43
SETTINGS - ADJUSTMENT - PROBLEM IDENTIFICATION MENUS
menu
sub-menu
Parameter Description
value
default setting
2
7
1
Bleed cycle
press OK button for 5 seconds
see First Ignition parag.
2
8
RESET MENU’ 2
2
8
0
Automatically resetting to the default setting
in menu 2
Reset
OK = yes
ESC = no
To reset all default parameter
settings, press the OK button
4
ZONE 1 PARAMETER
4
0
ZONE 1 TEMPERATURE SETTING
4
0
2
Heating fixed temperature setting
“Heating fixed temp”
from 35 to 82 °C
(high temperature - para. 420
=1)
70
Activated only with temperature
control and fixed temperature
(see 421)
from 20 to 45 °C
(high temperature - para. 420
=0)
20
4
2
ZONE 1 SETTING
4
2
0
Heating appliance temperature value setting 0 = from 20 to 45°C
(low temperature)
1 = from 35 to 85°C
(high temperature)
select in the appliance type
base
4
2
1
Basic heating control type selection type
depending on the peripheral devices
connected
0 = fixed flow temperature
1 = device On/Off
2 = room sensor
3 = external sensor only
4 = room
external sensor
1
To activate heating control,
press the AUTO button. The
display lights up the AUTO
symbol
4
2
2
Slope
from 0_2 to 0_8
(low temperature)
from 1_0 to 3_5
1_5 (high temperature)
Flow T
emperature
Low temperature
High temperature
External temperature
Ambiente temperature
setting value
°C
20
25
15
30
40
50
60
70
80
90
100
°C
10
2.5
3.0
3.5
2.0
1.5
1.2
1.0
0.8
0.6
0.4
0.2
5
0
-5
-10 -15 -20 °C
If the external sensor is used,
the boiler calculates the
most suitable heating flow
temperature taking the external
temperature and the type of
appliance into account.
The type of curve must be
chosen according to the type of
appliance radiator and the heat
losses present in the building.
4
2
3
Parallel shift
from - 7 to + 7 (low temperature)
0
from - 14 to + 14 (high temperature)
To adapt the thermal curve to the appliance requirements, it is possible to perform
a parallel shift of the curve in order to alter the calculated flow temperature and
therefore the ambient temperature.
By accessing this parameter or pressing the buttons 8 the curve can be shifted in a
parallel manner as indicated in the figure shown below.
The value is indicated on the display:
- from -7 to +7 (low temperature)
- from -14 to +14 (high temperature)
Each step represents a flow temperature increase/decrease of 1°C in relation to the
set-point value.
Summary of Contents for 47-116-49