Instruction manual –AQ F210 Feeder Protection IED
227 (292
)
Set the CBW stage as follows:
Parameter
Value
Current 1 (Inom)
0.80 kA
Operation 1 (Inom)
30000 Op
Current 2 (Imax)
16.00 kA
Operations 2 (Imax)
100 Op
Enable Alarm 1
1: Enabled
Alarm 1 Set
1000
operations
Enable Alarm 2
1: Enabled
Alarm 2 Set
100 operations
With these settings Alarm 1 will be issued when any of the three phases cumulative
interruptions counter is below the set 1000 operations left and similarly when any of the
counters is below the set 100 operations left Alarm 2 will be issued.