TheATScan betested nowwithout loadinterruption see page 2 1 Solenoid interlock prevents you from closing the isolation contacts until the ATS is in the same position as the Bypass Switch 4 ObservewhichBypass Switch Position windowindica tor is yellow NORMAL or EMERGENCY at the Bypass Switch Handle This indicates the source connect...

Page 15: ...tch handle continue turning the Isolation Handle clockwise about 8 turns until the window shows CONN connected E L N Automatic Transfer Switch Bypass Switch Turn crank clockwise until window shows TEST Figure 3 18 TEST to CONN connected position TS CONNECTED Upper amber light should be on TS TEST TS ISOLATED position window CONN clockwise draws in the transfer switch Figure 3 19 Isolation Handle t...

Page 16: ...Emergency Source Load connected to Normal Source The Transfer Switch Connected To Normal light is on and Transfer Switch Connected To Emergency light is off Load connected to Emergency Source The Transfer Switch Connected To Emergency light is on and Transfer Switch Connected To Normal light is off Turn the handle clockwise Turn the handle counterclockwise Turn the Bypass Handle clockwise until th...

Page 17: ... emergency 1 3 load connected to normal 1 3 Load Disconnect Active light 1 4 lubrication 2 1 M maintenance preventive 2 1 maintenance handle 2 3 warning 2 3 manual load transfer 2 3 warning 2 3 N nameplate 1 1 Normal Source Accepted light 1 3 O operation electrical 1 4 manual 2 3 warning 2 3 optional accessories see Controller User s Guide P parts 2 1 phase rotation check 1 3 preventive maintenanc...

Reviews: