26
1X-F Series Operation Manual
Regulatory information
European standards for fire control and indicating equipment
These control panels have been designed in accordance with European EN 54-2,
EN 54-4, BS 5839-1, NBN S 21-100, and NEN 2535 standards.
In addition, all models comply with the following EN 54-2 optional requirements:
Table 7: EN 54-2 optional requirements
Option
Description
7.8
Output to fire alarm devices
Note: Inputs and outputs on the optional 2010-1-SB expansion I/O board do not
support the optional requirement of EN 54-2 clause 7.8 and should not be used for
fire alarm devices.
7.9.1
Output to fire alarm routing equipment [1]
7.9.2
Alarm confirmation input from fire alarm routing equipment [1]
7.10
Output to fire protection equipment (type A) [2]
7.11
Delays to outputs
7.13
Alarm counter [3]
8.4
Total loss of the power supply
8.9
Output to fault warning routing equipment [2]
10
Test condition
[1] Excluding two-zone models.
[2] NEN 2535 operating mode only.
[3] Dutch models only.
EN 54-13 European compatibility assessment of system components
These control panels form part of a certified system as described by EN 54-13
when installed and configured for EN 54-13 operation as described by the
manufacturer in the corresponding installation documentation.
Contact your installation or maintenance contractor to determine if your fire
system is compliant with this standard.
European standards for electrical safety and electromagnetic compatibility
These control panels have been designed in accordance with the following
European standards for electrical safety and electromagnetic compatibility:
• EN 62368-1
• EN 50130-4
• EN 61000-6-3
• EN 61000-3-2
• EN 61000-3-3