1X-F Series Operation Manual
15
Cancelling an active fire routing delay (or warning delay for NBN S 21-100)
If a fire routing delay (or warning delay for NBN S 21-100) is enabled and active,
press the Fire Routing ON button (or Warning Start/Stop button for
NBN S 21-100) or the Fire Routing Delay button (or Warning Delay button for
NBN S 21-100) to cancel the delay and activate fire routing (or warning for
NBN S 21-100) immediately.
A fire routing delay (or warning delay for NBN S 21-100) is indicated as follows:
• Steady Fire Routing Delay LED (or Warning Delay LED for NBN S 21-100): A
delay is enabled.
• Flashing Fire Routing Delay LED (or Warning Delay LED for NBN S 21-100)
during a fire alarm: A configured delay is active. Fire routing (or warning for
NBN S 21-100) is activated when the configured delay elapses or when the
delay is cancelled.
A fire alarm activated by a manual call point overrides any configured delay and
activates fire routing (or warning for NBN S 21-100) immediately.
Performing a control panel LED indicator and control panel buzzer test
To perform a control panel LED indicator and buzzer test, press and hold the
Test button for more than 3 seconds.
The test is indicated as follows:
• General Fault LED: Flashing.
• System Fault LED: Flashing.
• All other LEDs: On steady.
• Control panel buzzer: Sounding continuous.
The test continues as long as the Test button remains pressed (with an
automatic timeout of 12 seconds). When the test is completed the control panel
returns to its former state.
Note:
Devices connected to the control panel fault relay will also be activated for
the duration of this test.