42 - EN
MENU
SUB
-MENU
PAR
AME
TER
DESCRIPTION
RANGE
5
3
1
Set room temperature
5
3
2
Delivery temperature
5
3
3
Return temperature
5
3
4
Z2 heat request status
OFF - ON
5
3
5
Pump status
OFF - ON
5
4
Zone 2 devices
5
4
0
Zone pump modulation
Fixed speed
Modulating on delta T
Modulating on pressure
5
4
1
Target delta T for modulation
4°C - 25°C
5
4
2
Fixed pump speed
20 ÷ 100%
5
5
Cooling
5
5
0
Z2 Cooling T set
par. 5.5.6 - 5.5.7
5
5
1
Z2 Cooling T range
Fan coil (FC)
Underfloor heating (UFH)
5
5
2
Temperature adjustment type selection
ON/OFF thermostats
Fixed delivery temperature
Outdoor sensor only
5
5
3
Temperature adjustment curve
[18;33] FC; [0-30] UFH
5
5
4
Parallel shifting
[-2.5°C; +2.5°C]
5
5
6
Max T
MinT -12°C [FC];
MinT - 23°C [UFH]
5
5
7
Min T
7°C-MaxT [FC]; 18-MaxT [UFH]
5
5
8
Target DeltaT for modulation
[-5; -20°C]
7
ZONE MODULE (if present)
7
1
Manual mode
7
1
0
Manual mode activation
OFF - ON
7
1
1
Z1 pump control
OFF - ON
7
1
2
Z2 pump control
OFF - ON