14
1X-F Series Operation Manual
Public user level operation
Public user level operations are those that can be performed by any user. No
password is required to perform tasks at this level.
Public user level operation lets you:
• Acknowledge a system event and silence the control panel buzzer
• Cancel an active sounder (or evacuation for NBN S 21-100) delay
• Cancel an active fire routing (or warning for NBN S 21-100) delay
• Perform a control panel LED and buzzer test
• Display local indications only (for control panels with repeater functionality)
Acknowledging a system event and silencing the control panel buzzer
To acknowledge a system event and silence the control panel buzzer, press the
Panel Silence button.
A steady Panel Silence LED indicates that the buzzer was silenced and that all
current events are acknowledged.
Cancelling an active sounder delay (or evacuation delay for NBN S 21-100)
If a sounder delay (or evacuation delay for NBN S 21-100) is enabled and active,
press the Sounder Delay button (or Evacuation Delay button for NBN S 21-100)
to cancel the delay and activate sounders immediately.
Sounders (for EN 54-2 evacuation) and evacuation (for NBN S 21-100) can
cancel the delay and activate sounders immediately by pressing the Sounder
Start/Stop button (or evacuation Start/Stop button for NBN S 21-100).
A sounder delay (or evacuation delay for NBN S 21-100) is indicated as follows:
• Steady Sounder Delay LED (or Evacuation Delay LED for NBN S 21-100): A
delay is enabled.
• Flashing Sounder Delay LED (or Evacuation Delay LED for NBN S 21-100)
during a fire alarm: A configured delay is active (sounders are activated when
the configured delay elapses or when the delay is cancelled).
A fire alarm activated by a manual call point overrides any configured delay and
activates sounders immediately.