4
4
- 12
No
No
Yes
Yes
Check the outdoor unit
control PCB.
Replace if PCB has failed.
Sensor trouble
(5) [Alarms “F04,” “F06,” “F07,” “F08,” “F12”]
Are connectors
CN020, 021, 022, 023,
and 024 (TD, TO, C1, C2, and
TS sensors) connected
correctly to the outdoor unit
control PCB?
Correct the connector
connections.
Are the TD, TO, C1,
C2, and TS sensor resistance*
characteristics OK?
Replace the TD, TO, C1,
C2, or TS sensor.
* Refer to “4. Table of Thermistor Characteristics.”
04-309 Sanyo-4 10/27/04 1:48 PM Page 12
Summary of Contents for ACS100PH
Page 95: ...3 3 2 3 1 Indoor Units Wall Mounted Type AWS36PH Electric Wiring Diagram ...
Page 96: ...3 3 3 3 1 Indoor Units Wall Mounted Type AWS36PH Schematic Diagram ...
Page 97: ...3 3 4 3 1 Indoor Units Wall Mounted Type AWS71PH Electric Wiring Diagram ...
Page 98: ...3 3 5 3 1 Indoor Units Wall Mounted Type AWS71PH Schematic Diagram ...
Page 99: ...3 3 6 3 2 Outdoor Units Electric Wiring Diagram AES71PIC ...
Page 100: ...3 3 7 3 2 Outdoor Units Schematic Diagram AES71PIC ...
Page 101: ...3 3 8 3 2 Outdoor Units Electric Wiring Diagram AES71PIH ...
Page 102: ...3 3 9 3 2 Outdoor Units Schematic Diagram AES71PIH ...
Page 103: ...3 3 10 3 2 Outdoor Units Electric Wiring Diagram AES100PIC ...
Page 104: ...3 3 11 3 2 Outdoor Units Schematic Diagram AES100PIC ...
Page 105: ...3 3 12 3 2 Outdoor Units Electric Wiring Diagram AES100PIH ...
Page 106: ...3 3 13 3 2 Outdoor Units Schematic Diagram AES100PIH ...
Page 107: ...3 3 14 3 2 Outdoor Units Electric Wiring Diagram AES125PIC ...
Page 108: ...3 3 15 3 2 Outdoor Units Schematic Diagram AES125PIC ...
Page 109: ...3 3 16 3 2 Outdoor Units Electric Wiring Diagram AES125PIH ...
Page 110: ...3 3 17 3 2 Outdoor Units Schematic Diagram AES125PIH ...