4100-HCF2
Revision 3.0
P a g e 34 | 35
10.0 MODBUS MAP AND DETAIL (OPTIONAL)
2 Wire RS-485 (1/2 Duplex)
9600 Baud, Even parity, 8 Data bits, 1 stop bit.
For connection to a PC, an RS-485 to USB converter module and modbus software (Modbus Poll,
DAQfactory, etc.) be used.
The following RS-485-USB converter has been tested with the system:
Model: UT-850
(Manufacturer: Gridconnect)
10.1 Modbus Commands Supports
After Read Coil Status Function Code: 01. Used to read relays output from PLC
Read Holding Registers Function Code: 03. Used to read values from PLC
10.2 Register Map
Read coils status (01)
coil
DESCRIPTION
TYPE
00001 relay 1 - low oil alarm (Q0.0)
bit
00002 relay 2 – Air alarm or Oil alarm (Q0.1)
bit
00003 relay3 - Fault or Oil alarm (Q0.2)
bit
00004 relay 4 –
Oil alarm or Pump run, or Level sensor_mA input level alarm (Q0.3)
bit
00005 relay 5 - Strobe alarm (Q0.4)
bit
00006 relay 6 - Buzzer output (Q0.5)
bit
Read Holding Registers (03)
REG
DESCRIPTION
TYPE
No.
of
Reg
40001 Depth of oil for 100%
real
2
40003 Calibration Slope
real
2
40005 Calibration Offset
real
2
40007 A value
real
2
40009 K value
real
2
40011 C value
real
2
40013 Calibration point CAL 1 (Unit)
real
2
40015 Calibration point CAL 2 (Unit)
real
2
40017 Calibration point CAL 1 (pF) capacitance
real
2
40019 Calibration point CAL 2 (pF) capacitance
real
2
40021 Depth of Oil
real
2
40023 Percent of Oil
real
2
40025 Level sensor_mA input level depth
real
2
40027 Level sensor_mA input level percent
real
2