Armstrong Steam QM-3 Calibration Manual Download Page 11

Armstrong International
IOM-246-V2.0
Steam QM-3 Calibration

Page 9 of 14

 

Calibrating the Heater

Calibration #5: Calibrating the Heater 

 

                                                                                                             

 

 

 

 

 

 

    

 

 

 

 

 

 

        

 

                                                                                                                                   

                                                                                                                                                                                                                                                                   

 

      1.   Turn off Steam QM-3 and unplug from power source.

 

      2.   Release latch on Harting connector and unplug from the Steam QM-3 cabinet.

 

      3.   With a calibrated ohmmeter measure the resistance between pin 8 and 16 on the Harting plug. The reading should  

 

          be between 100Ω and 200Ω (normal is about 150Ω). If the reading is lower than 100Ω or higher than 200Ω replace  

       the 

heater.

 

4.  If the reading is in accepted range, record it. The reading will need to be entered after the Steam QM-3 is powered up.

 

5.  Plug the Harting plug into the Steam QM-3 cabinet, plug in the power cord, and turn on the Steam QM-3.

 

6.  On the Steam QM-3 display pad, press left and right arrows simultaneously to access the code menu.

 

7.  To access the resistance calibration menu, enter 069 using the up and down arrows to change numbers,  

 

    and the left and right arrows to change the position. 

65 

   

ß

 

 

8.  Move the arrow to the Rheater line ( using up and down arrows). 

 

9.  Move the arrow to left of value and enter measured value rounded to nearest whole ohm value  

 

    (example 153.3 is entered as 153).

 

10.  Confirm the re-calibration of the resistance of the heater by signing the relevant box on the re-calibration certificate.

noTE:

 Any corrections to the calibration certificate must be done following good documentation practices. The error is crossed 

through by a single line. The correction is written alongside with an explanation if necessary. The correction is signed and dated.

Harting plug being removed

Harting plug pin 8 and 16 

Resistance calibration menu 069

  

Calibration

Rheater

P

10W

30W

Rheater

146 

T3

`

m

65    

ß

           01

Heater

Summary of Contents for Steam QM-3

Page 1: ...auts Sarts 2 me avenue 4 4040 HERSTAL BELGIUM T l 32 0 4 240 90 90 Fax 32 0 4 240 40 33 armstronginternational com Keep this manual with equipment for future reference STEAM QM 3 Steam Quality Monitor...

Page 2: ...ginternational com Armstrong Contents Revision History 1 Safety 2 Abbreviations and Acronyms 3 General Information 4 Recalibration Procedure 6 Calibrating the Temperature Sensors 6 Calibrating the Pre...

Page 3: ...librated Page 6 Recalibration Procedure Section Point 3 has been added Remove the Temperature Sensor T1 after unplugging it and plug it back in before install it in oil bath Calibrating the Temperatur...

Page 4: ...ualified person Installation should always be accompanied by competent technical assistance Improper installation start up operation maintenance or service may void warranty You are encouraged to cont...

Page 5: ...seconds DIN Deutsches Institut f r Normung eV dP Differential Pressure EC European Community EEC European Electrotechnical Commission EN European Norm EV Electronic Valve F Fahrenheit gal Gallon h Hou...

Page 6: ...nsors in the oil bath and recreate the actual temperatures for calibration This method is not covered in this document Pressure transmitter The pressure sensor is calibrated by simulating the voltage...

Page 7: ...ibrated on the Steam QM 3 The instruments are 3 temperature sensors 1 pressure transmitter 1 heating element 1 condensate flow meter 1 gas flow meter NCG meter 2 differential pressure sensors Heating...

Page 8: ...4 If not you must adjust the sensor 11 On the Steam QM 3 display pad press left and right arrows simultaneously to access the code menu 12 Enter 234 using the up and down arrows to change numbers and...

Page 9: ...edure in step 1 for T3 Temperature sensor NOTE Any corrections to the calibration certificate must be done following good documentation practices The error is crossed through by a single line The corr...

Page 10: ...the Steam QM 3 display pad press up and down arrows simultaneously to access the Debug sensor menu 7 Write the value of P1 on the calibration certificate If P1 is 0 1 bar regarding the set point 0 bar...

Page 11: ...d press left and right arrows simultaneously to access the code menu 7 To access the resistance calibration menu enter 069 using the up and down arrows to change numbers and the left and right arrows...

Page 12: ...alve from the draw vessel slowly to establish a cycle rate of the EV2 valve of approximately 30 seconds One cycle is from opening to closure of valve you should be able to hear this If the environment...

Page 13: ...ertificate NOTE Any corrections to the calibration certificate must be done following good documentation practices The error is crossed through by a single line The correction is written alongside wit...

Page 14: ...r syringe before resetting to 2ml 8 With the NCG injector syringe disconnected reset the syringe to 2ml 9 Connect the NCG injector syringe to the middle of the NCG injector assembly tee with a 6mm tub...

Page 15: ...w sensor calibration menu 24 On the Steam QM 3 display pad press left and right arrows simultaneously to access the code menu 25 To access the flow sensor calibration menu enter code 123 using the up...

Page 16: ...er draw vessel connecting to the bottom of the NCG burette use two wrenches 10mm and 11mm to ensure no damage to the NCG burette occurs Reconnect the expansion coil to the bottom of the NCG burette us...

Reviews: