2880R-LT, 2881R-LT, 2882R-LT
Revision 1.0
P a g e 14 | 28
5.1
Input / Output Terminal Specification
Input Terminals – Power Source
Terminal
ID
Overvoltage
category
Rated Voltage
(V)
Rated
Current/power
(A/W/VA)
___ HZ or
DC
Specified
Mains
fluctuation
TB3 II
100-240V 150mA
50/60Hz
±
10%
TB3
II
12 OR 24V
250mA
DC
+
15%
−
10%
Input Terminals – Measuring Circuits
Terminal
ID
Function
Measurement
Category
Nominal a.c. or
d.c line to
neutral voltage
/ if CAT I, Max.
transient
overvoltage Ut
Nominal
a.c. or d.c
current
Rating of
insulation
required for
external
circuit
TB6
Frequency
I
N/A
--
DI * or RI**
TB4
RS485
Communication
I
5V, 5mA / 0
--
DI * or RI**
*
Double Insulation
**
Reinforced Insulation
Output Terminals
Terminal
ID
Function
Isolation or
protection
Rated V, A
Max. V, A
Load type
and nominal
TB1 Load
Relay
3A Contact
@250VAC
-- --
TB2 Load
Relay
3A Contact
@250VAC
-- --
TB5 Current
Isolator(optional)
- 18V,20mA,
900
Ω
- 9V, 20mA,
450
Ω
50mA@18V --