20
Defrost Valve
model
FDF6A-049-RK (valve) – FDF6A (coil)
coil rating
AC 220-240V 50/60Hz
coil resistance
1273 Ω ± 127Ω at 20°C
Crankcase Heater
power
30 W
resistance
1760 Ω ± 10% at 20°C
Drip Tray Heater
power
75 W
resistance
700 Ω ± 10% at 20°C
Sensors
OCT: Outdoor Coil Temperature. Used for:
-
EEV management
-
Fan management
-
Protection against overheating of the heat exchanger (cooling or dry mode)
-
Defrost cycle management (heating mode)
OAT: Outdoor Air Temperature. Used for:
-
EEV management
-
Fan management
-
Defrost cycle management
-
Crankcase heater management
-
Base heater management
CDT: Compressor Discharge Temperature. Used for:
-
EEV management
-
Protection against overheating of the compressor
-
Crankcase heater management
WTT: Wide Tube Temperature. Used for:
-
EEV management
NTT: Narrow Tube Temperature. Used for:
-
EEV management
Summary of Contents for AEI1G 42 EMX
Page 27: ...27 13 Component replacement FRONT RIGHT LEFT AND REAR PANEL ...
Page 28: ...28 ...
Page 29: ...29 CONTROL AND EXPANSION BOARD remove the right the left the front and the rear panel ...
Page 30: ...30 ...
Page 31: ...31 ...
Page 32: ...32 COMPRESSOR remove the right the left the front and the rear panel ...
Page 33: ...33 EXPANSION VALVE remove the right the left the front and the rear panel ...
Page 34: ...34 FAN MOTOR remove the right the left the front and the rear panel ...
Page 36: ...36 15 Labels Energy labels AEI1G 42 EMX ...
Page 37: ...37 AEI1G 50 EMX Energy labels ...
Page 38: ...38 Rating labels ...
Page 39: ... ARGOCLIMA SPA Via Alfeno Varo 35 Alfianello BS Italy ...