![Argo AEI1G 42 EMX Technical Data & Service Manual Download Page 13](http://html.mh-extra.com/html/argo/aei1g-42-emx/aei1g-42-emx_technical-data-and-service-manual_2967447013.webp)
13
Auto mode
When an indoor unit is in auto mode (auto cooling or auto heating), the actual mode will switch between
heating and cooling mode to maintain the room air temperature (RAT) to the set point temperature
(SPT).
The unit will switch between heating and cooling mode if one of the following conditions is met:
-
Cooling Heating if at least 3 minutes have passed since the unit was stopped and
∆
T ≤ -3
-
Cooling Heating if at least 1 hour have passed since the unit was stopped and
∆
T ≤ -1
-
Heating Cooling if at least 3 minutes have passed since the unit was stopped and
∆
T ≥ 3
-
Heating Cooling if at least 1 hour have passed since the unit was stopped and
∆
T ≥ 1
where:
-
∆
T = RAT – SPT
Fan mode
When an indoor unit is in fan mode:
-
Thermal load of the indoor unit is 0 (no heating or cooling capacity demand to the outdoor unit).
-
The system operates for the other indoor units.
-
If the system is in cooling mode or it is stopped, the indoor fan runs at the selected speed.
-
If the system is in heating mode, the indoor fan stops to avoid overheating of the room.
Summary of Contents for AEI1G 42 EMX
Page 27: ...27 13 Component replacement FRONT RIGHT LEFT AND REAR PANEL ...
Page 28: ...28 ...
Page 29: ...29 CONTROL AND EXPANSION BOARD remove the right the left the front and the rear panel ...
Page 30: ...30 ...
Page 31: ...31 ...
Page 32: ...32 COMPRESSOR remove the right the left the front and the rear panel ...
Page 33: ...33 EXPANSION VALVE remove the right the left the front and the rear panel ...
Page 34: ...34 FAN MOTOR remove the right the left the front and the rear panel ...
Page 36: ...36 15 Labels Energy labels AEI1G 42 EMX ...
Page 37: ...37 AEI1G 50 EMX Energy labels ...
Page 38: ...38 Rating labels ...
Page 39: ... ARGOCLIMA SPA Via Alfeno Varo 35 Alfianello BS Italy ...