8.0 TROUBLESHOOTING
Main Panel
Press
“ ”
for some troubleshooting tips.
Condition: Power Supply Status
x
Confirm the Power Supply LED is active (Green).
Condition: Power Input Status
x
Confirm the Power input is 100-240 VAC using a
meter.
x
Confirm if input fuse has blown.
Condition: Communication Error
x
Means no communication between 4100 Signal
Converter (A00740) and RS485 (CM1241) Module.
x
Under normal operating conditions, both LED’s
should be Lit and Flashing continuously.
x
Check wiring between 4100 Signal Converter
(A00740) and RS485 (CM1241) Module.
x
Confirm 24VDC power to 4100 Signal Converter
(A00740).
GREEN LED