Cabinet
temperature
is too high or
too low
•
poor room conditions
•
check the position of the cabinet inside the store
•
output air temperature is outside
the specified range
•
incorrect controller parameters
•
check the operation of evaporator fan
•
check wiring and input voltage
•
the fans are installed reversely; check and restore
the air flow direction
•
check that fan plenum is sufficient and not ob-
structed
•
check the intake pressure that should comply with
rated specifications
•
check and reset the incorrect parameters
•
the cabinet is defrosting.
•
check defrosting parameters
•
the capacitor or the evaporator are
freezing.
•
check that the suction line is not obstructed
•
the capacitor or the evaporator are
obstructed or dirty.
• proceed to cleaning chap.22.5
•
the load is not distributed evenly
•
load the goods in an orderly manner (Fig.12)
Water leaks,
bad smell
•
cabinet drains are obstructed or
damaged
• clear the drains
• repair or replace the drains
•
water collection tray is sealed in-
correctly
•
seal it properly
•
water collection tray overflows
•
check wiring of evaporation heater
•
check the operation of evaporation heater
•
lacking joints between cabinets in
channel or not sealed incorrectly
•
install and seal the joints
Frost or ice
in the cabinet
•
fans do not work
in the evaporator
•
heating elements broken
•
Sdef probe detached
•
check electrical connections
•
check the electrical continuity of the hot cables
• air currents that alter the circula
-
tion of refrigerated air
•
check the ventilation inside the store
i
in all cases not described or where it is not possible to solve the problem by following these
directions call the nearest authorised after-sales centre.