XR30CX
4/5
13.
HOW TO USE THE HOT KEY
13.1
HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1.
Program one controller with the front keypad.
2.
When the controller is ON, insert the “
Hot key
” and push
o
key; the
"uPL"
message
appears followed a by flashing
“End”
3.
Push “
SET”
key and the
End
will stop flashing.
4.
Turn OFF the instrument remove the
“Hot Key”,
then turn it ON again.
NOTE
: the “
Err
” message is displayed for failed programming. In this case push again
o
key
if you want to restart the upload again or remove the “
Hot key
” to abort the operation.
13.2
HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY
(DOWNLOAD)
1.
Turn OFF the instrument.
2.
Insert a
programmed “Hot Key” into the 5 PIN receptacle
and then turn the
Controller ON.
3.
Automatically the parameter list of the
“Hot Key”
is downloaded into the Controller
memory, the “
doL
” message is blinking followed a by flashing
“End”.
4.
After 10 seconds the instrument will restart working with the new parameters.
5.
Remove the
“Hot Key”.
.
NOTE
the message “
Err
” is displayed for failed programming. In this case turn the unit off and
then on if you want to restart the download again or remove the “
Hot key
” to abort the
operation.
14.
ALARM SIGNALS
Mess
age
Cause
Outputs
“P1”
Room probe failure
Compressor output acc. to par. “Con” and “COF”
“P3”
Third probe failure
Outputs unchanged
“P4”
Fourth probe failure
Outputs unchanged
“HA”
Maximum temperature alarm
Outputs unchanged.
“LA” Minimum temperature alarm
Outputs unchanged.
"HA2" Condenser high temperature
It depends on the “Ac2” parameter
"LA2" Condenser low temperature
It depends on the “bLL” parameter
“dA”
Door open
Compressor according to rrd
“EA” External alarm
Output unchanged.
“CA” Serious external alarm (i1F=bAL)
All outputs OFF.
“CA”
Pressure switch alarm (i1F=PAL)
All outputs OFF
“rtc” Real time clock alarm
Alarm output ON; Other outputs unchanged;
Defrosts according to par. “
IdF
” Set real time clock
has to be set
rtF Real
time
clock
board
failure
Alarm output ON; Other outputs unchanged;
Defrosts according to par. “
IdF
” Contact the
service
14.1
ALARM RECOVERY
Probe alarms
P1
”, “
P3
” and “
P4
” start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Check
connections before replacing the probe.
Temperature alarms “
HA
”, “
LA
” “
HA2
” and “
LA2
” automatically stop as soon as the
temperature returns to normal values.
Alarms
“EA”
and
“CA”
(with i1F=bAL) recover as soon as the digital input is disabled.
Alarm “
CA”
(with i1F=PAL) recovers only by
switching off and on
the instrument.
14.2
OTHER MESSAGES
Pon
Keyboard unlocked.
PoF
Keyboard locked
noP
In programming mode
: none parameter is present in Pr1
On the display
or in dP2, dP3, dP4: the selected probe is nor enabled
noA
None alarm is recorded.
15.
TECHNICAL DATA
Housing:
self extinguishing ABS.
Case: XR30CX
frontal 32x74 mm; depth 60mm;
Mounting: XR30CX
panel mounting in a 71x29mm panel cut-out
Protection:
IP20;
Frontal protection: XR30CX
IP65
Connections:
Screw terminal block 2,5 mm
2
wiring.
Power supply:
according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac 10%,
50/60Hz, 110Vac 10%, 50/60Hz
Power absorption:
3VA max
Display
: 3 digits, red LED, 14,2 mm high;
Inputs
: Up to 4 NTC or PTC probes.
Digital input:
free voltage contact
Relay outputs: compressor
SPST 8(3) A, 250Vac; or 20(8)A 250Vac
AUX:
SPDT 8(3) A, 250Vac
Data storing
: on the non-volatile memory (EEPROM).
Internal clock back-up:
24 hours
Kind of action:
1B;
Pollution grade:
2;
Software class:
A.;
Rated impulsive voltage
: 2500V;
Overvoltage Category
: II
Operating temperature:
0÷60 °C;
Storage temperature:
-30÷85 °C.
Relative humidity:
20 85% (no condensing)
Measuring and regulation range: NTC probe:
-40÷110°C (-40÷230°F);
PTC probe:
-50÷150°C (-58÷302°F)
Resolution:
0,1 °C or 1°C or 1 °F (selectable);
Accuracy (ambient temp. 25°C)
: ±0,7 °C
±1 digit
16.
CONNECTIONS
The X-REP output excludes
the TTL output.. It’s present in the following codes:
XR30CX- xx
2
xx, XR30CX –xx
3
xx;
16.1
XR30CX – 20A COMPRESSOR
12Vac/dc supply
: connect to the terminals 7 and 8.
24Vac/dc supply
: connect to the terminals 7 and 8.
120Vac supply
: connect to the terminals 7 and 8.
16.2
XR30CX – 20A COMPRESSOR
N.C.
1 2 3 4 5
6
7
9 10 11 12
Comp
Light/
Alarm
Ro
om
8
Hot Key/IV probe
TTL or X-REP output
8(3)A250V
20(8)A250V
Line
12Vac/dc supply
: connect to the terminals 7 and 8.
24Vac/dc supply
: connect to the terminals 7 and 8.
120Vac supply
: connect to the terminals 7 and 8.
17.
DEFAULT SETTING VALUES
Label Name
Range
°C/°F
Set
rtc
Hy
Differential
0,1 25.5°C/ 1 255°F
2.0 Pr1
LS
Minimum set point
-50°C SET/-58°F SET
-50.0 Pr2
US
Maximum set point
SET 110°C/ SET 230°F
110 Pr2
Ot
Thermostat probe calibration
-12 12°C /-120 120°F
0.0 Pr1
P3P
Third probe presence
n=not present; Y=pres.
n
Pr2
O3
Third probe calibration
-12 12°C /-120 120°F
0 Pr2
P4P
Fourth probe presence
n=not present; Y=pres.
n
Pr2
O4
Fourth probe calibration
-12 12°C /-120 120°F
0 Pr2
OdS
Outputs delay at start up
0÷255 min
0
Pr2
AC
Anti-short cycle delay
0 50 min
1 Pr1
CCt
Continuos cycle duration
0.0÷24.0h
0.0
Pr2
CCS
Set point for continuous cycle
(-55.0÷150,0°C) (-67÷302°F)
3
Pr2
COn
Compressor ON time with faulty
probe
0 255 min
15 Pr2
COF
Compressor OFF time with faulty
probe
0 255 min
30 Pr2
CH
Kind of action
CL=cooling; Ht= heating
cL
Pr1
CF
Temperature measurement unit
°C °F
°C
Pr2
rES
Resolution
in=integer; dE= dec.point
dE
Pr1
dLy
Display temperature delay
0 ÷ 20.0 min (10 sec.)
0
Pr2
IdF
Interval between defrost cycles
1 120 ore
8 Pr1
MdF
(Maximum) length for defrost
0 255 min
20 Pr1
dFd
Displaying during defrost
rt, it, SEt, DEF
it Pr2
dAd
MAX display delay after defrost
0 ÷ 255 min
30
Pr2
ALc
Temperat. alarms configuration
rE= related to set;
Ab = absolute
Ab Pr2
ALU
MAXIMUM temperature alarm
Set 110.0°C; Set÷230°F
110 Pr1
ALL
Minimum temperature alarm
-50.0°C Set/ -58°F Set
-50.0 Pr1
AFH
Differential for temperat. alarm
recovery
(0,1°C÷25,5°C) (1°F÷45°F)
1 Pr2
ALd
Temperature alarm delay
0 255 min
15 Pr2
dAo
Delay of temperature alarm at start
up
0 23h e 50’
1.3 Pr2
AP2
Probe for temperat. alarm of
condenser
nP; P1; P2; P3; P4
P4 Pr2
AL2
Condenser for low temperat. alarm (-55 ÷ 150°C) (-67÷ 302°F)
-40
Pr2
AU2
Condenser for high temperat. alarm (-55 ÷ 150°C) (-67÷ 302°F)
110
Pr2
Set point
Real time clock menu
LS-US
3,0
-
-
Pr1
---
Summary of Contents for SF SERIES
Page 1: ...Service Manual SF MODELS...
Page 2: ...o SF 150 500 i i 2 HC HC 5b 5c 5d 5e 5f...
Page 30: ...30 5c Compressor data SF150...
Page 31: ...31...
Page 32: ...32 5c Compressor data SF500...
Page 33: ...33...
Page 47: ...47...