The flue connector has two apertures, readings can be taken for
the temperature of the combustion by-products and of the
combustion air, as well as of the concentrations of O

2

and CO

2

,

etc. .
To access these intakes it is necessary to unscrew the front
screw and remove the metal plate with sealing gasket.
To achieve the best test conditions, turn the central heating
adjustment knob “

G

” to the “

max

” position and remove the

electrical connection to the heating sensor (see section 6.). This
will allow the appliance to operate at the maximum heating
power.

4.5

C

OMBUSTION

A

NALYSIS

F

IG

. 4.2

In the boiler, it is possible to monitor the correct operation of
the flue exhaust/air intake, checking for a loss of general
pressure in the system. Through the use of a differential
manometer connected to the test points of the combustion
chamber, it is possible to detect the 

P of operation of the air

pressure switch.
The value detected should not be less than 0.5 mbar under
conditions of maximum thermal power in order for the boiler
to function properly and without interruption.

4.6

F

UME

D

ISCHARGE

M

ONITORING

F

IG

. 4.3

4. Press the reset button 

“E”

for the lighting system; the spark will light the main

burner. If the burner does not light the first time, repeat the procedure.

5. Check the minimum and maximum pressure values for the gas going to the

bur ner ; adjust it if needed using the values indicated in the table in
section 5 (See the relative section for burner pressure adjustment within the
servicing manual).

The boiler is fitted with the following devices (see section 4.2 for references).

1 -

I

GNITION

F

AILURE

:

This indicates ignition failure when a flame is not detected within 7 seconds of
starting an ignition sequence. The L.E.D.

“F”

will illuminate to signal the

shutdown status.
The system can be reset by pressing and releasing the button 

“E”

after

checking to make sure that the gas cock is open.

2 - 

I

NSUFFICIENT

S

YSTEM

P

RESSURE

:

In the event of insufficient water pressure in the heating system, a safety device
will shutdown the boiler. Check the system pressure on the pressure gauge 

“J”

and if it is less than 0.4 bar refill the system to 1.5 bar. Once the system
pressure is at the correct level the boiler will ignite automatically.

3 -  

O

VERHEATING

:

This control shuts off the boiler in the case where the primary circuit reaches a
temperature in excess of 105°C.
The red L.E.D.

“F”

will illuminate to signal this shutdown status.

The system can be reset by waiting a few minutes for the primary exchanger to
cool down and then by pressing and releasing the “

E

” button.

4.7

B

OILER

S

AFETY

S

YSTEMS

Summary of Contents for microSYSTEM 10 RFFI

Page 1: ...Installation Instructions Type C Boilers G C N 41 116 04 LEAVE THESE INSTRUCTIONS WITH THE END USER Country of destination GB IE...

Page 2: ...L VIEW 2 INSTALLATION 2 1 DELIVERY 2 2 REFERENCE STANDARDS 2 3 SITING THE APPLIANCE 2 4 OVERALL DIMENSIONS 2 5 CLEARANCES 2 6 MOUNTING THE APPLIANCE 2 7 ELECTRICAL CONNECTION 2 8 GAS CONNECTION 2 9 WA...

Page 3: ...immediately If you are going away for a long period of time remember to shut the mains gas tap or the gas cylinder valve Always disconnect the appliance either by unplugging it from the mains or turni...

Page 4: ...ing Regulations the bylaws of the local water authority in Scotland in accordance with the Building Standards Scotland Regulation and Health and Safety document No 635 Electricity at work regulations...

Page 5: ...uld be made to the current edition of I S 813 and the current ETCI rules If the boiler is to be sited into a timber framed building reference must be made to the current edition of the Institution of...

Page 6: ...een wire should be connected to the terminal marked with the symbol The blue wire should be connected to the terminal marked N The brown wire should be connected to the terminal marked L Note The diag...

Page 7: ...region contractor connects the gas meter to the service pipe The gas installation should be in accordance with the relevant standards In GB this is BS6891 and in IE this is the current edition of I S...

Page 8: ...ation R24 2 of the water regulations guide and for IE the current edition of I S 813 FILLING A temporary method for initially filling the system and replacing lost water during servicing and initial f...

Page 9: ...number A suitable terminal guard is available from TOWER FLUE COMPONENTS Morley Road Tonbridge Kent TN9 1RA The minimum acceptable spacing from the terminal to obstructions and ventilation openings ar...

Page 10: ...l N 4 For the time clock connect the clock switching wires to the positions 3 and 4 and connect the clock motor electrical supply to the terminals marked L and N Note A frost thermostat is built in to...

Page 11: ...FIG 2 13 11 FIG 2 12...

Page 12: ...elease valve 16 Expansion vessel 17 Air pressure switch A Central Heating Flow C Inlet Gas E Central Heating Return 2 13 GAS AND WATER CIRCUITS FIG 2 14 3 D H W STORAGE CYLINDER The microSYSTEM can be...

Page 13: ...using a 3 port valve installation in conjunction with an unvented cylinder it will be necessary to use a 2 port valve on the cylinder flow connection in addition to the 3 port valve to satisfy Buildin...

Page 14: ...ISTON part number 706329 can be obtained from an ARISTON supplier The kit consits of 1 Electronic module able to plug into the boiler s P C B 2 3 way priority valve with actuator for connection to the...

Page 15: ...f the gas supply for the boiler serves other appliances ensure that an adequate supply is available both to the boiler and the other appliances when they are in use at the same time Pipe work must be...

Page 16: ...s full If the water pressure in the system is below 1 5 bar bring it up to the appropriate level Ensure that the gas cock is closed Make sure that the electrical connection has been made properly and...

Page 17: ...urner If the burner does not light the first time repeat the procedure 5 Check the minimum and maximum pressure values for the gas going to the burner adjust it if needed using the values indicated in...

Page 18: ...2 8 3 80 58 29 20 0 77 2 9 0 91 22 9 80 58 37 25 0 77 2 9 0 90 29 5 TABLE 5 1 Lower Wobbe Index 15 C 1013mbar MJ m3 h Nominal Delivery Pressure mbar Minimum Delivery Pressure mbar 10 RFFI Main Burner...

Page 19: ...ck of the gas safety systems safety device for lack of gas or flame ionisation detection electrode safety device for gas cock 11 Check of the electrical connection make sure it complies with the instr...

Page 20: ...Pressure bar Nominal Pressure Natural Gas G20 mbar LPG G30 G31 mbar Electrical Supply V 5 V Hz Power Consumption W Protection Grade of Electrical System IP Internal Fuse Rating Weight Kg G C Number 6...

Reviews: