12
Condition type
Description
Maximum loops exceeded in a
network
The number of loops in a fire network exceeds the
maximum allowed
New node in the fire network
A control panel has been added to the fire network
Output group activation
An output group is activated
Prealarm
A device (and corresponding zone) is in prealarm
Sounder, fire routing, and fire
protection delays
A sounder, fire routing, or fire protection delay is enabled or
disabled
Tests
A control panel feature or device is being tested
[1] These condition types only apply if an extinguishing panel is included in the fire network.
Status indications
This section includes a summary of the control panel status indications.
Standby
Standby is indicated as follows:
•
The Supply LED is steady
•
If a sounder delay has been enabled the Sounder Delay LED is steady
•
If a fire routing de
lay has been enabled the Fire Routing Delay LED is steady
•
If a fire protection delay has been enabled the Fire Protection Delay LED is
steady
Note:
Depending on your fire system configuration the buzzer may sound
intermittently to indicate an enabled delay condition.
Fire alarm
In
accordance with European standards, fire alarm status is indicated on the
control panel LCD by zone (and not by device).
When an alarm is reported in more than one zone, the LCD displays two zone
messages: the first for the first zone to report an alarm and the second for the
most recent zone to report an alarm, as shown below.
Figure 4: Fire alarm indication on the control panel LCD