background image

SECTION 1

INSTALLATION

1---1

ASCO 7000 Series Automatic Delayed–Transition
Transfer & Bypass–Isolation Switches (7ADTBs) are
factory wired and tested. Field installation requires
mounting and connection of service cables, and auxiliary
control circuits (if required).

Remove the Shipping Skid

Open the front door and remove the four lag screws (2 in
front, 2 in rear) securing enclosure to the shipping skid.

Supporting Foundation

The supporting foundation for the enclosure must be
level and straight. Refer to the applicable enclosure
outline drawing included with the switch for all mounting
details including door opening space.

If bottom cable entry is used, the foundation must be
prepared so that the conduit stubs are located correctly.
Refer to the enclosure outline drawing for specified area
and location. Provide cable bending space and clearance
to live metal parts. When a concrete floor is poured, use
interlocking conduit spacer caps or a wood or metal
template to maintain proper conduit alignment.

Mounting

Refer to the applicable enclosure outline drawing fur-
nished with this switch and mount the automatic transfer
switch according to details and instructions shown on
diagram.

Line Connections

Refer to the Wiring Diagram provided with the switch.
All wiring must be made in accordance with the National
Electrical Code and local codes.

Do not remove the interphase barriers from the transfer
switch. Always protect the transfer switch, bypass switch,
and isolation contacts and mechanisms from construc-
tion grit and metal chips when cabling.

De–energize the conductors before making any

line or auxiliary circuitry connections. Be sure

that Normal and Emergency line connections

are in proper phase rotation. Place engine gen-

erator starting control in the OFF position. Make

sure engine generator is not in operation.

Testing Power Conductors

Do not connect the power conductors to the transfer
switch until they are tested. Installing power cables in
conduit, cable troughs and ceiling-suspended hangers
often requires considerable force. The pulling of cables
can damage insulation and stretch or break the
conductor’s strands. For this reason, after the cables are
pulled into position, and before they are connected, they
should be tested to verify that they are not defective or
have been damaged during installation.

Protect the switch from construction grit

and metal chips to prevent malfunction or

shortened life of the 7ADTB switch.

Connecting Power Conductors

After the power cables have been tested, connect them to
the appropriate terminal lugs on the bypass switch as
shown on the wiring diagram provided with the switch.
Make sure the lugs provided are suitable for use with the
cables being installed. Standard terminal lugs are solder-
less screw type and will accept the wire sizes listed on the
drawings provided with the 7ADTB. Be careful when
stripping insulation from the cables; avoid nicking or
ringing the conductor. Remove surface oxides from
cables by cleaning with a wire brush. When aluminum
cable is used, apply joint compound to conductors.
Tighten cable lugs to the torque specified on rating label.

Controller Ground

A grounding wire must be connected to the controller’s
lower left mounting stud. Because the controller is
mounted on the enclosure door, a conductive strap must
be used between the enclosure and the door. This
connection provides proper grounding which does not
rely upon the door hinges.

Harnesses

The transfer switch is connected to the left side of the
controller by a plug–in harness (two plugs).

Summary of Contents for 7000 Series

Page 1: ...installation and connection details and accessories Refer to Group 5 Controller User s Guide 381333 126 for ATS status display messages time delays pickup dropout settings and adjustments An experienced licensed electrician must install the 7ADTB Rating Label Each 7000 Series 7ADTB contains a rating label to define the load and fault circuit withstand closing ratings Refer to the label on the Tran...

Page 2: ...00 amp 480 V ATS in Type 1 enclosure J7ADTB C 3 600 N 5 C Phase Poles Neutral A solid Amperes Voltage Controller Enclosure B switched 5X if accessories ordered 5 standard G type 4 C type 1 F type 3R L type 12 3 three Ø 2 single Ø D 220 C 208 E 230 K 415 M 460 J 400 L 440 N 480 G 277 F 240 H 380 Q 575 P 550 R 600 600 400 260 blank none blank open type 150 A 115 B 120 Transfer Switch inside Bypass H...

Page 3: ...ne connections are in proper phase rotation Place engine gen erator starting control in the OFF position Make sure engine generator is not in operation Testing Power Conductors Do not connect the power conductors to the transfer switch until they are tested Installing power cables in conduit cable troughs and ceiling suspended hangers often requires considerable force The pulling of cables can dam...

Page 4: ...ttom of the assembly Be sure to reconnect plug J3 to the P3 receptacle for automatic transfer switch operation Auxiliary Circuits Connect auxiliary circuit wires to appropriate terminals on transfer switch terminal block TB as shown on the wiring diagram provided with this automatic transfer switch engine start connections on customer terminal block TB Figure 1 1 Customer terminal block on the top...

Page 5: ...lack square means light is on White square means light is off If necessary adjust voltage regulator on generator per the manufacturer s recommendations The 7ADTB will respond only to rated voltage specified on the nameplate Now continue to 2 Electrical Operation on next page 1 Close the normal source circuit breaker The Transfer Switch Connected To Normal and the Normal Source Accepted lights shou...

Page 6: ...Isolation Handle clockwise to the CONN connected position 4 Turn Bypass Handle clockwise to the OPEN position This completes the Functional Test of the 7ADTB 1 Turn and hold Transfer Control switch clockwise to Transfer Test until the engine starts and runs within 15 sec The Emergency Source Accepted light should come on Load Disconnect Active 2 Transfer switch CN opens and the Transfer Switch Con...

Page 7: ...ee page 3 4 Maintain transfer switch lubrication If switch is subjected to severe dust or abnormal operating conditions renew factory lubrication on all movements and linkages Relubricate solenoid operator if TS coil is replaced Don t use oil order lubrication kit 75 100 Check all cable connections retighten them REPLACEMENT PARTS Replacement parts are available in kit form When or dering parts pr...

Page 8: ...witches Gen does not stop after load retransfer to normal source Wait for Feature 2E time delay to time out Starting control must be in the automatic position Load Disconnect Active light comes on Wait for load disconnect time delay to time out Explanation Transfer switch in delayed transition transfer mode Load disconnect time delay is adjustable from 0 to 5 min 59 sec Load Disconnect Active ligh...

Page 9: ...positions ALL POWER MUST BE OFF Transfer Switch Position Interlocked Shafts Maintenance Handle Shaft Indicators Normal E t t h ft shaft extension up E O upper contacts open Normal N link contact shafts shaft extension up N C lower contacts closed Load E up E O upper contacts open Load Disconnected N down N O lower contacts open Emergency E down E C upper contacts closed Emergency N down N O lower ...

Page 10: ...that the Transfer Switch is connected Solenoid interlock prevents incorrect operation 1 Observe which Transfer Switch Connected To light is on Normal or Emergency on the door This is the position of the transfer switch see Figure 3 2 2 Follow the directions on next page to Bypass to the same source as connected to transfer switch select Normal or Emergency Window indicator shows green when the ATS...

Page 11: ... Bypass to Normal diagram BYPASS SWITCH BYPASSED TO NORMAL BYPASSED TO EMERGENCY Upper green light comes on Lower window indicator NORMAL shows yellow Figure 3 6 Status light and window indicator for Bypassed to Normal Source Turn the Bypass Handle clockwise until Bypass Switch Position shows closed on EMERGENCY yellow window indicator The red lightBypassed toEmergency willcome on and the amber li...

Page 12: ...on TS TEST TS ISOLATED position window CONN TEST ISOLATE counterclockwise draws out the transfer switch Figure 3 10 Isolation Handle turned to TEST NOTE In the TEST position the transfer switch solenoid operator circuit is energized through secondary disconnects Hazardous voltage capable of causing electrical shock burns or death do not touch any control circuit terminals 3 Continue turningIsolati...

Page 13: ...ould be checked annually Discoloration is normal Do not file contacts because it wastes material Instead use light emery paper to clean up the contact surfaces The non replaceable main contacts are designed to last the life of the transfer switch To prevent the possibility of fatal electrical shocks and burns bypass isolate and withdraw the transfer switch before working on it 1 Deenergize transfe...

Page 14: ...n the transfer switch Figure 3 17 Isolation Handle turned to TEST 3 TheATScan betested nowwithout loadinterruption see page 2 1 Solenoid interlock prevents you from closing the isolation contacts until the ATS is in the same position as the Bypass Switch 4 ObservewhichBypass Switch Position windowindica tor is yellow NORMAL or EMERGENCY at the Bypass Switch Handle This indicates the source connect...

Page 15: ...tch handle continue turning the Isolation Handle clockwise about 8 turns until the window shows CONN connected E L N Automatic Transfer Switch Bypass Switch Turn crank clockwise until window shows TEST Figure 3 18 TEST to CONN connected position TS CONNECTED Upper amber light should be on TS TEST TS ISOLATED position window CONN clockwise draws in the transfer switch Figure 3 19 Isolation Handle t...

Page 16: ...Emergency Source Load connected to Normal Source The Transfer Switch Connected To Normal light is on and Transfer Switch Connected To Emergency light is off Load connected to Emergency Source The Transfer Switch Connected To Emergency light is on and Transfer Switch Connected To Normal light is off Turn the handle clockwise Turn the handle counterclockwise Turn the Bypass Handle clockwise until th...

Page 17: ... emergency 1 3 load connected to normal 1 3 Load Disconnect Active light 1 4 lubrication 2 1 M maintenance preventive 2 1 maintenance handle 2 3 warning 2 3 manual load transfer 2 3 warning 2 3 N nameplate 1 1 Normal Source Accepted light 1 3 O operation electrical 1 4 manual 2 3 warning 2 3 optional accessories see Controller User s Guide P parts 2 1 phase rotation check 1 3 preventive maintenanc...

Reviews: