In the figure A the capillary tube is correctly installed in a dryfilter. In order to ensure effcient
use of the filter, it must be positioned with an inclination of at least 150 and the capillary tube
must be underneath.
In the figure B the capillary tube is too close too the web of the filter. It provides great resistan-
ce and filter blocking after a short time. Or too far away, so it will be filled with flux or solder.
Solder the new filter.
Clean the solder points with a wire brush.
Flush the system with nitrogen.
If only the dryfilter is to be replaced, the system must be pressure tested. See section 3g.