Maximum Allowable Intake or Exhaust Vent Length in Feet
Standard Termination at Elevation 0 - 4,500 ft
Number
of 90°
Elbows
Used
1-1/2” Pipe
2” Pipe
2-1/2" Pipe
3" Pipe
Model
Model
Model
Model
030
045
70
90
110
030
045
70
90
110
030
045
70
90
110
030
045
70
90
110
1
25
n/a
n/a
n/a
76
61
39
19
110
110
88
53
133
132
113
113
2
20
71
56
34
14
105
105
83
48
128
127
108
108
3
15
66
51
29
9
100
100
78
43
123
122
103
103
4
10
61
46
24
n/a
95
95
73
38
118
117
98
98
5
n/a
56
41
10
90
90
68
33
113
112
93
93
6
51
36
14
85
85
63
28
108
107
88
88
7
46
31
9
80
80
58
23
103
102
83
83
8
41
26
n/a
75
75
53
18
98
97
78
78
9
36
21
70
70
48
13
93
92
73
73
10
31
16
65
65
43
8
89
87
68
68
Standard Termination at Elevation 4,501 - 10,000 ft
Number
of 90°
Elbows
Used
1-1/2” Pipe
2” Pipe
2-1/2" Pipe
3" Pipe
Model
Model
Model
Model
030
045
70
90
110
030
045
70
90
110
030
045
70
90
110
030
045
70
90
110
1
25
n/a
n/a
n/a
76
61
39
n/a
110
110
88
53
133
132
113
113
2
20
71
56
34
105
105
83
48
128
127
108
108
3
15
66
51
29
100
100
78
43
123
122
103
103
4
10
61
46
24
95
95
73
38
118
117
98
98
5
n/a
56
41
19
90
90
68
33
113
112
93
93
6
51
36
14
85
85
63
28
108
107
88
88
7
46
31
9
80
80
58
23
103
102
83
83
8
41
26
n/a
75
75
53
18
98
97
78
78
9
36
21
70
70
48
13
93
92
73
73
10
31
16
65
65
43
8
88
87
68
68
*Size intake and exhaust pipe length separately. Values in table are for intake or exhaust, not combined total. Both Intake and Exhaust
must be same pipe size.
Table 5A.