"HH" Over Voltage
Pro tection for the DC Bus
of Fan Drive
The fan dr ive boa rd is
abn ormal
Yes
Whether th e i nput voltage of the unit
exceeds 460V?
No
Replace th e fan drive board
Yes
Chang e the volta ge to
380V
2.89 "HL" Under Voltage Protection for DC Bus of Fan Drive
Fault display:
main board of outdoor unit displays
Fault diagnosis:
If the fault code displayed on the 2-digit digital LED of the outdoor unit's main control board is HL, it
indicates the under voltage protection for the DC bus of fan drive.
Possible causes:
■ The unit's input power cable has a voltage below 320 V;
■ The fan drive board operates improperly.
Troubleshooting:
"HL" Under Vol tage
Pro tection for the DC Bus
of Fan Drive
The fan dr ive boa rd is
abn ormal
Yes
Whether th e i nput voltage of the
unit fall s below 320V?
No
Replace th e fan drive board
Yes
Chang e the volta ge to
380V