8
MECHANICAL INSTALLATION
The system delivery usually also includes a boiler, burner auger, auger motor, automation system
and storage. These are selected based on the type of fuel and fuel storage being used.
Installing the burner in the boiler
The burner can be installed in a solid fuel boiler, the power rating of which corresponds to the
power of the burner. The underpressure required for the reliable and correct operation of the
burner (25-30 pa in the fire chamber) can be ensured either by a correctly dimensioned chimney
or an underpressure-controlled flue gas extractor.
We recommend that compatibility with anything other than an Ariterm boiler is checked by the
burner manufacturer.
The burner is fixed by its flange to the boiler with bolts and the seam is sealed with heat-
resistant silicone (1). The joints must be sealed so well that they are completely air-tight! The
bolts are tightened diagonally. If the boiler opening and burner flange are of different sizes, for
the purposes of installation, a suitable installation flange must be made.