2.81 "H3" Reset Protection for the Fan Drive Module
Fault display:
wired controller of indoor unit displays
Fault diagnosis:
If the fault code displayed on the 2-digit digital LED of the outdoor unit's main control board is H3, it
indicates the reset protection for the fan drive board.
Possible causes:
■ The fan drive board operates improperly
Troubleshooting:
"H3" Reset Protection for
the Fan Drive Mo dule
The fan dr ive boa rd is
abn ormal
Yes
Replace th e fan drive board
No
Is th e p roblem so lve d after
the fan dri ve boa rd is powered off an d
then powered on for mo re than
three ti mes?
No
Yes
Compressor d rive bo ard is
abn ormal. Replace it
Whether P3 is d ispl aye d a t
the same time (reset the compresso r
drive boar d)?