Each zone message indicates:
•
The zone identifier and description, the timestamp, and the device description
of the first alarm reported in the zone
•
A counter with the total number of devices in alarm in the zone.
To see the details of the devices in alarm, press F1 (Show Events) and select
Alarms. Then select the corresponding zone reporting the alarm. A list of devices
in alarm for the zone is displayed.
Additional fire alarm status indications are:
•
The control panel Alarm LED flashes if the alarm is activated by a detector or
is steady if it is activated by a manual call point.
•
If a zone board is installed and the corresponding zone is included on the
zone board, then the zone alarm LED is flashing or steady (depending on the
source of the alarm).
•
If a sounder delay has been enabled the Sounder Delay LED is steady.
•
The Sounder Delay LED flashes while the delay is counting.
•
The Sounder Start/Stop LED indicates the Sounder Start/Stop button status
(disabled, not disabled) and the status of the sounders (see Table 3 on page
5 for more information).
•
If a fire routing delay has been enabled the Fire Routing Delay LED is steady.
The Fire Routing Delay LED flashes while the delay is counting.
•
When fire routing is activated, the Fire Routing ON/Acknowledged LED
flashes
. If configured to do so by your installation or maintenance contractor,
a steady Fire Routing ON/Acknowledged LED indicates that the fire routing
signal has been acknowledged by the remote monitoring equipment.
•
If a fire protection dela
y has been enabled the Fire Protection Delay LED is
steady. The Fire Protection Delay LED flashes while the delay is counting.
•
When fire protection is activated, the Fire Protection ON/Acknowledged LED
flashes. If configured to do so by your installation
or maintenance contractor,
a steady Fire Protection ON/Acknowledged LED indicates that the fire
protection signal has been acknowledged by the remote monitoring
equipment.
•
Alarm information for the first and last zones to report an alarm is displayed
on the LCD.
•
The control panel buzzer sounds continuously.
Alarms activated by a manual call point always take priority over alarms activated
by a detector. When an alarm is activated by both devices, the Alarm LED is
steady.