Name
Range
Step
Default
Description
Reference display (AVR/FCR)
0: Per unit
1: V and A
2: kV and A
-
0: Per
unit
Defines the unit in which the AVR and FCR
reference values are presented.
AVR reference atm.
–500.00…50
000.00
0.01
–50.00
Displays the reference value of the AVR control
mode at the moment.
AVR measured atm.
–500.00…50
000.00
0.01
–50.00
Dislays the measured value of the AVR control
mode at the moment.
FCR reference atm.
–500.00…50
000.00
0.01
–50.00
Displays the reference value of the FCR control
mode at the moment.
FCR measured atm.
–500.00…50
000.00
0.01
–50.00
Dislays the measured value of the FCR control
mode at the moment.
Reference display (MVar/PF)
0: Per unit
1: MVar
2: kVar
-
0: Per
unit
Defines the unit in which the MVar and PF
reference values are presented.
MVar reference atm.
–500.00…50
000.00
0.01
–50.00
Displays the reference value of the MVar control
mode at the moment.
MVar measured atm.
–500.00…50
000.00
0.01
–50.00
Dislays the measured value of the MVar control
mode at the moment.
PF reference atm.
–500.000…50
000.000
0.001
–50.00
Displays the reference value of the PF control
mode at the moment.
PF measured atm.
–500.000…50
000.000
0.001
–50.00
Dislays the measured value of the PF control
mode at the moment.
6.2.5 Events recorded by the Generator commander
Table. 6.2.5 - 384. Excitation events.
Event block
name
Event
code
Event name
Description
Control
EventMaskLo
GMAG
0
FCL on limit
ON
The delayed excitation field current limiter is
running.
GMAG
1
FCL on limit
OFF
The delayed excitation field current limiter is not
running.
GMAG
2
UEL in
operation ON
The underexcitation limiter is running.
GMAG
3
UEL in
operation OFF
The underexcitation limiter is not running.
GMAG
4
SCL
overexcitation
ON
The stator current limiter is running
(overexcited).
GMAG
5
SCL
overexcitation
OFF
The stator current limiter is not running
(overexcited).
GMAG
6
SCL
underexcitation
ON
The stator current limiter is running
(underexcited).
GMAG
7
SCL
underexcitation
OFF
The stator current limiter is not running
(underexcited).
GMAG
8
High IP ON
High active current (used in the SCL) is ON.
GMAG
9
High IP OFF
High active current (used in the SCL) is OFF.
Genera
Generattor Commander
or Commander
Instruction manual