p6
Mounting
Unmounting
The TPIs of the nework must be mounted one
after another.
• INSTALLATION IN AREA 2 (IECEx, ATEX)
II3G Ex nA IIC T4 Gc
The product must be installed by qualified staff, competent on the directives
and the regulation applicable to the area 2.
It must be installed in a protecting enveloppe conform with the EN 60079-15.
The operator must ensure an external protection in order to prevent transient
disturbances on the supply of the modules higher than 40% of the nominal
voltage.
The USB cable must be inserted or withdrawn only if the instrument has been
set off tension or if the area is safe.
The converter must be disconnected from its DIN rail footing only if the
rail supply has been set off tension or if the area is safe.
The installation must be done according to the EN 60079-14 : 2014.
• INSTALLATION IN DIVISION 2 (cFMus)
Class I, Div.2, Groups A,B,C,D T4
(GB)
The product must be installed by qualified staff, competent on the directives
and the regulation applicable to the division 2.
It must be installed in an additional protecting enveloppe ensuring a protection
at least of the type IP54.
The USB cable must be inserted or withdrawn only if the instrument has been
set off tension or if the area is safe.
The converter must be disconnected from its DIN rail footing only if the
rail supply has been set off tension or if the area is safe.
The installation must be done according to the Canadian Electrical Code Part
1 (for Canada) and the National Electrical Code / NFPA 70 (for the USA).
(FR)
Le produit doit être installé par un personnel qualifié et compétent sur les
directives et la législation applicables à la division 2.
Il doit être installé dans une enveloppe protectrice additionnelle assurant une
protection au minimum de type IP54.
Le câble USB ne doit être inséré ou retiré que si l’appareil a été mis hors ten-
sion ou si la zone est sûre.
Le convertisseur ne doit être déconnecté de son embase rail DIN que
si l’alimentation du rail a été mise hors tension ou si la zone est sûre.
L’installation doit être réalisée selon le Canadian Electrical Code Partie 1 (pour
le Canada) et le National Electrical Code / NFPA 70 (pour les USA).