ARJAY ENGINEERING 2880R-LT User Manual Download Page 11

 

2880R-LT, 2881R-LT, 2882R-LT

 

Revision 1.0

 

P a g e  11 | 28

 

4.2

 

Probe Installation 

 

NOTICE 

Read the following information 

before

 installation.

 

 
Standard probe entry into a tank is via a 3/4" NPT opening (standard probes) or 1" NPT opening 
(heavy duty probes).  Flanges and concentric shields are available as options.  The entrance 
configuration may vary depending on the application requirements. 
 
TO SCREW IN THE PROBE (THREADED ENTRY) USE A WRENCH ON THE LOWER FITTING 
ONLY.  The probe fittings are compression type with Teflon ferrules assembled by applying torque 
between the two sections.  The fittings are sealed at the factory to provide a compression seal 
capable of withstanding pressure up to 1500 psi / 10342kPa. Once opened they cannot be 
reassembled without new ferrules. 
 
The probe should be mounted vertically and parallel to a reference ground surface, which is 
typically the vertical wall of the tank or a concentric shield around the probe.  The following points 
are important when installing the probe: 
 
1- 

Reference ground:

  This is important for accurate measurements and is typically the metal 

walls of the tank.  For non-metallic tanks, a concentrically shielded probe is required in which 
case the shield provides its own Ground.  IMPORTANT: For standard threaded entry and flange 
entry probes (without concentric shields), make sure the fittings are clean to ensure a GOOD 
ELECTRICAL CONNECTION BETWEEN THE PROBE HEAD ENCLOSURE AND THE TANK 
(REFERENCE GROUND). 

 
2- 

The distance between the probe and the ground reference:

  This only applies to probes 

without concentric shields.  The closer the distance to the tank wall, the greater the sensitivity of 
measurement; too close and bridging problems may occur with more viscous material. The 
distance should be greater than 25mm. 

 
3- 

The degree of parallelism between the probe and the reference ground:

  The probe must 

be parallel to the reference ground for a linear output signal.  Note: the concentric shield option 
is inherently linear due to the concentric shield. 

 
4- 

The measurement accuracy may be affected by the temperature change of the material in 
the tank.

 The amount of measurement error depends on the material.  If the temperature 

change is excessive, temperature correction may be required.  Contact the Arjay representative 
for more information. 

 
5- 

Agitators or moving objects in the tank:

 Moving objects in the tank close to the probe such 

as agitator blades, moving baffles etc. appear as moving ground references to a capacitance 
probe and will cause measurement errors.  In applications where these objects are present, a 
concentrically shielded probe should be used. 

 

NOTICE 

Install the probe with care. Teflon sheath is used to electrically isolate 
the metal probe from the liquid. Damage causing leaks may cause 
reading errors.

 

 
 

Summary of Contents for 2880R-LT

Page 1: ... LT 2882RW LT REMOTE MOUNTED LEVEL MONITOR USER MANUAL REV 1 0 ARJAY ENGINEERINGLTD 2881R Brighton Road Oakville Toronto Canada L6H 6C9 TEL 1 905 829 2418 FAX 1 905 829 4701 NORTH AMERICA 1 800 387 9487 WEBSITE www arjayeng com EMAIL arjay arjayeng com ...

Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 3: ...AC Powered Models Only 15 5 3 Glossary Of Symbols 15 6 0 STARTUP AND CALIBRATION 16 6 1 Startup 16 6 2 Menu Flow Chart Back Chart Background Information 16 6 2 1 Menu Short Form 16 6 2 2 Menu Description 17 6 2 3 Data Entry 17 6 3 288XR Controller Setup 17 6 3 1 Setup And Network 17 6 3 2 Relay Setup Menu 18 6 4 288XR Controller Calibration 20 6 4 1 Auto Calibration 20 6 4 2 Manual Calibration 20 ...

Page 4: ...er values Communication Interface Modbus RS485 Relays Analog Outputs Relay Outputs 2 SPDT relays Dry Contacts are 3A 250 VAC Resistive selectable failsafe or non failsafe selectable high or low acting alarm programmable time delay 0 600 seconds 0 100 differential 2881R Or 2881RW Isolated mA Signal Output 4 20 mA 900 Ohms max 24VDC Power OR 450 Ohms max 12VDC Power Optional Note If Isolation is ord...

Page 5: ...one 1 AEx db IIC T5 Gb International IECEx ATEX II 2G Ex db IIC T5 Gb Sira 17ATEX1303X IECEx CSA 17 0034X SPECIFIC CONDITIONS OF USE FOR HAZARDOUS LOCATION denoted by X after the certificate number 1 Process temperature for the standard and heavy duty probes are 60 C to 200 C and for flexible probe is 60 C to 100 C It is end user s responsibility to ensure that the ambient around the Capacitance C...

Page 6: ...50 60Hz 6 Explosion Proof Without Window North America 81R LS 2 N A 7 Explosion Proof Without Window ATEX IECEx North America 82R OWS 3 12 VDC 8 Explosion Proof With Window ATEX IECEx North America 80RW OWI 4 24 VDC 81RW CAP 82RW FCM FCS IFA W Window Option 2880R 2881R 2880RW 2881RW available for these models only ...

Page 7: ...ARNING Indicates a potentially or imminently hazardous situation which if not avoided could result in death or serious injury DANGER Indicates a potentially or imminently hazardous situation which if not avoided will result in death or serious injury NOTICE Indicates a situation which if not avoided may cause damage to the instrument Information that requires special emphasis ...

Page 8: ...structed of a Teflon coated probe The probe length is customer specified for the tank and depth of material to be measured Probes can be inserted vertically or angled into the tank The importance is that the probe must be parallel to the tank wall when inserted for best linearity A concentric shielded probe is available as an option to improve linearity and achieve a parallel ground reference The ...

Page 9: ...remote calibration via network User specified custom features may be added by contacting Arjay Engineering Ltd 3 2 Model Number Table MODEL DESCRIPTION 2880R LT REMOTE MOUNTED 4 20mA NON ISOLATED 2880RW LT REMOTE MOUNTED 4 20mA NON ISOLATED WINDOW MOUNT 2881R LT REMOTE PROBE MOUNTED 4 20mA ISOLATED 2881RW LT REMOTE MOUNTED 4 20mA ISOLATED WINDOW MOUNT 2882R LT REMOTE MOUNTED 4 20mA NON ISOLATED C ...

Page 10: ...ween controller and probe Check the polarity of the and wiring between the controller and the PMC prior to powering on the unit to and to to avoid damage Shield of cable should be connected to secondary ground terminal marked as at controller side only Incoming Earth ground should be connected to primary ground terminal marked on sub plate NOTICE The controller operates in a Failsafe Mode factory ...

Page 11: ...robes without concentric shields make sure the fittings are clean to ensure a GOOD ELECTRICAL CONNECTION BETWEEN THE PROBE HEAD ENCLOSURE AND THE TANK REFERENCE GROUND 2 The distance between the probe and the ground reference This only applies to probes without concentric shields The closer the distance to the tank wall the greater the sensitivity of measurement too close and bridging problems may...

Page 12: ...2880R LT 2881R LT 2882R LT Revision 1 0 P a g e 12 28 Figure 2 Probe Installation ...

Page 13: ...set in a Failsafe mode TB3 Power Input Power input as per Model Check if ordered AC or DC Earth ground is connected to Primary ground screw inside of enclosure TB4 Network Output Connect RS485 and to the network D and D TB5 mA Output Optional Isolator for Model 2881R The 4 20mA is a sourced output referenced to Ground It is not loop powered TB6 Probe Input Probe is factory wired to P terminal of P...

Page 14: ...minal ID Function Measurement Category Nominal a c or d c line to neutral voltage if CAT I Max transient overvoltage Ut Nominal a c or d c current Rating of insulation required for external circuit TB6 Frequency I N A DI or RI TB4 RS485 Communication I 5V 5mA 0 DI or RI Double Insulation Reinforced Insulation Output Terminals Terminal ID Function Isolation or protection Rated V A Max V A Load type...

Page 15: ...he symbols to its ON and OFF positions using the following symbols Power Off Power On 5 The wiring for AC power should be minimum 18 AWG 300V or as required by local country codes 6 After field wiring the primary wires must be secured to the enclosure by tie wraps to maintain the separation from the signal wires 7 Wiring diagram for permanent connection See drawings at the back of this manual 8 Us...

Page 16: ...ration are accessed using the display and keypad on the controller The Flow Chart in Section 10 0 provides an overview to the various menus and features Keep a copy of the flow chart at hand when accessing the internal controller features Below is a description of the menu functions 6 2 1 Menu Short Form Since the 288XR controller has a small LCD some menu description may be in short form The foll...

Page 17: ...operator to change the configuration set up values indicated in the View Changes will be required for the initial setup of relay setpoints delays span etc or to re set the values to the factory default 6 2 3 Data Entry Data Entry Press key to increase decrease the digital value Press SELECT key to move the cursor Press MENU key to abort certain screens 6 3 288XR Controller Setup Power up the 288XR...

Page 18: ...is used to smooth data from a sudden change and minimize fluctuating readings For example a 5 second setting means the calculated value of the capacitance and resulting values of pF will start to respond immediately but will take 5 seconds to reach their final values The factory default is 0 to provide an immediate and active response This can be user selected from 0 99 9 seconds 8 Password The un...

Page 19: ... Factory default is Yes The following table shows the effect of the Relay Action and Failsafe settings Relay Action Failsafe Setting Effect High No Alarm condition when process level rises above the High Setpoint for at least the alarm delay period Alarm condition remains active until the process level drops below the Low Setpoint No action is taken when the process level is between the High and L...

Page 20: ...calibration point has been done If the calibration is successful the display will show Cal Ok for a couple of seconds and then return to the calibration menu If the display shows Cal Err then a calibration fault has occurred Check the following 1 The 2nd level entry value is accidentally left at the 1st calibration point level Re do the auto calibration according to the above steps 1 3 2 The level...

Page 21: ...ion to an Arjay Remote Access monitor or customer control system which allows viewing data and setup of any of the transmitters on the network The 4 20mA output may still be used if necessary 2 Setup for the 28XX for network operation Each 28XX controller must have a unique number to connect in a network system See section 10 0 Menu Flow Chart CHANGE menu for details to change the ID number Where ...

Page 22: ...loat 2 Optional 40034 33 Cal1 pF Level calibration 1st capacitance value in pF float 2 Optional 40036 35 Cal2 pF Level calibration 2nd capacitance value in pF float 2 Optional 40038 37 Relay 1 Differential High Alarm float 2 Optional 40040 39 Relay 2 Differential High Alarm float 2 Optional 40042 41 Relay 1 Differential Low Alarm float 2 40044 43 Relay 2 Differential Low Alarm float 2 40046 45 Rel...

Page 23: ...2880R LT 2881R LT 2882R LT Revision 1 0 P a g e 23 28 8 0 MAINTENANCE There is no routine cleaning required for this controller ...

Page 24: ...OUT FROM THE mA OUTPUT TERMINAL THIS TERMINAL SHOULD NOT BE CONNECTED TO 24V IT IS NOT A 2 WIRE mA TRANSMITTER See Figure 3 for Electrical hookup details Disconnect external wires from mA output and measure with mA Meter Check the mA output Action direct or inverse and mA output Span are set as desired See section 10 0 Flow chart Change menu If the mA output still does not match the level then cal...

Page 25: ...2880R LT 2881R LT 2882R LT Revision 1 0 P a g e 25 28 ARJAY ENGINEERING TECHNICAL SUPPORT 800 387 9487 1 905 829 2418 www arjayeng com ...

Page 26: ...CT Press SELECT NORMAL OPERATING DISPLAY Press Press Press Press Press Press Password 0000 Password 2000 See Note 1 See Note 3 CALIBRTE Auto Cal CALIBRTE Man Cal CALIBRTE Exit 1 xxx x xx x pF 2 xxx x xx x pF Cal ok Cal Err xxxxxx Press SELECT Press SELECT Press SELECT Press SELECT or 2 xxx x 2 pF xxx x Cal ok Cal Err xxxxxx Press SELECT or Press SELECT 1 xxx x 1 pF xxx x Press SELECT Press SELECT ...

Page 27: ...2880R LT 2881R LT 2882R LT Revision 1 0 P a g e 27 28 ...

Page 28: ...2880R LT 2881R LT 2882R LT Revision 1 0 P a g e 28 28 ...

Reviews: