History log archive (inverter only)
NetMan 204 Solar
records the inverter values in a history log archive every day. The data are saved
to a file in text format.
The date is contained in the name of the log file itself; for example:
DP_2016_07_14.log
This file contains all the available data of year 2016, July, 14
th
. Each record is saved into the log file
every 5 minutes, starting at 05:00 until 22:00. Each log file contains a header that contains the
version of the software that has produced the log and data information; the file can be imported in
Excel for graphs and analysis. The values are semicolon separated.
The record, namely a single line of the file, has the following fields:
1.
Time information, in HH:MM (hour:minute)
2.
Instant power, in KW.
3.
Reactive instant power, in KW
4.
Active instant power, in KW
5.
External measure
6.
Inverter module temperature, in Celsius
7.
Daily energy, in KWh
8.
Grid frequency, in Hz
9.
Grid phase R instant power, in W
10.
Grid phase S instant power, in W
11.
Grid phase T instant power, in W
12.
Grid phase R reactive power, in W
13.
Grid phase S reactive power, in W
14.
Grid phase T reactive power, in W
15.
Grid voltage, phase R, in V
16.
Grid voltage, phase S, in V
17.
Grid voltage, phase T, in V
18.
PV voltage input 1, in V
19.
PV voltage input 2, in V
20.
PV voltage input 3, in V
21.
PV current input 1, in A
22.
PV current input 2, in A
23.
PV current input 3, in A
24.
Latched alarms 1
25.
Latched alarms 2
26.
Latched alarms 3
27.
Latched alarms 4
28.
Latched alarms 5
29.
Boost temperature, in °C
30.
Spare 1
31.
Spare 2
32.
Spare 3
33.
Spare 4
All the measures values are average values, calculated in a five
minutes’ period of time.
This file can be sent by e-mail on a daily, weekly or monthly basis. See configuration for details.