4-3. Symptoms and Parts to Inspect
Judgment condition
Clear condition
P03
P05
P15
P19
P20
P22
P26
Remote
controller
alarm display
Alarm
contents
Judgment and
correction
Abnormal discharge
temperature
• Discharge temp.
detected at or
above the specified
value.
Stops when temp. exceeds
111
°
C.
Recovery at restart
Recovery at restart
Recovery at restart
Recovery at restart
Recovery at restart
Recovery at restart
Recovery at restart
1. Check refrigerant cycle
(gas leak).
2. Electronic control valve
trouble
3. Check tubing sensor (TD).
Missing phase
detected. (CT
disconnected or AC
power trouble)
Current value sent from MDC
on outdoor unit control PCB is
low.
No AC power input for 3
minutes or longer: pre-trip - 5
1. Check R/S/T power.
2. Check inverter control PCB.
3. Check outdoor unit control
PCB.
Insufficient gas level
detected.
The following conditions
continue for 1 minute.
• Discharge temp. is 95
°
C or
higher.
• Electronic control valve is at
step 480.
• Current value from MDC is
1.7 A (3-phase) or 1.0 A
(1-phase) or less.
Check refrigerant cycle
(gas leak).
4-way valve locked
• Judgment occurs
after compressor
has been ON for 5
minutes.
Indoor heat exchanger temp.
drops although compressors
are ON in heating mode:
[min(E1, E2)]
≤
10
°
C.
Indoor heat exchanger temp.
rises although compressors are
ON in cooling mode:
E2
≥
40
°
C
1. Check 4-way valve.
2. Check 4-way valve wiring.
3. Check outdoor unit control
PCB.
High-pressure
protection trouble
detected from
cooling high-load C2
temp.
Temp. exceeds 64
°
C and
subsequently does not drop to
55
°
C or below.
• Continuously for 30 seconds
→
Alarm is output when this
occurs once.
• Continuously for less than 30
seconds
→
Inverter stops.
1. Refrigerant cycle
overload operation
2. Outdoor coil temperature
sensor C2
Outdoor unit fan
motor trouble
• Inverter protection
circuit was
activated, or lock
was detected, at
outdoor unit fan
motor.
Inverter stops after alarm is
detected
1. Position detection trouble
2. Overcurrent protection
circuit at outdoor unit fan
motor was activated.
• Check outdoor unit control
PCB.
• Refer to outdoor unit fan
judgment methods.
Inverter protection
circuit was
activated, or G-Tr
short-circuit (short
time: 0.8 s or less)
in inverter control
Inverter stops after alarm is
detected. Alarm is output
when inverter stops (pre-trip)
consecutively 4 times.
1. Stops immediately when
restarted.
• Layer short in the
compressor
2. Check inverter control
PCB.
• Wiring trouble
04-309 Sanyo-4 10/27/04 1:48 PM Page 5
Summary of Contents for ACS100PH
Page 95: ...3 3 2 3 1 Indoor Units Wall Mounted Type AWS36PH Electric Wiring Diagram ...
Page 96: ...3 3 3 3 1 Indoor Units Wall Mounted Type AWS36PH Schematic Diagram ...
Page 97: ...3 3 4 3 1 Indoor Units Wall Mounted Type AWS71PH Electric Wiring Diagram ...
Page 98: ...3 3 5 3 1 Indoor Units Wall Mounted Type AWS71PH Schematic Diagram ...
Page 99: ...3 3 6 3 2 Outdoor Units Electric Wiring Diagram AES71PIC ...
Page 100: ...3 3 7 3 2 Outdoor Units Schematic Diagram AES71PIC ...
Page 101: ...3 3 8 3 2 Outdoor Units Electric Wiring Diagram AES71PIH ...
Page 102: ...3 3 9 3 2 Outdoor Units Schematic Diagram AES71PIH ...
Page 103: ...3 3 10 3 2 Outdoor Units Electric Wiring Diagram AES100PIC ...
Page 104: ...3 3 11 3 2 Outdoor Units Schematic Diagram AES100PIC ...
Page 105: ...3 3 12 3 2 Outdoor Units Electric Wiring Diagram AES100PIH ...
Page 106: ...3 3 13 3 2 Outdoor Units Schematic Diagram AES100PIH ...
Page 107: ...3 3 14 3 2 Outdoor Units Electric Wiring Diagram AES125PIC ...
Page 108: ...3 3 15 3 2 Outdoor Units Schematic Diagram AES125PIC ...
Page 109: ...3 3 16 3 2 Outdoor Units Electric Wiring Diagram AES125PIH ...
Page 110: ...3 3 17 3 2 Outdoor Units Schematic Diagram AES125PIH ...