Revised: 14/11/2011
Printed: 20/03/2013
3
INSTALLATION INSTRUCTIONS (FREESTANDING MODELS ONLY)
Select the position of your heater carefully, taking into consideration all combustible materials
in the roof; eg. Ceiling joists, roof trusses, etc.
Determine flue location through the ceiling:
Position the hearth correctly, then place the heater on the hearth so that the flue spigot on the
heater is correctly aligned with the flue location from the ceiling.
This heater has been tested and approved to AS 2918 using an approved Flue Kit.
Clearance to combustible surfaces:
Ensure correct model.
Minimum distance
Millimetres
Reference
Symbol
Heater
1800 2400
Standard Installation
A
150
150
B
350
300
Corner Installation
C
100
100
Standard Installation Corner Installation
INSTALLATION INSTRUCTIONS (FIRE PLACE INSERT MODELS ONLY)
The heater shall only be installed in a sound concrete or masonry fireplace, connected to a
chimney, both of which shall be inspected for soundness and thoroughly cleaned before the
heater is installed. After removing the packaging, slide the heater into the fireplace opening.
A flue system shall be connected to the heater, providing free and effective discharge of
combustion by-products outside the building and any enclosed or confined space.
Arrow models – Fireplace Inserts 1600 & 2000
Minimum distance:
Dimensions in mm
From top edge of hot air outlet to underside of mantle piece / shelf
550
From outer vertical edges of heater fascia to mantle piece uprights
50
Floor / hearth in front of heater from door sealing edge (fuel opening)
300
Floor / hearth in front of heater from either side of fire box opening
200
Note: The fireplace cavity shall be sufficient to accommodate the external firebox dimension
with a minimum clearance of 25 mm all around.
The power cord may be relocated from the right-hand front side of the heater to the left-hand
side.
Note: This procedure shall only be carried out by a licensed electrical contractor.