46
5f. Default settings
Label
Name
Range
Set point
Pr 1/2
Set
Set point
LS-US
-62
---
Hy
Differential
0,1-25,5°C/1-225°F
1
Pr1
LS
Minimum set point
(-100°C – SET) (-148°F – SET)
-63
Pr2
US
Maximum set point
(SET – 150,0°C) (SET - 302°F)
-30
Pr2
Ot
Thermostat probe calibration
-12 - 12°C/-120 - 120°F
0
Pr1
Ods
Outputs delay at start up
0 – 255min
0
Pr2
AC
Anti-short cycle delay
0 – 50min
5
Pr1
CCt
Continuous cycle duration
0,0 – 24,0h
0,0
Pr2
CCs
Set point continuous cycle
(-100 – 150,0°C) (-148 - 302°F)
-62
Pr2
COn
Compressor ON time with faulty probe
0 – 255min
60
Pr2
COF
Compressor OFF time with faulty
probe
-255min
5
Pr2
CH
Kind of action
CL=cooling;Ht=heating
CL
Pr2
CF
Temperature measurement unit
°C+°F
°C
Pr2
rES
Resolution
In=integer; dE=dec.point
In
Pr2
dLy
Display temperature delay
0-20,0min (10sec)
0
Pr2
IdF
Interval between defrost cycles
1-120h
0
Pr1
NdF
Maximum length for defrost
0-255min
0
Pr1
dFd
Displaying during defrost
Rt, it, Set, DEF
rt
Pr2
dAd
Max display delay after defrost
0-255min
0
Pr2
ALc
Temperature alarms conf guration
rE=related to set; Ab=absolute
rE
Pr2
ALU
Maximum temperature alarm
Set-110,0°C; Set-230°F
15
Pr1
ALL
Minimum temperature alarm
Set-100,0°C-set; Set-230°F-set
50
Pr1
AFH
Differential for temperature alarm
recovery
(0,1°C-25,5°C) (1°F-45°F)
1
Pr2
ALd
Temperature alarm delay
0-255min
0
Pr2
dAo
Delay of temperature alarm delay
0-23h e 50´
4
Pr2
tbA
Alarm relay disabling
n=no; y=yes
y
Pr2
Aro
Alarm relay activation with power
failure
n(0); y(1)
y
Pr2
ALF
Alarm relay activation for all the
alarms
n(0); y(1)
y
Pr2
bon
Time of buzzer restart after muting, in
case og alarm duration
0 – 30 (min)
30
Pr2
AoP
Alarm relay polarity (0A1=ALr)
oP; cL
cL
Pr2
i1P
Digital input polarity
oP=opening; cL=closing
cL
Pr1
i1F
Digital input conf
guration
EAL, bAL, PAL, dor, dEF, Htr,
AUS
AUS
Pr1
did
Digital input alarm delay
0 – 255min
15
Pr1
nPS
Number of activation of pressure
switch
0-15
15
Pr2
odc
Compress status when open door
No; Fan; CPr, F_C
No
Pr2
rrd
Regulation restart with for open alarm
n – y
y
Pr2
HES
Differential for energy saving
(-30°C - 30°C)(-54°F - 54°F)
1
Pr2
Adr
Serial address
0 – 247
1
Pr2
Pbc
Kind of probe
Ptc; ntc
Pt1
Pr2
onF
On/off key enabling
Nu, oFF, ES
oFF
Pr2
rSE
Real set point value
Actual set
---
Pr2
rEL
Software release
---
1,6
Pr1
PTB
Map code
---
1
Pr2