background image

834719A2.CDR

g

GE Industrial Systems

C60 Breaker Protection System

UR Series Instruction Manual

C60 Revision: 5.7x

Manual P/N: 1601-0100-

U1

 (GEK-113516)

Copyright © 2009 GE Multilin

GE Multilin

215 Anderson Avenue, Markham, Ontario

Canada L6E 1B3

Tel: (905) 294-6222 Fax: (905) 201-2098

Internet

http://www.GEmultilin.com

Title Page

IISO9001:2000

G

E MULTILI

N

RE

GISTERED

GE Multilin's Quality Management 

System is registered to 

ISO9001:2000

QMI # 005094

UL # A3775

*1601-0100-U1*

LISTED

52TL

IND.CONT. EQ.

E83849

Summary of Contents for C60 UR series

Page 1: ...6 Copyright 2009 GE Multilin GE Multilin 215 Anderson Avenue Markham Ontario Canada L6E 1B3 Tel 905 294 6222 Fax 905 201 2098 Internet http www GEmultilin com Title Page IISO9001 2000 G E M ULTILI N R...

Page 2: ......

Page 3: ...DSP module label colors are the same In the event that there is a mismatch between the CPU and CT VT module the relay will not function and a DSP ERROR or HARDWARE MISMATCH error will be displayed All...

Page 4: ......

Page 5: ...5 4 RELAY ACTIVATION 1 17 1 5 5 RELAY PASSWORDS 1 18 1 5 6 FLEXLOGIC CUSTOMIZATION 1 18 1 5 7 COMMISSIONING 1 19 2 PRODUCT DESCRIPTION 2 1 INTRODUCTION 2 1 1 OVERVIEW 2 1 2 1 2 ORDERING 2 2 2 1 3 REP...

Page 6: ...ENERVISTA UR SETUP INTERFACE 4 1 1 INTRODUCTION 4 1 4 1 2 CREATING A SITE LIST 4 1 4 1 3 ENERVISTA UR SETUP OVERVIEW 4 1 4 1 4 ENERVISTA UR SETUP MAIN WINDOW 4 3 4 2 EXTENDED ENERVISTA UR SETUP FEATUR...

Page 7: ...9 5 6 3 BREAKER FAILURE 5 110 5 6 4 PHASE CURRENT 5 119 5 6 5 NEUTRAL CURRENT 5 129 5 6 6 GROUND CURRENT 5 132 5 6 7 VOLTAGE ELEMENTS 5 135 5 6 8 SENSITIVE DIRECTIONAL POWER 5 141 5 7 CONTROL ELEMENTS...

Page 8: ...OL STATUS 6 8 6 2 18 TELEPROTECTION CHANNEL TESTS 6 9 6 2 19 ETHERNET SWITCH 6 9 6 3 METERING 6 3 1 METERING CONVENTIONS 6 11 6 3 2 SOURCES 6 14 6 3 3 SYNCHROCHECK 6 19 6 3 4 TRACKING FREQUENCY 6 19 6...

Page 9: ...TRODUCTION B 1 B 1 2 PHYSICAL LAYER B 1 B 1 3 DATA LINK LAYER B 1 B 1 4 CRC 16 ALGORITHM B 2 B 2 MODBUS FUNCTION CODES B 2 1 SUPPORTED FUNCTION CODES B 3 B 2 2 READ ACTUAL VALUES OR SETTINGS FUNCTION...

Page 10: ...NGS C 12 C 5 3 ABOUT ICD FILES C 13 C 5 4 CREATING AN ICD FILE WITH ENERVISTA UR SETUP C 17 C 5 5 ABOUT SCD FILES C 17 C 5 6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP C 20 C 6 ACSI CONFORMANCE C 6...

Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...

Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...

Page 13: ...lin include the serial number located on the rear nameplate For product information instruction manual updates and the latest software updates please visit the GE Multilin web site at http www GEmulti...

Page 14: ...abling and auxiliary equipment installed in stations can be even further reduced to 20 to 70 of the levels common in 1990 to achieve large cost reductions This requires placing even more functions wit...

Page 15: ...device Virtual outputs can also serve as virtual inputs to FlexLogic equations The analog inputs and outputs are signals that are associated with transducers such as Resistance Temperature Detec tors...

Page 16: ...tering input output control hmi communications or any functional entity in the system Employing OOD OOP in the software architecture of the C60 achieves the same features as the hardware architecture...

Page 17: ...ed 200 MB of available space on system drive and 200 MB of available space on installation drive Video capable of displaying 800 x 600 or higher in high color mode 16 bit color RS232 and or Ethernet p...

Page 18: ...ftware items for the C60 6 EnerVista Launchpad will obtain the software from the Web or CD and automatically start the installation program 7 Select the complete path including the new directory name...

Page 19: ...he back of the device The faceplate RS232 port is intended for local use and is not described in this section see the Using the Quick Connect Feature section for details on configuring the RS232 port...

Page 20: ...ERNET COMMUNICATIONS Before starting verify that the Ethernet network cable is properly connected to the Ethernet port on the back of the relay To setup the relay for Ethernet communications it will b...

Page 21: ...entered in the previous steps correspond to the relay setting values 12 Click OK when the relay order code has been received The new device will be added to the Site List window or Online window locat...

Page 22: ...cess the C60 from a laptop through Ethernet first assign an IP address to the relay from the front panel keyboard 1 Press the MENU key until the SETTINGS menu is displayed 2 Navigate to the SETTINGS P...

Page 23: ...sktop right click the My Network Places icon and select Properties to open the network con nections window 2 Right click the Local Area Connection icon and select Properties 3 Select the Internet Prot...

Page 24: ...guration If the following sequence of messages appears when entering the C WINNT ping 1 1 1 1 command Pinging 1 1 1 1 with 32 bytes of data Request timed out Request timed out Request timed out Reques...

Page 25: ...on specific DNS suffix IP Address 1 1 1 2 Subnet Mask 255 0 0 0 Default Gateway C WINNT It may be necessary to restart the laptop for the change in IP address to take effect Windows 98 or NT Before us...

Page 26: ...indows desktop right click the My Network Places icon and select Properties to open the network con nections window 2 Right click the Local Area Connection icon and select the Properties item 3 Select...

Page 27: ...d printed or changed according to user specifications Refer to chapter 4 in this manual and the EnerVista UR Setup Help File for more information about the using the EnerVista UR Setup software interf...

Page 28: ...he GE Multilin RS232 RS485 converter box is required This device catalog number F485 connects to the computer using a straight through serial cable A shielded twisted pair 20 22 or 24 AWG connects the...

Page 29: ...d 1 5 3 MENU HIERARCHY The setting and actual value messages are arranged hierarchically The header display pages are indicated by double scroll bar characters while sub header pages are indicated by...

Page 30: ...are two user password security access levels COMMAND and SETTING 1 COMMAND The COMMAND access level restricts the user from making any settings changes but allows the user to perform the fol lowing op...

Page 31: ...nd LED indications 3 LED test 4 Visual inspection for any damage corrosion dust or loose wires 5 Event recorder file download with further events analysis Out of service maintenance 1 Check wiring con...

Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...

Page 33: ...variety of communications modules are available Two rear RS485 ports allow independent access by operating and engineering staff All serial ports use the Modbus RTU protocol The RS485 ports may be con...

Page 34: ...odules or the HardFiber modules The order code options are described in the following sub sections Table 2 2 OTHER DEVICE FUNCTIONS FUNCTION FUNCTION FUNCTION Breaker Arcing Current I2 t Event Recorde...

Page 35: ...l current and 2 Form C outputs 8 digital inputs 6B 6B 6B 6B 6B 2 Form A voltage with optional current and 4 Form C outputs 4 digital inputs 6C 6C 6C 6C 6C 8 Form C outputs 6D 6D 6D 6D 6D 16 digital in...

Page 36: ...C 6C 6C 8 Form C outputs 6D 6D 6D 16 digital inputs 6E 6E 6E 4 Form C outputs 8 digital inputs 6F 6F 6F 8 Fast Form C outputs 6G 6G 6G 4 Form A voltage with optional current outputs 8 digital inputs 6...

Page 37: ...nishing 4L 4L 14 Form A no monitoring Latching outputs 67 67 8 Form A no monitoring outputs 6A 6A 2 Form A voltage with optional current and 2 Form C outputs 8 digital inputs 6B 6B 2 Form A voltage wi...

Page 38: ...outputs 4D 16 digital inputs with Auto Burnishing 4L 14 Form A no monitoring Latching outputs 67 8 Form A no monitoring outputs 6A 2 Form A voltage with optional current and 2 Form C outputs 8 digita...

Page 39: ...s 6E 4 Form C outputs 8 digital inputs 6F 8 Fast Form C outputs 6G 4 Form A voltage with optional current outputs 8 digital inputs 6H 6 Form A voltage with optional current outputs 4 digital inputs 6K...

Page 40: ...inputs 6K 4 Form C and 4 Fast Form C outputs 6L 2 Form A current with optional voltage and 2 Form C outputs 8 digital inputs 6M 2 Form A current with optional voltage and 4 Form C outputs 4 digital in...

Page 41: ...cteristic angle 0 to 359 in steps of 1 Calibration angle 0 00 to 0 95 in steps of 0 05 Minimum power 1 200 to 1 200 pu in steps of 0 001 Pickup level accuracy 1 or 0 001 pu whichever is greater Hyster...

Page 42: ...to 4 reclose attempts before lockout Selectable reclosing mode and breaker sequence TRIP BUS TRIP WITHOUT FLEXLOGIC Number of elements 6 Number of inputs 16 Operate time 2 ms at 60 Hz Time accuracy 3...

Page 43: ...from non volatile memory or syn chronize to a 3 bit control input or synch restore mode 2 2 3 MONITORING OSCILLOGRAPHY Maximum records 64 Sampling rate 64 samples per power cycle Triggers any element...

Page 44: ...0 2 VA at rated secondary Conversion range Standard CT 0 02 to 46 CT rating RMS symmetrical Sensitive Ground CT module 0 002 to 4 6 CT rating RMS symmetrical Current withstand 20 ms at 250 times rated...

Page 45: ...on No Data rate 64 or 128 kbps CRC 32 bit 2 2 6 POWER SUPPLY LOW RANGE Nominal DC voltage 24 to 48 V Minimum DC voltage 20 V Maximum DC voltage 60 V Voltage loss hold up 20 ms duration at nominal NOTE...

Page 46: ...nge 0 75 of full scale for 0 to 20 mA range 99 Settling time to a step change 100 ms Isolation 1 5 kV Driving signal any FlexAnalog quantity Upper and lower limit for the driving signal 90 to 90 pu in...

Page 47: ...al power budget between two type 2T or 2S modules using a single fiber cable is To calculate the maximum fiber length divide the worst case opti cal power budget by the cable attenuation per unit dist...

Page 48: ...s Altitude Up to 2000 m Installation category II Pollution degree 2 INTERFACE TYPE TYPICAL DISTANCE RS422 1200 m G 703 100 m EMITTER FIBER TYPE TRANSMIT POWER RECEIVED SENSITIVITY POWER BUDGET 820 nm...

Page 49: ...l IEC 60255 21 1 Shock and bump IEC 60255 21 2 Seismic IEC 60255 21 3 IEEE C37 98 Cold IEC 60028 2 1 16 h at 40 C Dry heat IEC 60028 2 2 16 h at 85 C The asterisk indicates a non UL rating Type test r...

Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...

Page 51: ...mited rear depth There is also a removable dust cover that fits over the faceplate which must be removed when attempting to access the keypad or RS232 communications port The case dimensions are shown...

Page 52: ...lows the relay to be easily upgraded or repaired by a qualified service person The faceplate is hinged to allow easy access to the removable modules and is itself removable to allow mounting on doors...

Page 53: ...its semi flush with the panel or switchgear door allowing the operator access to the keypad and the RS232 communications port The relay is secured to the panel with the use of four screws supplied wit...

Page 54: ...able online from the GE Multilin website GEK 113180 UR series UR V side mounting front panel assembly instructions GEK 113181 Connecting the side mounted UR V enhanced front panel to a vertical UR ser...

Page 55: ...GE Multilin C60 Breaker Protection System 3 5 3 HARDWARE 3 1 DESCRIPTION 3 Figure 3 6 C60 VERTICAL SIDE MOUNTING INSTALLATION STANDARD PANEL...

Page 56: ...per electrostatic discharge protection for example a static strap must be used when coming in con tact with modules while the relay is energized The relay being modular in design allows for the withdr...

Page 57: ...of the module to ensure that the same or replacement module is inserted into the correct slot Modules with current input provide automatic shorting of external CT circuits To properly insert a module...

Page 58: ...th respect to terminal number assignments which are three characters long assigned in order by module slot position row number and column letter Two slot wide modules take their slot designation from...

Page 59: ...GE Multilin C60 Breaker Protection System 3 9 3 HARDWARE 3 1 DESCRIPTION 3 Figure 3 11 EXAMPLE OF MODULES IN F AND H SLOTS...

Page 60: ...a H8a H5b H7b H8b H5a H7a H6c H8c H5c H7c H1 H2 H3 H4 I V I V I V I V DIGITAL INPUTS OUPUTS 6G P1a P2b P1c P1b P2c P2a P4a P4c P3b P3a P4b P3c CONTACT INPUT P5a CONTACT INPUT P7a CONTACT INPUT P5c CON...

Page 61: ...ontact input connections The power supply module provides 48 V DC power for dry contact input connections and a critical failure relay see the Typical wiring diagram earlier The critical failure relay...

Page 62: ...isolating transformer and an automatic shorting mechanism that shorts the input when the module is withdrawn from the chassis There are no internal ground connections on the current inputs Current tra...

Page 63: ...ound connection to neutral must be on the source side UNSHIELDED CABLE LOAD A B C N G Ground outside CT Source LOAD SHIELDED CABLE 996630A5 A B C Source To ground must be on load side Stress cone shie...

Page 64: ...s is different for the two applications The contact inputs are grouped with a common return The C60 has two versions of grouping four inputs per common return and two inputs per common return When a c...

Page 65: ...subsequently opened when measured as an impedance The solution to this problem is to use the voltage measuring trigger input of the relay test set and connect the form A contact through a voltage drop...

Page 66: ...a 6c 2 Inputs 6 Fast Form C 6a 6c 2 Inputs 6 Form A 7a 7c 2 Inputs 7 Fast Form C 7a 7c 2 Inputs 7a 7c 2 Inputs 8a 8c 2 Inputs 8 Fast Form C 8a 8c 2 Inputs 8a 8c 2 Inputs 6K MODULE 6L MODULE 6M MODULE...

Page 67: ...Solid State 7a 7c 2 Inputs 7a 7c 2 Inputs 7 Form A 7 Not Used 8a 8c 2 Inputs 8a 8c 2 Inputs 8 Form A 8 Solid State 4B MODULE 4C MODULE 4D MODULE 4L MODULE TERMINAL ASSIGNMENT OUTPUT TERMINAL ASSIGNMEN...

Page 68: ...3 18 C60 Breaker Protection System GE Multilin 3 2 WIRING 3 HARDWARE 3 Figure 3 17 CONTACT INPUT AND OUTPUT MODULE WIRING 1 of 2 842762A2 CDR...

Page 69: ...3b 4b 5b 6b 1a 2a 3a 4a 5a 6a 1c 2c 3c 4c 5c 6c 1 5 2 6 3 4 8a 7b 7a CONTACT IN 7a CONTACT IN 7c CONTACT IN 8a CONTACT IN 8c COMMON 7b SURGE 8c 7c 8b I V I V I V I V DIGITAL I O 6N 1b 2b 3b 4b 6c 1a 2...

Page 70: ...s 33 V DC for 48 V sources 84 V DC for 110 to 125 V sources and 166 V DC for 250 V sources Figure 3 19 DRY AND WET CONTACT INPUT CONNECTIONS Wherever a tilde symbol appears substitute with the slot po...

Page 71: ...e of state was sensed Then within 25 to 50 ms this current is slowly reduced to 3 mA as indicated above The 50 to 70 mA peak current burns any film on the con tacts allowing for proper sensing of stat...

Page 72: ...tions These connections are arranged as three ter minals per row with a total of eight rows A given row may be used for either inputs or outputs with terminals in column a having positive polarity and...

Page 73: ...S232 FACEPLATE PORT CONNECTION 3 2 9 CPU COMMUNICATION PORTS a OPTIONS In addition to the faceplate RS232 port the C60 provides two additional communication ports or a managed six port Ether net switc...

Page 74: ...F COMMON D1a D2a D3a D4b D4a BNC BNC IRIG B output IRIG B input CPU 9M Co axial cable Co axial cable Shielded twisted pairs SM fiber optic cable Ground at remote device RS485 COM2 COMMON D1a D2a D3a...

Page 75: ...only Each relay should also be daisy chained to the next one in the link A maximum of 32 relays can be connected in this manner without exceeding driver capability For larger systems additional seria...

Page 76: ...The 10 Mbps rate is available for CPU modules 9G and 9H 100Mbps is available for modules 9H 9J 9K 9L 9M 9N 9P and 9R The 9H 9K 9M and 9R modules have a second pair of identical optical fiber transmitt...

Page 77: ...c locations can also be synchronized Figure 3 26 IRIG B CONNECTION The IRIG B repeater provides an amplified DC shift IRIG B signal to other equipment By using one IRIG B serial connec tion several UR...

Page 78: ...ays can be connected in a single ring Figure 3 28 DIRECT INPUT AND OUTPUT SINGLE CHANNEL CONNECTION The interconnection for dual channel Type 7 communications modules is shown below Two channel module...

Page 79: ...C37 94 820 nm 128 kbps multi mode LED 2 channels 2S Six port managed Ethernet switch with high voltage power supply 2T Six port managed Ethernet switch with low voltage power supply 72 1550 nm single...

Page 80: ...rface attenuators may be necessary to ensure that you do not exceed the maxi mum optical input power to the receiver 7N Channel 1 RS422 channel 2 1300 nm single mode ELED 7P Channel 1 RS422 channel 2...

Page 81: ...urer to another Therefore it is not uncommon to see pin outs numbered TxA TxB RxA and RxB In such cases it can be assumed that A is equivalent to and B is equivalent to b G 703 SELECTION SWITCH PROCED...

Page 82: ...d be disabled off d G 703 TIMING MODES There are two timing modes for the G 703 module internal timing mode and loop timing mode default Internal Timing Mode The system clock is generated internally T...

Page 83: ...MOTE LOOPBACK MODE In dual loopback mode the multiplexers are active and the functions of the circuit are divided into two with each receiver transmitter pair linked together to deconstruct and then r...

Page 84: ...iming ST connections However when used in two channel applications certain criteria must be followed since there is one clock input for the two RS422 channels The system will function cor rectly if th...

Page 85: ...of the Tx clock in the center of the Tx data bit Figure 3 41 CLOCK AND DATA TRANSITIONS d RECEIVE TIMING The RS422 interface utilizes NRZI MARK modulation code and therefore does not rely on an Rx clo...

Page 86: ...maximum optical input power to the receiver Figure 3 42 RS422 AND FIBER INTERFACE CONNECTION Connections shown above are for multiplexers configured as DCE data communications equipment units 3 3 7 G...

Page 87: ...repeated at a frame rate of 8000 Hz with a resultant bit rate of 2048 kbps The specifications for the module are as follows IEEE standard C37 94 for 1 128 kbps optical fiber interface for 2G and 2H m...

Page 88: ...al Before performing this action control power must be removed from the relay The original location of the module should be recorded to help ensure that the same or replacement module is inserted into...

Page 89: ...of 2048 kbps The specifications for the module are as follows Emulated IEEE standard emulates C37 94 for 1 64 kbps optical fiber interface modules set to n 1 or 64 kbps Fiber optic cable type 9 125 m...

Page 90: ...ould be recorded to help ensure that the same or replacement module is inserted into the correct slot 2 Remove the module cover screw 3 Remove the top cover by sliding it towards the rear and then lif...

Page 91: ...XXX self test warning will be issued 3 4 2 MANAGED ETHERNET SWITCH MODULE HARDWARE The type 2S and 2T managed Ethernet switch modules provide two 10 100Base T and four multimode ST 100Base FX external...

Page 92: ...ur net work administrator to determine if the default IP address subnet mask or default gateway needs to be modified Do not connect to network while configuring the switch module a CONFIGURING THE SWI...

Page 93: ...ch module 1 Select the desired device from site tree in the online window 2 Select the Settings Product Setup Communications Ethernet Switch Ethernet Switch Settings File Retreive Settings File item f...

Page 94: ...ware on a switch module Using the EnerVista UR Setup software Serially using the C60 switch module console port Using FTP or TFTP through the C60 switch module console port It is highly recommended to...

Page 95: ...ns Ethernet Switch Firmware Upload menu item The following popup screen will appear warning that the settings will be lost when the firmware is upgraded It is highly recommended that you save the swit...

Page 96: ...he following window will pop up indicating that the firmware file transfer is in progress If the firmware load was successful the following window will appear Note The switch will automatically reboot...

Page 97: ...pts Loss of switch power IP gateway subnet Incompatibility between the CPU and the switch module UR port port 7 configured incorrectly or blocked Switch IP address assigned to another device in the sa...

Page 98: ...3 48 C60 Breaker Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3...

Page 99: ...must first be created See the EnerV ista UR Setup Help File or refer to the Connecting EnerVista UR Setup with the C60 section in Chapter 1 for details 4 1 3 ENERVISTA UR SETUP OVERVIEW a ENGAGING A D...

Page 100: ...h had been removed from the Settings List tree menu it will be added back to the Settings List tree menu Drag and Drop The Site List and Settings List control bar windows are each mutually a drag sour...

Page 101: ...itle bar which shows the pathname of the active data view 2 Main window menu bar 3 Main window tool bar 4 Site list control bar window 5 Settings list control bar window 6 Device data view windows wit...

Page 102: ...plate feature is disabled by default The following procedure describes how to enable the settings tem plate for UR series settings files 1 Select a settings file from the offline window of the EnerVis...

Page 103: ...by clicking on them The setting available to view will be displayed against a yellow background as shown below Figure 4 3 SETTINGS TEMPLATE VIEW TWO SETTINGS SPECIFIED AS EDITABLE 6 Click on Save to s...

Page 104: ...hose settings available for editing Display all settings with settings not available for editing greyed out Use the following procedure to only display settings available for editing 1 Select an insta...

Page 105: ...ied by the template but all settings will be shown The effect of applying the template to the phase time overcurrent settings is shown below Figure 4 6 APPLYING TEMPLATES VIA THE VIEW ALL SETTINGS COM...

Page 106: ...NTRIES The following procedure describes how to lock individual entries of a FlexLogic equation 1 Right click the settings file or online device and select the Template Mode Create Template item to en...

Page 107: ...elow and on the front panel display Figure 4 9 SECURED FLEXLOGIC IN GRAPHICAL VIEW b LOCKING FLEXLOGIC EQUATIONS TO A SERIAL NUMBER A settings file and associated FlexLogic equations can also be locke...

Page 108: ...or mation can be compared with the C60 actual values at any later date to determine if security has been compromised The traceability information is only included in the settings file if a complete se...

Page 109: ...lay configuration since the settings file was saved a SETTINGS FILE TRACEABILITY INFORMATION The serial number and file transfer date are saved in the settings files when they sent to an C60 device Th...

Page 110: ...INFORMATION SERIAL NUMBER ACTUAL VALUES PRODUCT INFO MODEL INFORMATION LAST SETTING CHANGE c ADDITIONAL TRACEABILITY RULES The following additional rules apply for the traceability feature If the use...

Page 111: ...nterface being EnerVista UR Setup software The front panel interface consists of LED panels an RS232 port keypad LCD display control pushbuttons and optional user programmable pushbuttons The faceplat...

Page 112: ...has been cleared these latched conditions can also be reset via the SETTINGS INPUT OUTPUTS RESETTING menu The RS232 port is intended for connection to a portable PC The USER keys are used by the break...

Page 113: ...st of 48 amber LED indicators in four columns The operation of these LEDs is user defined Support for applying a customized label beside every LED is provided Default labels are shipped in the label p...

Page 114: ...ound was involved USER PROGRAMMABLE INDICATORS The second and third provide 48 amber LED indicators whose operation is controlled by the user Support for applying a customized label beside every LED i...

Page 115: ...User programmable LEDs section of chapter 5 The LEDs are fully user programmable The default labels can be replaced by user printed labels for both panels as explained in the following section Figure...

Page 116: ...ert tool from the package and bend the tabs as described in the following procedures These tabs will be used for removal of the default and custom LED labels It is important that the tool be used EXAC...

Page 117: ...cedure describes how to remove the LED labels from the C60 enhanced front panel and insert the custom labels 1 Use the knife to lift the LED label and slide the label tool underneath Make sure the ben...

Page 118: ...pocket until the text is properly aligned with the LEDs as shown below The following procedure describes how to remove the user programmable pushbutton labels from the C60 enhanced front panel and ins...

Page 119: ...TE INTERFACE 4 2 Slide the label tool under the user programmable pushbutton label until the tabs snap out as shown below This will attach the label tool to the user programmable pushbutton label 3 Re...

Page 120: ...file The panel templates provide relative LED locations and located example text x edit boxes The following procedure demonstrates how to install uninstall the custom panel labeling 1 Remove the clear...

Page 121: ...e is broken down further into logical subgroups The MESSAGE keys navigate through the subgroups The VALUE keys scroll increment or decrement numerical setting values when in programming mode These key...

Page 122: ...ER COMMAND PASSWORD This message appears when the USER 1 USER 2 or USER 3 key is pressed and a COMMAND PASSWORD is required i e if COMMAND PASSWORD is enabled and no com mands have been issued within...

Page 123: ...er actual value headers SETTINGS PRODUCT SETUP Press the MENU key until the header for the first page of Settings appears This page contains settings to configure the relay SETTINGS SYSTEM SETUP Press...

Page 124: ...DOWN key displays the previous selection c ENTERING ALPHANUMERIC TEXT Text settings have data values which are fixed in length but user defined in character They may be comprised of upper case letter...

Page 125: ...e appears on the display 2 Press the MESSAGE RIGHT key until the PASSWORD SECURITY message appears on the display 3 Press the MESSAGE DOWN key until the INSTALLATION message appears on the display 4 P...

Page 126: ...7 Type in a numerical password up to 10 characters and press the ENTER key 8 When the VERIFY NEW PASSWORD is displayed re type in the same password and press ENTER 9 When the NEW PASSWORD HAS BEEN STO...

Page 127: ...t to Off after the expiration of the ten minute timeout In the event that an incorrect Command or Setting password has been entered via the any external communications inter face three times within a...

Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...

Page 129: ...K See page 5 37 FAULT REPORTS See page 5 38 OSCILLOGRAPHY See page 5 40 DATA LOGGER See page 5 42 DEMAND See page 5 43 USER PROGRAMMABLE LEDS See page 5 44 USER PROGRAMMABLE SELF TESTS See page 5 48 C...

Page 130: ...TIMERS See page 5 103 FLEXELEMENTS See page 5 104 NON VOLATILE LATCHES See page 5 108 SETTINGS GROUPED ELEMENTS SETTING GROUP 1 See page 5 109 SETTING GROUP 2 SETTING GROUP 6 SETTINGS CONTROL ELEMENT...

Page 131: ...TE OUTPUTS DNA BIT PAIRS See page 5 194 REMOTE OUTPUTS UserSt BIT PAIRS See page 5 195 RESETTING See page 5 195 DIRECT INPUTS See page 5 196 DIRECT OUTPUTS See page 5 196 TELEPROT INPUTS See page 5 20...

Page 132: ...es pu quantity actual quantity base quantity For current elements the base quantity is the nominal secondary or primary current of the CT Where the current source is the sum of two CTs with different...

Page 133: ...ual currents may be required for the circuit relaying and metering functions For a three winding transformer application it may be required to calculate watts and vars for each of three windings using...

Page 134: ...For example in the scheme shown in the above diagram the configures one Source to be the sum of CT1 and CT2 and can name this Source as Wdg 1 Current Once the sources have been configured the user has...

Page 135: ...e set of three channels Upon startup the CPU configures the settings required to characterize the current and voltage inputs and will display them in the appropriate section in the sequence of the ban...

Page 136: ...udes both keypad entry and the through the faceplate RS232 port Remote access is defined as any access to settings or commands via any rear communications port This includes both Ethernet and RS485 co...

Page 137: ...rd codes are required to enable each access level A password consists of 1 to 10 numerical characters When a CHANGE COMMAND PASSWORD or CHANGE SETTING PASSWORD setting is programmed to Yes via the fro...

Page 138: ...Password field 2 Re enter the password in the Confirm New Password field 3 Click the Change button This button will not be active until the new password matches the confirmation password 4 If the orig...

Page 139: ...control power is cycled COMMAND LEVEL ACCESS TIMEOUT This setting specifies the length of inactivity no local or remote access required to return to restricted access from the command password level S...

Page 140: ...this setting is Off then remote setting access is blocked even if the correct remote setting password is pro vided If this setting is any other FlexLogic operand then the operand must be asserted set...

Page 141: ...the magnitudes and angles of the measured currents If the magnitude is below the cut off level it is substi tuted with zero This applies to phase and ground current phasors as well as true RMS values...

Page 142: ...ommands Since the C60 responds to rising edges of the configured FlexLogic operands they must be asserted for at least 50 ms to take effect Clearing records with user programmable operands is not prot...

Page 143: ...TIONS a MAIN MENU PATH SETTINGS PRODUCT SETUP COMMUNICATIONS COMMUNICATIONS SERIAL PORTS See below MESSAGE NETWORK See page 5 16 MESSAGE MODBUS PROTOCOL See page 5 17 MESSAGE DNP PROTOCOL See page 5 1...

Page 144: ...ed network configurations and should normally be left at their default values but may be changed if required for example to allow access to multiple UR series relays behind a router By setting a diffe...

Page 145: ...endix B for more information on the Modbus protocol Changes to the MODBUS TCP PORT NUMBER setting will not take effect until the C60 is restarted e DNP PROTOCOL PATH SETTINGS PRODUCT SETUP COMMUNICATI...

Page 146: ...MESSAGE DNP VOLTAGE DEFAULT DEADBAND 30000 Range 0 to 100000000 in steps of 1 MESSAGE DNP POWER DEFAULT DEADBAND 30000 Range 0 to 100000000 in steps of 1 MESSAGE DNP ENERGY DEFAULT DEADBAND 30000 Rang...

Page 147: ...ing types current voltage power energy power factor and other Each setting represents the scale factor for all analog input points of that type For example if the DNP VOLTAGE SCALE FACTOR setting is s...

Page 148: ...DNP NUMBER OF PAIRED CONTROL POINTS setting allows configuration of from 0 to 32 binary output paired controls Points not configured as paired operate on a one to one basis The DNP ADDRESS setting is...

Page 149: ...block any points assigned after the first Off point are ignored Changes to the DNP IEC 60870 5 104 point lists will not take effect until the C60 is restarted g IEC 61850 PROTOCOL PATH SETTINGS PRODU...

Page 150: ...ICATIONS IEC 61850 GSSE GOOSE TRANSMISSION GENERAL The DEFAULT GSSE GOOSE UPDATE TIME sets the time between GSSE or GOOSE messages when there are no remote out put state changes to be sent When remote...

Page 151: ...e destination Ethernet MAC address was determined automatically by taking the sending MAC address that is the unique local MAC address of the C60 and setting the multicast bit The GOOSE VLAN PRIORITY...

Page 152: ...o be sent at the pre configured rate even if no changes in the data items are detected The GOOSE functionality was enhanced to prevent the relay from flooding a communications network with GOOSE mes s...

Page 153: ...Configure the transmission dataset 2 Configure the GOOSE service settings 3 Configure the data The general steps required for reception configuration are 1 Configure the reception dataset 2 Configure...

Page 154: ...data by making the following changes in the PRODUCT SETUP COMMUNICATION IEC 61850 PROTO COL GGIO1 STATUS CONFIGURATION settings menu Set GGIO1 INDICATION 1 to a FlexLogic operand used to provide the...

Page 155: ...and contains the configurable GOOSE dataset items for reception PATH RECEPTION CONFIGURABLE GOOSE 1 8 CONIFIG GSE 1 64 DATA ITEMS The configurable GOOSE settings allow the C60 to be configured to rece...

Page 156: ...then server scanning can be disabled to increase CPU resources When server scanning is disabled there will be not updated to the IEC 61850 logical node sta tus values in the C60 Clients will still be...

Page 157: ...e and apparent 46 phase CT primary setting 275 VT ratio setting frequency 90 Hz power factor 2 The GGIO1 status configuration points are shown below PATH SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 6185...

Page 158: ...IN 1 MIN This setting specifies the minimum value for each analog value Refer to IEC 61850 7 1 and 61850 7 3 for details This minimum value is used to determine the deadband The deadband is used in t...

Page 159: ...ects the FlexInteger value to drive each GGIO5 integer status value GGIO5 ST UIntIn1 This setting is stored as an 32 bit unsigned integer value The report control configuration settings are shown belo...

Page 160: ...onnect switches operate by opening and closing the XSWI operating counter status attribute OpCnt increments with every operation Frequent switch operation may result in very large OpCnt values over ti...

Page 161: ...software is available from various sources including Microsoft Windows NT The dir txt file obtained from the C60 contains a list and description of all available files event records oscillography etc...

Page 162: ...er to provide an accurate time Both unicast and broadcast SNTP are supported If SNTP functionality is enabled at the same time as IRIG B the IRIG B signal provides the time value to the C60 clock for...

Page 163: ...H SETTINGS PRODUCT SETUP COMMUNICATIONS EGD PROTOCOL SLOW PROD EXCH 1 2 CONFIGURATION Slow EGD exchanges 500 to 1000 ms are generally used for the transfer and display of data items The settings for t...

Page 164: ...port number for the Ethernet switch module are specified in this menu These settings are used in advanced network configurations Please consult the network administrator before making changes to these...

Page 165: ...time DST settings can be used to allow the C60 clock can follow the DST rules of the local time zone Note that when IRIG B time synchronization is active the DST settings are ignored The DST settings...

Page 166: ...aiting for the fault report trigger If trigger does not occur within this time the values are cleared to prepare for the next disturbance Fault current and voltage phasors one cycle after the trigger...

Page 167: ...1 SOURCE setting selects the source for input currents and voltages and disturbance detection The FAULT 1 REPORT TRIG setting assigns the FlexLogic operand representing the protection element elements...

Page 168: ...for example 10 50 75 etc A trigger position of 25 consists of 25 pre and 75 post trigger data The TRIGGER SOURCE is always captured in oscillography and may be any FlexLogic parameter element state co...

Page 169: ...lue parameters is presented in Appendix A FlexAnalog parameters The parameter index number shown in any of the tables is used to expedite the selection of the parameter on the relay display It can be...

Page 170: ...which the data logger will operate When set to Continu ous the data logger will actively record any configured channels at the rate as defined by the DATA LOGGER RATE The DATA LOGGER DATA LOGGER MODE...

Page 171: ...an through the list of parameters via the relay keypad display entering this number via the relay keypad will cause the corresponding parameter to be displayed DATA LOGGER CONFIG This display presents...

Page 172: ...ch new value of demand becomes available at the end of each pulse Assign a FlexLogic operand to the DEMAND TRIGGER setting to program the input for the new demand interval pulses If no trigger is assi...

Page 173: ...top left panel moving from top to bottom of each column of the LEDs This test checks for hardware failures that lead to more than one LED being turned off from a single logic point This stage can be i...

Page 174: ...art stage 2 At this point forward test may be aborted by pressing the pushbutton Application Example 2 Assume one needs to check if any LEDs are burned as well as exercise one LED at a time to check f...

Page 175: ...ammable LED settings select the FlexLogic operands that control the LEDs If the LED 1 TYPE setting is Self Reset the default setting the LED illumination will track the state of the selected LED opera...

Page 176: ...enable the Ethernet switch failure function ensure that the ETHERNET SWITCH FAIL FUNCTION is Enabled in this menu USER PROGRAMMABLE SELF TESTS DIRECT RING BREAK FUNCTION Enabled Range Disabled Enabled...

Page 177: ...and are not protected by the control password However by supervising their output operands the user can dynamically enable or disable control pushbuttons for security reasons Each control pushbutton a...

Page 178: ...breaker control typically uses the larger optional user programmable pushbuttons making the control pushbuttons available for other user applications Figure 5 7 CONTROL PUSHBUTTON LOGIC 842010A2 CDR C...

Page 179: ...user programmable pushbuttons are under the control level of password protection The user configurable pushbuttons for the enhanced faceplate are shown below USER PUSHBUTTON 1 PUSHBUTTON 1 FUNCTION D...

Page 180: ...olatile memory and maintained through a loss of control power The pushbutton is reset deactivated in latched mode by asserting the operand assigned to the PUSHBTN 1 RESET set ting or by directly press...

Page 181: ...mory Should the power supply be lost the correct state of the pushbutton is retained upon subsequent power up of the relay PUSHBTN 1 ID TEXT This setting specifies the top 20 character line of the use...

Page 182: ...o the PUSHBTN 1 OFF TEXT setting This message can be temporary removed if any front panel keypad button is pressed However ten seconds of keypad inactivity will restore the message if the PUSHBUTTON 1...

Page 183: ...k SETTING Off 0 Local Lock SETTING Off 0 Set SETTING Off 0 Reset SETTING Enabled Disabled Autoreset Function FLEXLOGIC OPERAND PUSHBUTTON 1 ON FLEXLOGIC OPERAND PUSHBUTTON 1 OFF TIMER 200 ms 0 AND AND...

Page 184: ...gic operand MESSAGE PARAMETER 256 Off Range FlexLogic operand Pushbutton 1 LED Instantaneous reset OR 1 If pushbutton 1 LED control is set to off 2 If pushbutton 1 LED control is not set to off PUSHBU...

Page 185: ...e PRODUCT SETUP DISPLAY PROPER TIES DEFAULT MESSAGE TIMEOUT setting USER PROGRAMMABLE CONTROL INPUT The user definable displays also respond to the INVOKE AND SCROLL setting Any FlexLogic operand in p...

Page 186: ...through the characters A space is selected like a character 4 Press the decimal key to advance the cursor to the next position 5 Repeat step 3 and continue entering characters until the desired text i...

Page 187: ...al form of user selected Modbus Register Address corresponding to first Tilde marker MESSAGE DISP 1 ITEM 2 6357 Shows decimal form of user selected Modbus Register Address corresponding to 2nd Tilde m...

Page 188: ...ce are not being received Direct input and output settings are similar to remote input and output settings The equivalent of the remote device name strings for direct inputs and outputs is the DIRECT...

Page 189: ...perands flags bits to be exchanged Table 5 5 DIRECT INPUT AND OUTPUT DATA RATES MODULE CHANNEL SUPPORTED DATA RATES 74 Channel 1 64 kbps Channel 2 64 kbps 7L Channel 1 64 kbps 128 kbps Channel 2 64 kb...

Page 190: ...DIRECT I O CH1 RING CONFIGURATION Yes DIRECT I O DATA RATE 128 kbps For UR series IED 2 DIRECT OUTPUT DEVICE ID 2 DIRECT I O CH1 RING CONFIGURATION Yes DIRECT I O DATA RATE 128 kbps The message deliv...

Page 191: ...rings are healthy IED 1 to IED 2 0 2 of power system cycle IED 1 to IED 3 0 4 of power system cycle IED 1 to IED 4 0 2 of power system cycle IED 2 to IED 3 0 2 of power system cycle IED 2 to IED 4 0...

Page 192: ...UT DEVICE ID 1 DIRECT I O CH1 RING CONFIGURATION Yes DIRECT I O CH2 RING CONFIGURATION Yes For UR series IED 3 DIRECT OUTPUT DEVICE ID 1 DIRECT I O CH1 RING CONFIGURATION Yes DIRECT I O CH2 RING CONFI...

Page 193: ...H1 2 PATH SETTINGS PRODUCT SETUP DIRECT I O CRC ALARM CH1 2 The C60 checks integrity of the incoming direct input and output messages using a 32 bit CRC The CRC alarm function is available for monitor...

Page 194: ...ming the best case of only 1 bit error in a failed packet having 1 failed packet for every 63 received is about equal to a BER of 10 4 c UNRETURNED MESSAGES ALARM CH1 2 PATH SETTINGS PRODUCT SETUP DIR...

Page 195: ...AL 2 RELAY ID NUMBER In installa tions that use multiplexers or modems it is desirable to ensure that the data used by the relays protecting a given line is from the correct relays The teleprotection...

Page 196: ...tting is defaulted to Not Programmed when at the factory The UNIT NOT PROGRAMMED self test error message is displayed until the relay is put into the Programmed state The RELAY NAME setting allows the...

Page 197: ...sists of the following steps Configure the field units This establishes the point to point connection between a specific port on the relay process bus module and a specific digital core on a specific...

Page 198: ...round CT primary rating must be entered To detect low level ground fault currents the sensitive ground input may be used In this case the sensitive ground CT primary rating must be entered Refer to ch...

Page 199: ...ARY voltage setting is the voltage across the relay input terminals when nominal voltage is applied to the VT primary For example on a system with a 13 8 kV nominal primary voltage and with a 14400 12...

Page 200: ...used for angle referencing while Clarke transformation of the phase signals is used for frequency metering and tracking for better performance dur ing fault open pole and VT and CT fail conditions Th...

Page 201: ...n the relevant settings menu The internal design of the ele ment specifies which type of parameter to use and provides a setting for source selection In elements where the parameter may be either fund...

Page 202: ...this application and the CT VT inputs that are used to provide the data Figure 5 20 EXAMPLE USE OF SOURCES INCREASING SLOT POSITION LETTER CT VT MODULE 1 CT VT MODULE 2 CT VT MODULE 3 CTs VTs not app...

Page 203: ...Range FlexLogic operand MESSAGE BREAKER 1 A 3P CLSD Off Range FlexLogic operand MESSAGE BREAKER 1 A 3P OPND Off Range FlexLogic operand MESSAGE BREAKER 1 B CLOSED Off Range FlexLogic operand MESSAGE B...

Page 204: ...and used to track the breaker open or closed position If the mode is selected as 1 Pole the input mentioned above is used to track phase A and the BREAKER 1 B and BREAKER 1 C settings select operands...

Page 205: ...ed BREAKER 1 FUNCTION SETTING Off 0 BREAKER 1 BLOCK OPEN FLEXLOGIC OPERANDS TRIP PHASE A TRIP PHASE B TRIP PHASE C TRIP 3 POLE SETTING Off 0 BREAKER 1 OPEN SETTING Enabled BREAKER 1 PUSHBUTTON CONTROL...

Page 206: ...OPND SETTING Off BREAKER 1 OPENED B SETTING Off BREAKER 1 OPENED C SETTING Off BREAKER 1 OUT OF SV SETTING BREAKER 1 Toperate 0 SETTING BREAKER 1 Toperate 0 SETTING BREAKER 1 Toperate 0 from breaker c...

Page 207: ...ct switch 1 SWITCH 1 MODE This setting selects 3 pole mode where all disconnect switch poles are operated simultaneously or 1 pole mode where all disconnect switch poles are operated either independen...

Page 208: ...ate a logic 1 when the disconnect switch is open If a separate 52 b contact input is not avail able then the inverted SWITCH 1 CLOSED status signal can be used SWITCH 1 B CLOSED If the mode is selecte...

Page 209: ...1 Toperate 0 FLEXLOGIC OPERAND SWITCH 1 CLOSED FLEXLOGIC OPERAND SWITCH 1 OPEN FLEXLOGIC OPERAND SWITCH 1 DISCREP FLEXLOGIC OPERAND SWITCH 1 TROUBLE FLEXLOGIC OPERAND SWITCH 1 BAD STATUS FLEXLOGIC OP...

Page 210: ...e of pickup of 1 that is 0 98 pu and 1 03 pu It is recommended to set the two times to a similar value otherwise the lin ear approximation may result in undesired behavior for the operating quantity t...

Page 211: ...at higher currents and where upstream and downstream pro tective devices have different operating characteristics The recloser curve configuration window shown below appears when the Initialize From E...

Page 212: ...see below Figure 5 25 COMPOSITE RECLOSER CURVE WITH HCT DISABLED With the HCT feature enabled the operating time reduces to 30 ms for pickup multiples exceeding 8 times pickup Figure 5 26 COMPOSITE R...

Page 213: ...CURVES GE113 GE120 GE138 AND GE142 GE104 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 01 0 02 0 05 0 1 0 2 0 5 1 2 CURRENT multiple of pickup TIME sec GE101 GE102 GE103 GE106 GE105 842723A1 CDR 1 1 2...

Page 214: ...D GE201 Figure 5 30 RECLOSER CURVES GE131 GE141 GE152 AND GE200 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 5 1 2 5 10 20 50 CURRENT multiple of pickup TIME sec GE134 GE151 GE140 GE137 GE201 842730A1...

Page 215: ...E116 GE117 GE118 GE132 GE136 AND GE139 842729A1 CDR 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 01 0 02 0 05 0 1 0 2 0 5 1 2 5 10 20 50 CURRENT multiple of pickup TIME sec GE133 GE163 GE162 GE161 GE16...

Page 216: ...igure 5 34 RECLOSER CURVES GE119 GE135 AND GE202 842724A1 CDR 1 1 2 1 5 2 2 5 3 4 5 6 7 8 9 10 12 15 20 0 01 0 02 0 05 0 1 0 2 0 5 1 2 5 10 20 CURRENT multiple of pickup TIME sec GE121 GE114 GE112 GE1...

Page 217: ...act output The state of the contact input can be displayed locally or viewed remotely via the communications facilities provided If a simple scheme where a contact input is used to block an element is...

Page 218: ...ON IF Contact Input On Cont Ip On Voltage is presently applied to the input external contact closed Off Cont Ip Off Voltage is presently not applied to the input external contact open Contact Output t...

Page 219: ...is in progress via dead time 2 A three pole reclosure is in progress via dead time 3 A three pole reclosure is in progress via dead time 4 Autoreclosure is in lockout state Reclosure of breaker 1 is...

Page 220: ...another Breaker 1 phase B is closed Breaker 1 phase B is open Breaker 1 phase C bad status is detected discrepancy between the 52 a and 52 b contacts Breaker 1 phase A intermediate status is detected...

Page 221: ...s picked up Phase C of phase instantaneous overcurrent 1 has picked up Phase A of phase instantaneous overcurrent 1 has operated Phase B of phase instantaneous overcurrent 1 has operated Phase C of ph...

Page 222: ...A CLSD SWITCH 1 A OPEN SWITCH 1 B BAD ST SWITCH 1 A INTERM SWITCH 1 B CLSD SWITCH 1 B OPEN SWITCH 1 C BAD ST SWITCH 1 A INTERM SWITCH 1 C CLSD SWITCH 1 C OPEN SWITCH 1 BAD STATUS SWITCH 1 CLOSED SWIT...

Page 223: ...ill not appear unless ordered will not appear unless ordered will not appear unless ordered INPUTS OUTPUTS Contact outputs current from detector on form A output only Cont Op 1 IOn Cont Op 2 IOn will...

Page 224: ...ET OP OPERAND RESET OP PUSHBUTTON Reset command is operated set by all three operands below Communications source of the reset command Operand assigned in the INPUTS OUTPUTS RESETTING menu source of t...

Page 225: ...gates are tabulated below and the operators available in FlexLogic are listed in the Flex Logic operators table USER PROGRAMMABLE PUSHBUTTONS PUSHBUTTON 1 ON PUSHBUTTON 1 OFF ANY PB ON Pushbutton numb...

Page 226: ...the last entry in the list of processed FlexLogic parameters One shot POSITIVE ONE SHOT One shot that responds to a positive going edge A one shot refers to a single input gate that generates a pulse...

Page 227: ...17 through 25 to AND 9 and the outputs from these two gates to AND 2 Inspect each operator between the initial operands and final virtual outputs to determine if the output from the operator is used...

Page 228: ...to start at the output end of the equation and work back towards the input as shown in the following steps It is also recommended to list operator inputs from bottom to top For demonstration the final...

Page 229: ...et of parame ters into a logic diagram The result of this process is shown below which is compared to the logic for virtual output 3 dia gram as a check Figure 5 41 FLEXLOGIC EQUATION FOR VIRTUAL OUTP...

Page 230: ...es where a lot of processing is required to perform logic this may be difficult to achieve but in most cases will not cause problems as all logic is calculated at least four times per power frequency...

Page 231: ...EQUATION EDITOR PATH SETTINGS FLEXLOGIC FLEXLOGIC EQUATION EDITOR There are 512 FlexLogic entries available numbered from 1 to 512 with default END entry settings If a Disabled Ele ment is selected a...

Page 232: ...Disabled Range Disabled Enabled MESSAGE FLEXELEMENT 1 NAME FxE1 Range up to 6 alphanumeric characters MESSAGE FLEXELEMENT 1 IN Off Range Off any analog actual value parameter MESSAGE FLEXELEMENT 1 IN...

Page 233: ...applications for the Absolute setting include monitoring the angular difference between two phasors with a symmetrical limit angle in both directions monitoring power regardless of its direction or mo...

Page 234: ...PKP FLEXELEMENT DIRECTION Over PICKUP HYSTERESIS of PICKUP FlexElement 1 OpSig FLEXELEMENT 1 PKP FLEXELEMENT DIRECTION Under PICKUP HYSTERESIS of PICKUP 842705A1 CDR 842706A2 CDR FlexElement 1 OpSig F...

Page 235: ...DT UNIT setting specifies the time unit for the setting FLEXELEMENT 1 dt This setting is applicable only if FLEXELEMENT 1 COMP MODE is set to Delta The FLEXELEMENT 1 DT setting specifies duration of t...

Page 236: ...specified FlexLogic operand resets Latch 1 Figure 5 46 NON VOLATILE LATCH OPERATION TABLE N 1 to 16 AND LOGIC LATCH 1 LATCH 1 FUNCTION Disabled Range Disabled Enabled MESSAGE LATCH 1 TYPE Reset Domin...

Page 237: ...The active setting group can be preset or selected via the SETTING GROUPS menu see the Control elements section later in this chapter See also the Introduction to elements section at the beginning of...

Page 238: ...CKUP 1 050 pu Range 0 001 to 30 000 pu in steps of 0 001 MESSAGE BF1 USE TIMER 1 Yes Range Yes No MESSAGE BF1 TIMER 1 PICKUP DELAY 0 000 s Range 0 000 to 65 535 s in steps of 0 001 MESSAGE BF1 USE TIM...

Page 239: ...f a current supervised initiate results in the breaker failure ele ment not being initiated for a breaker that has very little or no current flowing through it which may be the case for trans former f...

Page 240: ...serts an opening resistor into the faulted circuit to a lower level after resistor insertion The high set detector is enabled after timeout of timer 1 or 2 along with a timer that will enable the low...

Page 241: ...or three pole tripping schemes BF1 USE TIMER 1 If set to Yes the early path is operational BF1 TIMER 1 PICKUP DELAY Timer 1 is set to the shortest time required for breaker auxiliary contact Status 1...

Page 242: ...ximately 90 of the resistor current This setting is valid only for three pole breaker failure schemes BF1 LOSET TIME DELAY Sets the pickup delay for current detection after opening resistor insertion...

Page 243: ...SETTING Off 0 Use Seal In SETTING Yes 1 No 0 Use Current Supervision SETTING Yes 1 No 0 Phase C Initiate SETTING Off 0 SETTING RUN IC Pickup RUN IA Pickup RUN IB Pickup Initiated phase A to breaker fa...

Page 244: ...reaker failure logic sheet 1 0 Timer 2 Pickup Delay SETTING AND Use Timer 3 SETTINGS Yes 1 Breaker Pos 2 Phase A 3P Off 0 Breaker Pos 2 Phase B Off 0 Breaker Pos 2 Phase C Off 0 Breaker Test On Off 0...

Page 245: ...GE Multilin C60 Breaker Protection System 5 117 5 SETTINGS 5 6 GROUPED ELEMENTS 5 Figure 5 51 THREE POLE BREAKER FAILURE INITIATE Sheet 1 of 2...

Page 246: ...5 118 C60 Breaker Protection System GE Multilin 5 6 GROUPED ELEMENTS 5 SETTINGS 5 Figure 5 52 THREE POLE BREAKER FAILURE TIMERS Sheet 2 of 2...

Page 247: ...PHASE TOC4 MESSAGE PHASE TOC5 Note Seen only if slot F or slot M has an 8H or 8J CT module installed MESSAGE PHASE TOC6 Note Seen only if slot F or slot M has an 8H or 8J CT module installed MESSAGE...

Page 248: ...zero results in an instantaneous response to all current levels above pickup Time overcurrent time calculations are made with an internal energy capacity memory variable When this variable indi cates...

Page 249: ...587 8 007 5 187 3 710 2 837 2 277 1 897 1 626 6 0 136 090 57 130 21 880 12 010 7 780 5 564 4 255 3 416 2 845 2 439 8 0 181 454 76 174 29 174 16 014 10 374 7 419 5 674 4 555 3 794 3 252 10 0 226 817 9...

Page 250: ...280 3 837 3 528 3 297 3 116 2 971 IEC CURVE B 0 05 1 350 0 675 0 338 0 225 0 169 0 135 0 113 0 096 0 084 0 075 0 10 2 700 1 350 0 675 0 450 0 338 0 270 0 225 0 193 0 169 0 150 0 20 5 400 2 700 1 350 0...

Page 251: ...8 1 239 1 060 0 926 IAC VERY INVERSE 0 5 1 451 0 656 0 269 0 172 0 133 0 113 0 101 0 093 0 087 0 083 1 0 2 901 1 312 0 537 0 343 0 266 0 227 0 202 0 186 0 174 0 165 2 0 5 802 2 624 1 075 0 687 0 533 0...

Page 252: ...stanta neous to 600 00 seconds in steps of 10 ms EQ 5 14 EQ 5 15 where T Operate Time sec TDM Multiplier setting I Input Current Ipickup Pickup Current setting TRESET Reset Time in seconds assuming en...

Page 253: ...ced by a voltage restraint feature when enabled This is accom plished via the multipliers Mvr corresponding to the phase phase voltages of the voltage restraint characteristic curve see the figure bel...

Page 254: ...PHASE TOC1 BLOCK B PHASE TOC1 VOLT RESTRAINT PHASE TOC1 A PKP PHASE TOC1 A DPO PHASE TOC1 A OP PHASE TOC1 B PKP PHASE TOC1 B DPO PHASE TOC1 B OP PHASE TOC1 C PKP PHASE TOC1 C DPO PHASE TOC1 C OP PHAS...

Page 255: ...4 MESSAGE PHASE IOC1 PICKUP 1 000 pu Range 0 000 to 30 000 pu in steps of 0 001 MESSAGE PHASE IOC1 PICKUP DELAY 0 00 s Range 0 00 to 600 00 s in steps of 0 01 MESSAGE PHASE IOC1 RESET DELAY 0 00 s Ra...

Page 256: ...0 5 10 15 20 25 30 35 1 05 1 1 1 2 1 5 2 5 10 15 20 Multiple of pickup Maximum Minimum Milliseconds 843807A1 CDR IA PICKUP SETTING PHASE IOC1 FUNCTION Enabled 1 Disabled 0 SETTING PHASE IOC1 SOURCE IA...

Page 257: ...AGE NEUTRAL TOC4 MESSAGE NEUTRAL TOC5 Note Seen only if slot F or slot M has an 8H or 8J CT module installed MESSAGE NEUTRAL TOC6 Note Seen only if slot F or slot M has an 8H or 8J CT module installed...

Page 258: ...nd the element is blocked the time accumulator will be cleared immediately Figure 5 57 NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC NEUTRAL TOC1 NEUTRAL TOC1 FUNCTION Disabled Range Disabled Enabled MESSAG...

Page 259: ...faults The positive sequence restraint must be considered when testing for pickup accuracy and response time multiple of pickup The operating quantity depends on how test currents are injected into t...

Page 260: ...GROUND TOC4 MESSAGE GROUND TOC5 Note Seen only if slot F or slot M has an 8H or 8J CT module installed MESSAGE GROUND TOC6 Note Seen only if slot F or slot M has an 8H or 8J CT module installed MESSAG...

Page 261: ...to 46 times the CT rating This channel may be also equipped with a sensitive input The conversion range of a sensitive channel is from 0 002 to 4 6 times the CT rating Figure 5 59 GROUND TOC1 SCHEME...

Page 262: ...rom 0 002 to 4 6 times the CT rating Figure 5 60 GROUND IOC1 SCHEME LOGIC GROUND IOC1 GROUND IOC1 FUNCTION Disabled Range Disabled Enabled MESSAGE GROUND IOC1 SIGNAL SOURCE SRC 1 Range SRC 1 SRC 2 SRC...

Page 263: ...Source Transfer Schemes In the event of an undervoltage a transfer signal may be generated to transfer a load from its normal source to a standby or emergency power source The undervoltage elements c...

Page 264: ...oltage The minimum voltage setting selects the operating voltage below which the element is blocked a setting of 0 will allow a dead source to be considered a fault condition PHASE UNDERVOLTAGE1 PHASE...

Page 265: ...sabled Enabled MESSAGE NEUTRAL OV1 SIGNAL SOURCE SRC 1 Range SRC 1 SRC 2 SRC 3 SRC 4 MESSAGE NEUTRAL OV1 PICKUP 0 300 pu Range 0 000 to 3 000 pu in steps of 0 001 MESSAGE NEUTRAL OV1 CURVE Definite ti...

Page 266: ...AUX UV1 DELAY setting selects the minimum operating time of the auxiliary undervoltage element Both AUX UV1 PICKUP and AUX UV1 DELAY settings establish the operating curve of the undervoltage element...

Page 267: ...ication for this element is monitoring the zero sequence voltage 3V_0 supplied from an open corner delta VT connection AUXILIARY OV1 AUX OV1 FUNCTION Disabled Range Disabled Enabled MESSAGE AUX OV1 SI...

Page 268: ...OLTAGE SCHEME LOGIC 827836A2 CDR FLEXLOGIC OPERANDS AUX OV1 FUNCTION AUX OV1 BLOCK AUX OV1 SIGNAL SOURCE AUX OV1 PICKUP AUX OV1 DPO AUX OV1 OP AUX OV1 PKP RUN AND SETTING SETTING AUX OV1 RESET DELAY A...

Page 269: ...ctive powers as measured per the UR series metering convention is a sum of the element characteristic DIR POWER 1 RCA and calibration DIR POWER 1 CALIBRATION angles and SMIN is the minimum operating p...

Page 270: ...d in the figure below For example section a in the figure below shows settings for reverse power while section b shows settings for low forward power applications Figure 5 67 DIRECTIONAL POWER ELEMENT...

Page 271: ...y a shift towards the operate region along the RCA line the negative values imply a shift towards the restrain region along the RCA line Refer to the Directional power sample applications figure for d...

Page 272: ...ecific protection or control protection element and checking the desired bus box Once the desired element is selected for a specific bus a list of element operate type operands are displayed and can b...

Page 273: ...P BUS 1 LATCHING This setting enables or disables latching of the trip bus output This is typically used when lockout is required or user acknowledgement of the relay response is required TRIP BUS 1 R...

Page 274: ...ive The SETTING GROUP 1 NAME to SETTING GROUP 6 NAME settings allows to user to assign a name to each of the six settings groups Once programmed this name will appear on the second line of the GROUPED...

Page 275: ...Time out Acknowledge MESSAGE SELECTOR 1 ACK Off Range FlexLogic operand MESSAGE SELECTOR 1 3BIT A0 Off Range FlexLogic operand MESSAGE SELECTOR 1 3BIT A1 Off Range FlexLogic operand MESSAGE SELECTOR...

Page 276: ...t take place and an alarm will be set SELECTOR 1 STEP UP This setting specifies a control input for the selector switch The switch is shifted to a new position at each rising edge of this signal The p...

Page 277: ...ELEC TOR TIME OUT setting after the last activity of the three bit control inputs Note that the stepping up control input and three bit control input have independent acknowledging signals SELECTOR 1...

Page 278: ...se diagrams T represents a time out setting Figure 5 72 TIME OUT MODE 842737A1 CDR STEP UP 3BIT A0 3BIT A1 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 pre existing position 2 c...

Page 279: ...should synchronize the setting group to the three bit control input Make the following changes to setting group control in the SETTINGS CONTROL ELEMENTS SETTING GROUPS menu SETTING GROUPS FUNCTION En...

Page 280: ...wing changes in the SETTINGS PRODUCT SETUP USER PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu PUSHBUTTON 1 FUNCTION Self reset PUSHBUTTON 1 DROP OUT TIME 0 10 s The logic for the selector switch is...

Page 281: ...equal to 2 at a frequency equal to the frequency difference F This time can be calculated by EQ 5 19 SYNCHROCHECK 1 SYNCHK1 FUNCTION Disabled Range Disabled Enabled MESSAGE SYNCHK1 BLOCK Off Range Fle...

Page 282: ...OURCE SELECT This setting selects the combination of dead and live sources that will by pass synchronism check function and permit the breaker to be closed when one or both of the two voltages V1 or a...

Page 283: ...ith both phase voltages and an auxiliary voltage ensure that only the auxiliary voltage is programmed in one of the sources to be used for synchrocheck Exception Synchronism cannot be checked between...

Page 284: ...INGS F Maximum Max Freq Diff Freq Hysteresis SETTING Maximum Max Angle Diff SETTING V Maximum Max Volt Diff AND OR XOR AND AND AND AND AND 827076AB CDR ACTUAL VALUE Synchrocheck 1 V Synchrocheck 1 Syn...

Page 285: ...owing example Figure 5 76 SYNCHROCHECK APPLIED ACROSS A TRANSFORMER In this example the phase voltage VT input is programmed as Delta with a secondary setting of 120 volts and a ratio of 13800 V 120 V...

Page 286: ...s Range 0 00 to 655 35 s in steps of 0 01 MESSAGE AR 1P INIT Off Range FlexLogic operand MESSAGE AR 3P INIT Off Range FlexLogic operand MESSAGE AR 3P TD INIT Off Range FlexLogic operand MESSAGE AR MU...

Page 287: ...multaneously for the first shot both breakers should reclose with either the single pole or three pole dead time according to the fault type and the reclose mode The signal used to initiate the autore...

Page 288: ...iated for any type of fault and starts the AR 3 P DEAD TIME 1 for the first shot If the initiating signal is AR 3P TD INIT the scheme starts AR 3 P DEAD TIME 2 for the first shot If two or more shots...

Page 289: ...reclose is initiated The breaker is tripped three pole through the AR SHOT COUNT 0 oper and that will set the AR FORCE 3P operand Because the shot counter has reached the maximum number of shots per m...

Page 290: ...gram logic when a 3P Initiate is present and the autoreclose mode is either 1 Pole or 3Pole A 3 pole autoreclose for single pole faults only Initiation of the scheme when the count is at the maximum a...

Page 291: ...r settings In Protection only initiation mode the autoreclose element will be initiated by protection operation and will begin incrementing the dead time when protection resets without the need of bre...

Page 292: ...and will be set If the block signal occurs when the scheme is in the RIP state the scheme will be sent to lockout AR PAUSE The pause input offers the ability to freeze the autoreclose cycle until the...

Page 293: ...he first single pole trip AR BREAKER SEQUENCE This setting selects the breakers reclose sequence Select 1 for reclose breaker 1 only 2 for reclose breaker 2 only 1 2 for reclose both breakers simultan...

Page 294: ...gic sheet 2 SETTING 1 Pole Mode 3 Pole A 3 Pole B OR FLEXLOGIC OPERAND PHASE SELECT MULTI P SETTING Off 0 Multi P Fault 0 5 ms Off 0 Reset OR FLEXLOGIC OPERAND OPEN POLE OP BKR CLOSED from autoreclose...

Page 295: ...OPERAND BREAKER 1 CLOSED SETTING Max Number of Shots 4 3 2 1 0 maximum Increment shout count Decrement shout count Reset count OR AND FLEXLOGIC OPERANDS AR SHOT CNT 4 AR SHOT CNT 3 AR SHOT CNT 2 AR S...

Page 296: ...KER 2 ONE P OPEN BREAKER 2 CLOSED BREAKER 1 MNL CLS BREAKER 1 OOS BREAKER 2 OOS FLEXLOGIC OPERAND FLEXLOGIC OPERAND FLEXLOGIC OPERAND BREAKER 2 MNL CLS FLEXLOGIC OPERAND FLEXLOGIC OPERAND FLEXLOGIC OP...

Page 297: ...PROT T TRIP BKR T PROT RESET T R I P AR RIP AR 1 P RIP AR FORCE 3P TRIP CLOSE AR CLOSE BKR1 T CLOSE BKR1 T TRIP BKR T PROT RESET 3 P 2 DEAD TIME TRANSFER TIME T CLOSE BKR2 842703A4 CDR T PROT T CLOSE...

Page 298: ...ELEMENT SCHEME LOGIC CIRCUIT MONITORING APPLICATIONS Some versions of the digital input modules include an active voltage monitor circuit connected across form A contacts The voltage monitor circuit...

Page 299: ...f the breaker trip coil If the circuit presents a high resis tance the trickle current will fall below the monitor threshold and an alarm would be declared In most breaker control circuits the trip co...

Page 300: ...cuit In this case it is not required to supervise the monitoring circuit with the breaker position the BLOCK setting is selected to Off In this case the settings are as follows EnerVista UR Setup exam...

Page 301: ...EQL or less than LO the set value COUNTER 1 UP Selects the FlexLogic operand for incrementing the counter If an enabled UP input is received when the accumulated value is at the limit of 2 147 483 64...

Page 302: ...for capturing freezing the accumulated count value into a separate register with the date and time of the operation and resetting the count to 0 COUNTER 1 FREEZE COUNT Selects the FlexLogic operand fo...

Page 303: ...ARCING CURRENT See page 5 176 MESSAGE BREAKER 4 ARCING CURRENT See page 5 176 MESSAGE BREAKER FLASHOVER 1 See page 5 178 MESSAGE BREAKER FLASHOVER 2 See page 5 178 MESSAGE BREAKER FLASHOVER 3 See page...

Page 304: ...lt duration is defined as a time between operation of the disturbance detector occurring before initiation of this feature and reset of an internal low set overcurrent function Cor rection is implemen...

Page 305: ...ING AMP BLOCK BREAKER 1 ARCING AMP INIT A BREAKER 1 ARCING AMP INIT B BREAKER 1 ARCING AMP INIT C BREAKER 1 ARCING AMP LIMIT CLEAR BREAKER 1 ARCING AMPS BKR 1 ARCING AMP A BKR 1 OPERATING TIME A BKR 1...

Page 306: ...GE BKR 1 FLSHOVR SIDE 2 SRC None Range None SRC 1 SRC 2 SRC 3 SRC 4 MESSAGE BKR 1 STATUS CLSD A Off Range FlexLogic operand MESSAGE BKR 1 STATUS CLSD B Off Range FlexLogic operand MESSAGE BKR 1 STATUS...

Page 307: ...ection are 1 52a status 0 2 VAg VBg or VCg is greater than the pickup setting 3 IA IB IC 0 no current flows through the breaker 4 VA is greater than pickup not applicable in this scheme The conditions...

Page 308: ...to indicate the open status of the breaker A separate FlexLogic operand can be selected to detect individual breaker pole status and provide flashover detection The recommended setting is 52a breaker...

Page 309: ...BRK 1 FLSHOVR OP B BRK 1 FLSHOVR DPO C BRK 1 FLSHOVR PKP C BRK 1 FLSHOVR OP C BRK 1 FLSHOVR SUPV A BRK 1 STATUS CLSD B BRK 1 FLSHOVR SUPV B BRK 1 STATUS CLSD C BRK 1 FLSHOVR SUPV C BRK 1 FLSHOVR AMP P...

Page 310: ...clared in the corresponding phase and the BRK RESTRIKE 1 OP operand is asserted for a short period of time The user can add coun ters and other logic to facilitate the decision making process as to th...

Page 311: ...KER RESTRIKE 1 SOURCE This setting selects the source of the current for this element This source must have a valid CT bank assigned BREAKER RESTRIKE 1 PICKUP This setting specifies the pickup level o...

Page 312: ...ndications of fuse failure could also be present when faults are present on the system so a means of detecting faults and inhibiting fuse failure declarations during these events is pro vided Once the...

Page 313: ...Latch SET Reset dominant RESET Function SETTING Disabled 0 Enabled 1 SOURCE 1 V_2 V_1 I_1 COMPARATORS Run V_1 0 05 pu Run V_2 0 1 pu Run I_1 0 075 pu Run V_1 0 80 pu Run I_1 0 05 pu SRC1 50DD OP FLEX...

Page 314: ...settable debounce time in order for the C60 to validate the new contact state In the figure below the debounce time is set at 2 5 ms thus the 6th sample in a row validates the change of state mark no...

Page 315: ...ter the LOW HIGH marks no 1 2 3 and 4 in the figure below and HIGH LOW marks no 5 6 7 and 8 below transitions Figure 5 92 INPUT CONTACT DEBOUNCING MECHANISM AND TIME STAMPING SAMPLE TIMING Contact inp...

Page 316: ...and will be set to on for only one evaluation of the FlexLogic equations and then return to off If set to Latched the virtual input sets the state of the output operand to the same state as the most r...

Page 317: ...damage to the less robust initiating contact This can be done by monitoring an auxiliary contact on the breaker which opens when the breaker has tripped but this scheme is subject to incorrect oper at...

Page 318: ...cifies the contact response under conflicting control inputs that is when both the OPERATE and RESET signals are applied With both control inputs applied simultaneously the contact will close if set t...

Page 319: ...sta UR Setup example shown Program the Latching Outputs by making the following changes in the SETTINGS INPUTS OUTPUTS CONTACT OUT PUTS CONTACT OUTPUT H1a menu assuming an H4L module OUTPUT H1a OPERAT...

Page 320: ...implementation provides 32 of the 96 available UserSt bit pairs The IEC 61850 specification includes features that are used to cope with the loss of communication between transmitting and receiving d...

Page 321: ...and UserSt 1 through UserSt 32 The function of DNA inputs is defined in the IEC 61850 specification and is presented in the IEC 61850 DNA Assignments table in the Remote outputs section The function...

Page 322: ...emote double point status input REM DPS IN 1 DEV This setting selects a remote device ID to indicate the origin of a GOOSE message The range is selected from the remote device IDs specified in the Rem...

Page 323: ...ETTING PATH SETTINGS INPUTS OUTPUTS RESETTING Some events can be programmed to latch the faceplate LED event indicators and the target message on the display Once set the latching mechanism will hold...

Page 324: ...communication exchange the input will default to Logic 1 When communication resumes the input becomes fully operational Setting DIRECT INPUT 1 DEFAULT STATE to Latest Off freezes the input in case of...

Page 325: ...al from downstream devices say 2 3 and 4 to the upstream device that monitors a single incomer of the busbar as shown in the figure below Figure 5 95 SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME Assum...

Page 326: ...hitecture shown below The scheme output operand HYB POTT TX1 is used to key the permission Figure 5 97 SINGLE CHANNEL OPEN LOOP CONFIGURATION In the above architecture Devices 1 and 3 do not communica...

Page 327: ...CT INPUT AND OUTPUT EXAMPLE 3 In three terminal applications both the remote terminals must grant permission to trip Therefore at each terminal direct inputs 5 and 6 should be ANDed in FlexLogic and t...

Page 328: ...ality The teleprotection function must be enabled to utilize the inputs b TELEPROTECTION INPUTS PATH SETTINGS INPUTS OUTPUTS TELEPROTECTION TELEPROT INPUTS Setting the TELEPROT INPUT DEFAULT setting t...

Page 329: ...OUTPUT 2 1 Off Range FlexLogic operand MESSAGE TELEPROT OUTPUT 2 2 Off Range FlexLogic operand MESSAGE TELEPROT OUTPUT 2 16 Off Range FlexLogic operand 842750A2 CDR TELEPROT OUTPUT 1 1 same for 1 2 1...

Page 330: ...en using the GOOSE analog input FlexAna log values in other C60 features such as FlexElements The base factor is applied to the GOOSE analog input FlexAnalog quantity to normalize it to a per unit qua...

Page 331: ...UINTEGER 1 DEFAULT MODE is set to Default Value This setting is stored as a 32 bit unsigned integer number UINTEGER 1 DEFAULT MODE When the sending device is offline and this setting is Last Known the...

Page 332: ...automatically generated for every channel available in the specific relay as shown above for the first channel of a type 5F transducer module installed in slot H The function of the channel may be ei...

Page 333: ...re automatically generated for every channel available in the specific relay as shown above for the first channel of a type 5C transducer module installed in the first available slot The function of t...

Page 334: ...12 90 194 134 70 191 64 159 70 12 51 100 212 138 50 200 64 167 20 12 90 110 230 142 29 209 85 174 87 13 28 120 248 146 06 219 29 182 75 13 67 130 266 149 82 228 96 190 80 14 06 140 284 153 58 238 85...

Page 335: ...EQ 5 21 The feature is intentionally inhibited if the MAX VAL and MIN VAL settings are entered incorrectly e g when MAX VAL MIN VAL 0 1 pu The resulting characteristic is illustrated in the following...

Page 336: ...following settings should be entered DCMA OUTPUT H1 SOURCE SRC 1 P DCMA OUTPUT H1 RANGE 1 to 1 mA DCMA OUTPUT H1 MIN VAL 1 247 pu DCMA OUTPUT H1 MAX VAL 1 247 pu With the above settings the output wil...

Page 337: ...his chapter for additional details is EQ 5 30 The minimum and maximum voltage values to be monitored in pu are EQ 5 31 The following settings should be entered DCMA OUTPUT H3 SOURCE SRC 2 V_1 mag DCMA...

Page 338: ...based inputs and outputs remain fully operational in test mode If a control action is programmed using direct inputs and outputs or remote inputs and outputs then the test procedure must take this in...

Page 339: ...voltage across the input terminals The force contact inputs feature provides a method of performing checks on the function of all contact inputs Once enabled the relay is placed into test mode allowin...

Page 340: ...3 should open and digital input 4 should close Also contact output 1 should freeze contact output 2 should open contact output 3 should close and contact output 4 should remain fully operational The r...

Page 341: ...NTACT OUTPUTS See page 6 4 VIRTUAL OUTPUTS See page 6 5 AUTORECLOSE See page 6 5 REMOTE DEVICES STATUS See page 6 5 REMOTE DEVICES STATISTICS See page 6 6 DIGITAL COUNTERS See page 6 6 SELECTOR SWITCH...

Page 342: ...61850 GOOSE ANALOGS See page 6 20 SENSITIVE DIRECTIONAL POWER See page 6 20 TRANSDUCER I O DCMA INPUTS See page 6 20 TRANSDUCER I O RTD INPUTS See page 6 20 ACTUAL VALUES RECORDS FAULT REPORTS See pag...

Page 343: ...es the ID of the virtual input For example Virt Ip 1 refers to the virtual input in terms of the default name The second line of the display indicates the logic state of the virtual input 6 2 3 REMOTE...

Page 344: ...The first line of a message display indicates the ID of the contact output For example Cont Op 1 refers to the contact output in terms of the default name array index The second line of the display i...

Page 345: ...at output 6 2 8 AUTORECLOSE PATH ACTUAL VALUES STATUS AUTORECLOSE The automatic reclosure shot count is shown here 6 2 9 REMOTE DEVICES a STATUS PATH ACTUAL VALUES STATUS REMOTE DEVICES STATUS The pre...

Page 346: ...defined counter name includes the accumulated and frozen counts the count units label will also appear Also included is the date and time stamp for the frozen count The COUNTER 1 MICROS value refers...

Page 347: ...tions channel count the direct output messages that do not make the trip around the communications ring The CRC FAIL COUNT values one per communications channel count the direct output messages that h...

Page 348: ...ed The IEC 61850 GGIO5 integer input data points are displayed in this menu The GGIO5 integer data values are received via IEC 61850 GOOSE messages sent from other devices 6 2 17 EGD PROTOCOL STATUS a...

Page 349: ...ission this count can be reset to 0 through the COMMANDS CLEAR RECORDS menu VALIDITY OF CHANNEL CONFIGURATION This value displays the current state of the communications channel identification check a...

Page 350: ...h is shown in this menu SWITCH 1 PORT STATUS to SWITCH 6 PORT STATUS These values represents the receiver status of each port on the Ethernet switch If the value is OK then data is being received from...

Page 351: ...e PF Lag Current Voltage WATTS Positive VARS Negative PF Lead Current Voltage WATTS Negative VARS Negative PF Lag Current Voltage WATTS Negative VARS Positive PF Lead Current Generator Generator Induc...

Page 352: ...measurable the phase angles are not referenced The phase angles are assigned as positive in the leading direction and are presented as negative in the lagging direction to more closely align with pow...

Page 353: ...ated in the following figure Figure 6 3 MEASUREMENT CONVENTION FOR SYMMETRICAL COMPONENTS ABC phase rotation ACB phase rotation Table 6 1 SYMMETRICAL COMPONENTS CALCULATION EXAMPLE SYSTEM VOLTAGES SEC...

Page 354: ...PATH ACTUAL VALUES METERING SOURCE SRC 1 PHASE CURRENT SOURCE SRC 1 PHASE CURRENT SRC 1 See page 6 14 MESSAGE GROUND CURRENT SRC 1 See page 6 15 MESSAGE PHASE VOLTAGE SRC 1 See page 6 15 MESSAGE AUXIL...

Page 355: ...rce see SETTINGS SYSTEM SETUP SIGNAL SOURCES d PHASE VOLTAGE METERING PATH ACTUAL VALUES METERING SOURCE SRC 1 PHASE VOLTAGE MESSAGE SRC 1 ZERO SEQ I0 0 000 A 0 0 MESSAGE SRC 1 POS SEQ I1 0 000 A 0 0...

Page 356: ...TTINGS SYSTEM SETUP SIGNAL SOURCES f POWER METERING PATH ACTUAL VALUES METERING SOURCE SRC 1 POWER MESSAGE SRC 1 PHASOR Vca 0 000 V 0 0 MESSAGE SRC 1 ZERO SEQ V0 0 000 V 0 0 MESSAGE SRC 1 POS SEQ V1 0...

Page 357: ...IGNAL SOURCES Because energy values are accumulated these values should be recorded and then reset immediately prior to changing CT or VT characteristics h DEMAND METERING PATH ACTUAL VALUES METERING...

Page 358: ...CTUAL VALUES METERING SOURCE SRC 1 FREQUENCY The metered frequency values are displayed in this menu The SRC 1 text will be replaced by whatever name was pro grammed by the user for the associated sou...

Page 359: ...GE SYNCHROCHECK 1 DELTA PHASE 0 0 MESSAGE SYNCHROCHECK 1 DELTA FREQ 0 00 Hz TRACKING FREQUENCY TRACKING FREQUENCY 60 00 Hz FLEXELEMENT 1 FLEXELEMENT 1 OpSig 0 000 pu Table 6 2 FLEXELEMENT BASE UNITS B...

Page 360: ...itive directional power elements are displayed here The display may be useful to calibrate the feature by compensating the angular errors of the CTs and VTs with the use of the RCA and CALIBRATION set...

Page 361: ...1024 events listed in chronological order from most recent to oldest If all 1024 event records have been filled the oldest record will be removed as a new record is added Each event record shows the...

Page 362: ...ords 6 4 4 DATA LOGGER PATH ACTUAL VALUES RECORDS DATA LOGGER The OLDEST SAMPLE TIME represents the time at which the oldest available samples were taken It will be static until the log gets full at w...

Page 363: ...Refer to the COMMANDS CLEAR RECORDS menu for clearing breaker arcing current records The BREAKER OPERATING TIME is defined as the slowest operating time of breaker poles that were initiated to open BR...

Page 364: ...NUMBER Range standard GE multilin serial number format MESSAGE ETHERNET MAC ADDRESS 000000000000 Range standard Ethernet MAC address format MESSAGE MANUFACTURING DATE 0 Range YYYY MM DD HH MM SS MESS...

Page 365: ...fully command entry 7 1 2 VIRTUAL INPUTS PATH COMMANDS VIRTUAL INPUTS The states of up to 64 virtual inputs are changed here The first line of the display indicates the ID of the virtual input The sec...

Page 366: ...the 24 hour clock The complete date as a minimum must be entered to allow execution of this com mand The new time will take effect at the moment the ENTER key is clicked COMMANDS CLEAR RECORDS CLEAR...

Page 367: ...hown The SERVICE COMMAND is used to perform specific C60 service actions Presently there is only one service action avail able Code 101 is used to clear factory diagnostic information stored in the no...

Page 368: ...s have not been programmed 7 2 3 RELAY SELF TESTS a DESCRIPTION The relay performs a number of self test diagnostic checks to ensure device integrity The two types of self tests major and minor are li...

Page 369: ...ow often the test is performed On power up Afterwards the backplane is checked for missing cards every five sec onds What to do Check all modules against the order code ensure they are inserted proper...

Page 370: ...switch How often the test is performed Monitored every five seconds An error is issued after five consecutive failures What to do Check the C60 device and switch IP configuration settings Check for i...

Page 371: ...Upon initiation of a contact output state change What to do Verify the state of the output contact and contact the factory if the problem persists Latched target message No Description of problem A d...

Page 372: ...emperature is greater than the maximum operating temperature 80 C How often the test is performed Every hour What to do Remove the C60 from service and install in a location that meets operating tempe...

Page 373: ...enables this functionality When entering a settings or command password via EnerVista or any serial interface the user must enter the correspond ing connection password If the connection is to the ba...

Page 374: ...attempt to change the setting and follow the prompt to enter the programmed password If the password is correctly entered access will be allowed Accessibility automatically reverts to the Restricted...

Page 375: ...new password in the Enter New Password field 2 Re enter the password in the Confirm New Password field 3 Click the Change button This button will not be active until the new password matches the confi...

Page 376: ...MEOUTS These settings allow the user to specify the length of inactivity required before returning to the restricted access level Note that the access level will set as restricted if control power is...

Page 377: ...transition of the FlexLogic operand is detected the time out is restarted The status of this timer is updated every 5 seconds The following settings are available through the remote EnerVista UR Setup...

Page 378: ...ed by default The following procedure describes how to enable the settings tem plate for UR series settings files 1 Select a settings file from the offline window of the EnerVista UR Setup main screen...

Page 379: ...n them The setting available to view will be displayed against a yellow background as shown below Figure 8 3 SETTINGS TEMPLATE VIEW TWO SETTINGS SPECIFIED AS EDITABLE 6 Click on Save to save changes t...

Page 380: ...available for editing Display all settings with settings not available for editing greyed out Use the following procedure to only display settings available for editing 1 Select an installed device or...

Page 381: ...plate but all settings will be shown The effect of applying the template to the phase time overcurrent settings is shown below Figure 8 6 APPLYING TEMPLATES VIA THE VIEW ALL SETTINGS COMMAND e REMOVIN...

Page 382: ...llowing procedure describes how to lock individual entries of a FlexLogic equation 1 Right click the settings file or online device and select the Template Mode Create Template item to enable the set...

Page 383: ...he front panel display Figure 8 9 SECURED FLEXLOGIC IN GRAPHICAL VIEW b LOCKING FLEXLOGIC EQUATIONS TO A SERIAL NUMBER A settings file and associated FlexLogic equations can also be locked to a specif...

Page 384: ...be compared with the C60 actual values at any later date to determine if security has been compromised The traceability information is only included in the settings file if a complete settings file i...

Page 385: ...ion since the settings file was saved a SETTINGS FILE TRACEABILITY INFORMATION The serial number and file transfer date are saved in the settings files when they sent to an C60 device The C60 serial n...

Page 386: ...SERIAL NUMBER ACTUAL VALUES PRODUCT INFO MODEL INFORMATION LAST SETTING CHANGE c ADDITIONAL TRACEABILITY RULES The following additional rules apply for the traceability feature If the user changes any...

Page 387: ...y management system is disabled by default This allows access to the device immediately after installation When security is disabled all users are granted administrator access 1 Select the Security Us...

Page 388: ...e user when exiting the user management configuration window Actual Values Checking this box allows the user to read actual values Settings Checking this box allows the user to read setting values Com...

Page 389: ...allows the user to execute commands Event Recorder Checking this box allows the user to use the digital fault recorder FlexLogic Checking this box allows the user to read FlexLogic values Update Info...

Page 390: ...8 18 C60 Breaker Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8...

Page 391: ...istance to fault Z positive sequence impedance of the line The currents from the local and remote systems can be parted between their fault F and pre fault load pre components EQ 9 2 and neglecting sh...

Page 392: ...1 VT SUBSTITUTION setting value is V0 and the VTs are connected in a wye configuration the fault location is performed based on the actual phase to ground voltages If the VTs are connected in a delta...

Page 393: ...50DD OP X VA or VAB VC or VCA VB or VBC 827094A5 CDR Off 0 AND FAULT LOCATOR 1 RUN 0 3 SEC ACTUAL VALUES DATE TIME FAULT TYPE FAULT LOCATION FAULT RECLOSE SHOT FAULT REPORT Vn or V_0 FAULT REPORT 1 Z1...

Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...

Page 395: ...Mag Degrees Source 1 positive sequence current magnitude 6174 SRC 1 I_1 Angle Amps Source 1 positive sequence current angle 6175 SRC 1 I_2 Mag Degrees Source 1 negative sequence current magnitude 6177...

Page 396: ...I_2 Mag Degrees Source 3 negative sequence current magnitude 6305 SRC 3 I_2 Angle Amps Source 3 negative sequence current angle 6306 SRC 3 Igd Mag Degrees Source 3 differential ground current magnitu...

Page 397: ...Vx Angle Degrees Source 1 auxiliary voltage angle 6691 SRC 1 V_0 Mag Volts Source 1 zero sequence voltage magnitude 6693 SRC 1 V_0 Angle Degrees Source 1 zero sequence voltage angle 6694 SRC 1 V_1 Mag...

Page 398: ...6807 SRC 3 Vab Angle Degrees Source 3 phase AB voltage angle 6808 SRC 3 Vbc Mag Volts Source 3 phase BC voltage magnitude 6810 SRC 3 Vbc Angle Degrees Source 3 phase BC voltage angle 6811 SRC 3 Vca M...

Page 399: ...ase C real power 7176 SRC 1 Q Vars Source 1 three phase reactive power 7178 SRC 1 Qa Vars Source 1 phase A reactive power 7180 SRC 1 Qb Vars Source 1 phase B reactive power 7182 SRC 1 Qc Vars Source 1...

Page 400: ...74 SRC 4 Qa Vars Source 4 phase A reactive power 7276 SRC 4 Qb Vars Source 4 phase B reactive power 7278 SRC 4 Qc Vars Source 4 phase C reactive power 7280 SRC 4 S VA Source 4 three phase apparent pow...

Page 401: ...t phase B voltage magnitude 9038 Prefault Vb Ang 0 Degrees Fault 1 pre fault phase B voltage angle 9039 Prefault Vc Mag 0 Volts Fault 1 pre fault phase C voltage magnitude 9041 Prefault Vc Ang 0 Degre...

Page 402: ...actual value 13548 DCMA Inputs 23 Value mA dcmA input 23 actual value 13550 DCMA Inputs 24 Value mA dcmA input 24 actual value 13552 RTD Inputs 1 Value RTD input 1 actual value 13553 RTD Inputs 2 Val...

Page 403: ...RTD Inputs 47 Value RTD input 47 actual value 13599 RTD Inputs 48 Value RTD input 48 actual value 24459 Active Setting Group Current setting group 32768 Tracking Frequency Hz Tracking frequency 39425...

Page 404: ...9976 GOOSE UInt Input 5 IEC61850 GOOSE UInteger input 5 9978 GOOSE UInt Input 6 IEC61850 GOOSE UInteger input 6 9980 GOOSE UInt Input 7 IEC61850 GOOSE UInteger input 7 9982 GOOSE UInt Input 8 IEC61850...

Page 405: ...00 4800 9600 14400 19200 28800 33600 38400 57600 or 115200 bps are available Even odd and no parity are avail able Refer to the Communications section of chapter 5 for further details The master devic...

Page 406: ...all slaves start listening for a new packet from the master except for the addressed slave B 1 4 CRC 16 ALGORITHM The CRC 16 algorithm essentially treats the entire data stream data bits only start s...

Page 407: ...ing address will determine the type of data being read Function codes 03h and 04h are therefore identical The following table shows the format of the master and slave packets The example shows a maste...

Page 408: ...ION EXAMPLE MASTER TRANSMISSION SLAVE RESPONSE PACKET FORMAT EXAMPLE HEX PACKET FORMAT EXAMPLE HEX SLAVE ADDRESS 11 SLAVE ADDRESS 11 FUNCTION CODE 05 FUNCTION CODE 05 OPERATION CODE high 00 OPERATION...

Page 409: ...function code set to 1 The following table shows the format of the master and slave packets The example shows a master device sending the unsupported function code 39h to slave device 11 Table B 7 MA...

Page 410: ...ns connection specific file transfer information so files may be read simultaneously on multiple Modbus connections b OTHER PROTOCOLS All the files available via Modbus may also be retrieved using the...

Page 411: ...a EnerVista or any serial interface the user must enter the correspond ing connection password If the connection is to the back of the C60 the remote password must be used If the connection is to the...

Page 412: ...and 64 modules 0400 Virtual Input 1 State 0 to 1 1 F108 0 Off 0401 Virtual Input 2 State 0 to 1 1 F108 0 Off 0402 Virtual Input 3 State 0 to 1 1 F108 0 Off 0403 Virtual Input 4 State 0 to 1 1 F108 0 O...

Page 413: ...0 to 1 1 F108 0 Off 0434 Virtual Input 53 State 0 to 1 1 F108 0 Off 0435 Virtual Input 54 State 0 to 1 1 F108 0 Off 0436 Virtual Input 55 State 0 to 1 1 F108 0 Off 0437 Virtual Input 56 State 0 to 1 1...

Page 414: ...ect Input Output States Read Only 15C0 Direct input states 6 items 0 to 65535 1 F500 0 15C8 Direct outputs average message return time 1 0 to 65535 ms 1 F001 0 15C9 Direct outputs average message retu...

Page 415: ...tage RMS V F060 0 1A04 Source 1 Phase CG Voltage RMS V F060 0 1A06 Source 1 Phase AG Voltage Magnitude 0 to 999999 999 V 0 001 F060 0 1A08 Source 1 Phase AG Voltage Angle 359 9 to 0 degrees 0 1 F002 0...

Page 416: ...0 VA 0 001 F060 0 1C16 Source 1 Phase C Apparent Power 1000000000000 to 1000000000000 VA 0 001 F060 0 1C18 Source 1 Three Phase Power Factor 0 999 to 1 0 001 F013 0 1C19 Source 1 Phase A Power Factor...

Page 417: ...1 F050 0 1E94 Source 1 Demand Va Maximum 0 to 999999 999 VA 0 001 F060 0 1E96 Source 1 Demand Va Maximum Date 0 to 4294967295 1 F050 0 1E98 Reserved 8 items F001 0 1EA0 Repeated for Source 2 1EC0 Repe...

Page 418: ...nitude 0 to 999999 999 V 0 001 F060 0 234E Fault 1 Prefault Phase B Voltage Angle 359 9 to 0 degrees 0 1 F002 0 234F Fault 1 Prefault Phase C Voltage Magnitude 0 to 999999 999 V 0 001 F060 0 2351 Faul...

Page 419: ...IEC 61850 GGIO5 uinteger input 13 operand F612 0 26BD IEC 61850 GGIO5 uinteger input 14 operand F612 0 26BE IEC 61850 GGIO5 uinteger input 15 operand F612 0 26BF IEC 61850 GGIO5 uinteger input 16 ope...

Page 420: ...46 Fault Report 12 Time 0 to 4294967295 1 F050 0 3048 Fault Report 13 Time 0 to 4294967295 1 F050 0 304A Fault Report 14 Time 0 to 4294967295 1 F050 0 304C Fault Report 15 Time 0 to 4294967295 1 F050...

Page 421: ...002 0 34FC RTD Input 13 Value 32768 to 32767 C 1 F002 0 34FD RTD Input 14 Value 32768 to 32767 C 1 F002 0 34FE RTD Input 15 Value 32768 to 32767 C 1 F002 0 34FF RTD Input 16 Value 32768 to 32767 C 1 F...

Page 422: ...5 4016 Password access events 0 to 1 1 F102 0 Disabled 4017 Local setting authorization 1 to 65535 1 F300 1 4018 Remote setting authorization 0 to 65535 1 F300 1 4019 Access authorization timeout 5 to...

Page 423: ...40BE DNP other default deadband 0 to 65535 1 F001 30000 40C0 DNP IIN time synchronization bit period 1 to 10080 min 1 F001 1440 40C1 DNP message fragment size 30 to 2048 1 F001 240 40C2 DNP client ad...

Page 424: ...Network Time Protocol SNTP UDP port number 1 to 65535 1 F001 123 Data Logger Commands Read Write Command 4170 Data Logger Clear 0 to 1 1 F126 0 No Data Logger Read Write Setting 4181 Data Logger Chan...

Page 425: ...xLogic Operand to Activate LED 0 to 65535 1 F300 0 4281 User LED type latched or self resetting 0 to 1 1 F127 1 Self Reset 4282 Repeated for User Programmable LED 2 4284 Repeated for User Programmable...

Page 426: ...unction 0 to 1 1 F102 0 Disabled 4445 User Programmable Secondary Ethernet Fail Function 0 to 1 1 F102 0 Disabled 4446 User Programmable Battery Fail Function 0 to 1 1 F102 1 Enabled 4447 User Program...

Page 427: ...713 Breaker 1 phase A three pole opened 0 to 65535 1 F300 0 4714 Breaker 1 phase B opened 0 to 65535 1 F300 0 4715 Breaker 1 phase C opened 0 to 65535 1 F300 0 4716 Breaker 1 operate time 0 to 2 s 0 0...

Page 428: ...y 13 4DA0 Repeated for User Definable Display 14 4DC0 Repeated for User Definable Display 15 4DE0 Repeated for User Definable Display 16 User Programmable Pushbuttons Read Write Setting 12 modules 4E0...

Page 429: ...ed for RTD Input 12 54E4 Repeated for RTD Input 13 54F7 Repeated for RTD Input 14 550A Repeated for RTD Input 15 551D Repeated for RTD Input 16 5530 Repeated for RTD Input 17 5543 Repeated for RTD Inp...

Page 430: ...lexLogic Timer 21 58A8 Repeated for FlexLogic Timer 22 58B0 Repeated for FlexLogic Timer 23 58B8 Repeated for FlexLogic Timer 24 58C0 Repeated for FlexLogic Timer 25 58C8 Repeated for FlexLogic Timer...

Page 431: ...us Overcurrent 12 Neutral Time Overcurrent Read Write Grouped Setting 6 modules 5B00 Neutral Time Overcurrent 1 Function 0 to 1 1 F102 0 Disabled 5B01 Neutral Time Overcurrent 1 Signal Source 0 to 5 1...

Page 432: ...rrent 4 5D40 Repeated for Ground Time Overcurrent 5 5D50 Repeated for Ground Time Overcurrent 6 Ground Instantaneous Overcurrent Read Write Grouped Setting 12 modules 5E00 Ground Instantaneous Overcur...

Page 433: ...reclose Maximum Number of Shots 1 to 4 1 F001 2 6892 Autoreclose Block Breaker 1 0 to 65535 1 F300 0 6893 Autoreclose Close Time Breaker 1 0 to 655 35 s 0 01 F001 10 6894 Autoreclose Breaker Manual Cl...

Page 434: ...C0 Breaker 1 Arcing Current Function 0 to 1 1 F102 0 Disabled 72C1 Breaker 1 Arcing Current Source 0 to 5 1 F167 0 SRC 1 72C2 Breaker 1 Arcing Current Initiate A 0 to 65535 1 F300 0 72C3 Breaker 1 Arc...

Page 435: ...nect switch 1 phase C closed 0 to 65535 1 F300 0 754E Disconnect switch 1 phase C opened 0 to 65535 1 F300 0 754F Disconnect switch 1 operate time 0 to 2 s 0 001 F001 70 7550 Disconnect switch 1 alarm...

Page 436: ...ite Grouped Setting 3 modules 7F00 Neutral Overvoltage 1 Function 0 to 1 1 F102 0 Disabled 7F01 Neutral Overvoltage 1 Signal Source 0 to 5 1 F167 0 SRC 1 7F02 Neutral Overvoltage 1 Pickup 0 to 3 00 pu...

Page 437: ...les 8500 EGD Slow Producer Exchange 1 Function 0 to 1 1 F102 0 Disabled 8501 EGD Fast Producer Exchange 1 Destination 0 to 4294967295 1 F003 0 8503 EGD Slow Producer Exchange 1 Data Rate 500 to 1000 m...

Page 438: ...ent 1 Function 0 to 1 1 F102 0 Disabled 8A01 Digital Element 1 Name F203 Dig Element 1 8A09 Digital Element 1 Input 0 to 65535 1 F300 0 8A0A Digital Element 1 Pickup Delay 0 to 999999 999 s 0 001 F003...

Page 439: ...1 Block F300 0 8E02 Trip Bus 1 Pickup Delay 0 to 600 s 0 01 F001 0 8E03 Trip Bus 1 Reset Delay 0 to 600 s 0 01 F001 0 8E04 Trip Bus 1 Input 1 0 to 65535 1 F300 0 8E05 Trip Bus 1 Input 2 0 to 65535 1...

Page 440: ...t 9 90B4 Repeated for FlexElement 10 90C8 Repeated for FlexElement 11 90DC Repeated for FlexElement 12 90F0 Repeated for FlexElement 13 9104 Repeated for FlexElement 14 9118 Repeated for FlexElement 1...

Page 441: ...Input Output 2 9418 Repeated for Direct Input Output 3 9424 Repeated for Direct Input Output 4 9430 Repeated for Direct Input Output 5 943C Repeated for Direct Input Output 6 9448 Repeated for Direct...

Page 442: ...7483 647 0 001 F004 0 9A0D FlexElement 7 Actual 2147483 647 to 2147483 647 0 001 F004 0 9A0F FlexElement 8 Actual 2147483 647 to 2147483 647 0 001 F004 0 Teleprotection Inputs Outputs Read Write Setti...

Page 443: ...10 items 1 F001 0 A298 Repeated for Selector 2 DNP IEC Points Read Write Setting A300 DNP IEC 60870 5 104 Binary Input Points 256 items 0 to 65535 1 F300 0 A400 DNP IEC 60870 5 104 Analog Input Point...

Page 444: ...50 GOOSE analog input 1 per unit base 0 to 999999999 999 0 001 F060 1 AA07 Repeated for IEC 61850 GOOSE analog input 2 AA0E Repeated for IEC 61850 GOOSE analog input 3 AA15 Repeated for IEC 61850 GOOS...

Page 445: ...tems 0 to 65534 1 F206 none AD73 IEC 61850 logical node MMXNx name prefix 6 items 0 to 65534 1 F206 none ADE2 IEC 61850 logical node CSWIx name prefix 6 items 0 to 65534 1 F206 none AE3C IEC 61850 log...

Page 446: ...EC 61850 GGIO4 analog input 28 AFD4 Repeated for IEC 61850 GGIO4 analog input 29 AFDB Repeated for IEC 61850 GGIO4 analog input 30 AFE2 Repeated for IEC 61850 GGIO4 analog input 31 AFE9 Repeated for I...

Page 447: ...IEC 61850 MMXU PhV phsADeadband 1 0 001 to 100 0 001 F003 10000 B0D2 IEC 61850 MMXU PhV phsB Deadband 1 0 001 to 100 0 001 F003 10000 B0D4 IEC 61850 MMXU PhV phsC Deadband 1 0 001 to 100 0 001 F003 10...

Page 448: ...0 to 7 1 F001 4 B5C6 IEC 61850 Configurable GOOSE VLAN ID 0 to 4095 1 F001 0 B5C7 IEC 61850 Configurable GOOSE ETYPE APPID 0 to 16383 1 F001 0 B5C8 IEC 61850 Configurable GOOSE ConfRev 1 to 4294967295...

Page 449: ...or Contact Input 29 BBE8 Repeated for Contact Input 30 BBF0 Repeated for Contact Input 31 BBF8 Repeated for Contact Input 32 BC00 Repeated for Contact Input 33 BC08 Repeated for Contact Input 34 BC10...

Page 450: ...BDA0 Repeated for Contact Input 85 BDA8 Repeated for Contact Input 86 BDB0 Repeated for Contact Input 87 BDB8 Repeated for Contact Input 88 BDC0 Repeated for Contact Input 89 BDC8 Repeated for Contac...

Page 451: ...d for Virtual Input 34 BFC8 Repeated for Virtual Input 35 BFD4 Repeated for Virtual Input 36 BFE0 Repeated for Virtual Input 37 BFEC Repeated for Virtual Input 38 BFF8 Repeated for Virtual Input 39 C0...

Page 452: ...ed for Virtual Output 21 C1D8 Repeated for Virtual Output 22 C1E0 Repeated for Virtual Output 23 C1E8 Repeated for Virtual Output 24 C1F0 Repeated for Virtual Output 25 C1F8 Repeated for Virtual Outpu...

Page 453: ...88 Repeated for Virtual Output 76 C390 Repeated for Virtual Output 77 C398 Repeated for Virtual Output 78 C3A0 Repeated for Virtual Output 79 C3A8 Repeated for Virtual Output 80 C3B0 Repeated for Virt...

Page 454: ...tact Output 19 C524 Repeated for Contact Output 20 C530 Repeated for Contact Output 21 C53C Repeated for Contact Output 22 C548 Repeated for Contact Output 23 C554 Repeated for Contact Output 24 C560...

Page 455: ...rand 0 to 65535 1 F300 0 C774 Clear Data Logger operand 0 to 65535 1 F300 0 C775 Clear Breaker 1 Arcing Current operand 0 to 65535 1 F300 0 C776 Clear Breaker 2 Arcing Current operand 0 to 65535 1 F30...

Page 456: ...put 24 C8F0 Repeated for Direct Input 25 C8F4 Repeated for Direct Input 26 C8F8 Repeated for Direct Input 27 C8FC Repeated for Direct Input 28 C900 Repeated for Direct Input 29 C904 Repeated for Direc...

Page 457: ...Ch 1 Unreturned Messages Alarm Function 0 to 1 1 F102 0 Disabled CAE1 Direct I O Ch 1 Unreturned Messages Alarm Msg Count 100 to 10000 1 F001 600 CAE2 Direct I O Ch 1 Unreturned Messages Alarm Thresho...

Page 458: ...epeated for Remote Input 20 D068 Repeated for Remote Input 21 D072 Repeated for Remote Input 22 D07C Repeated for Remote Input 23 D086 Repeated for Remote Input 24 D090 Repeated for Remote Input 25 D0...

Page 459: ...Output 2 D2A8 Repeated for Remote Output 3 D2AC Repeated for Remote Output 4 D2B0 Repeated for Remote Output 5 D2B4 Repeated for Remote Output 6 D2B8 Repeated for Remote Output 7 D2BC Repeated for Rem...

Page 460: ...odel Value 0 to 2 1 F001 2 D339 IEC 61850 GGIO2 CF SPCSO26 ctlModel Value 0 to 2 1 F001 2 D33A IEC 61850 GGIO2 CF SPCSO27 ctlModel Value 0 to 2 1 F001 2 D33B IEC 61850 GGIO2 CF SPCSO28 ctlModel Value...

Page 461: ...D398 Repeated for Remote Device 7 D39C Repeated for Remote Device 8 D3A0 Repeated for Remote Device 9 D3A4 Repeated for Remote Device 10 D3A8 Repeated for Remote Device 11 D3AC Repeated for Remote Dev...

Page 462: ...icates the number of decimal points to display Example Current values are stored as 32 bit numbers with three decimal places and base units in Amps If the retrieved value is 12345 678 A and the displa...

Page 463: ...bled 1 Input 1 2 Input 2 F106 ENUMERATION PHASE ROTATION 0 ABC 1 ACB F108 ENUMERATION OFF ON 0 Off 1 On F109 ENUMERATION CONTACT OUTPUT OPERATION 0 Self reset 1 Latched 2 Disabled F110 ENUMERATION CON...

Page 464: ...00 111 16 00 22 0 72 52 2 10 82 5 10 112 16 50 23 0 74 53 2 20 83 5 20 113 17 00 24 0 76 54 2 30 84 5 30 114 17 50 25 0 78 55 2 40 85 5 40 115 18 00 26 0 80 56 2 50 86 5 50 116 18 50 27 0 82 57 2 60 8...

Page 465: ...gital Element 12 704 Digital Element 13 705 Digital Element 14 706 Digital Element 15 707 Digital Element 16 708 Digital Element 17 709 Digital Element 18 710 Digital Element 19 711 Digital Element 20...

Page 466: ...t 41 890 RTD Input 42 891 RTD Input 43 892 RTD Input 44 893 RTD Input 45 894 RTD Input 46 895 RTD Input 47 896 RTD Input 48 900 User Programmable Pushbutton 1 901 User Programmable Pushbutton 2 902 Us...

Page 467: ...R_UINT32 32 BIT ERROR CODE F141 specifies bit number A bit value of 0 no error 1 error Bitmask Error 0 Any Self Tests 1 IRIG B Failure 2 Port 1 Offline 3 Port 2 Offline 4 Port 3 Offline 5 Port 4 Offli...

Page 468: ...mand 13 Led Test Initiated 14 Flash Programming 15 Fault Report Trigger 16 User Programmable Fault Report Trigger 17 18 Reload CT VT module Settings 19 20 Ethernet Port 1 Offline 21 Ethernet Port 2 Of...

Page 469: ...0 A 1 B 2 C bitmask value bitmask value 0 NONE 35 UserSt 3 1 DNA 1 36 UserSt 4 2 DNA 2 37 UserSt 5 3 DNA 3 38 UserSt 6 4 DNA 4 39 UserSt 7 5 DNA 5 40 UserSt 8 6 DNA 6 41 UserSt 9 7 DNA 7 42 UserSt 10...

Page 470: ...2 DV1 and LV2 3 DV1 or DV2 4 DV1 Xor DV2 5 DV1 and DV2 bitmask definition 0 Off 1 8 samples cycle 2 16 samples cycle 3 32 samples cycle 4 64 samples cycle value GOOSE dataset 0 Off 1 GooseIn 1 2 Goos...

Page 471: ...Test Enumeration 1 F226 ENUMERATION REMOTE INPUT OUTPUT TRANSFER METHOD 0 None 1 GSSE 2 GOOSE F227 ENUMERATION RELAY SERVICE STATUS 0 Unknown 1 Relay In Service 2 Relay Out Of Service F230 ENUMERATIO...

Page 472: ...0 MMXU2 MX W phsB cVal mag f 321 MMXU2 MX W phsC cVal mag f 322 MMXU2 MX VAr phsA cVal mag f 323 MMXU2 MX VAr phsB cVal mag f value GOOSE dataset item 324 MMXU2 MX VAr phsC cVal mag f 325 MMXU2 MX VA...

Page 473: ...ang f 426 MMXU5 MX A phsC cVal mag f 427 MMXU5 MX A phsC cVal ang f 428 MMXU5 MX A neut cVal mag f 429 MMXU5 MX A neut cVal ang f value GOOSE dataset item 430 MMXU5 MX W phsA cVal mag f 431 MMXU5 MX W...

Page 474: ...tIn8 stVal 527 GGIO5 ST UIntIn9 q 528 GGIO5 ST UIntIn9 stVal 529 GGIO5 ST UIntIn10 q 530 GGIO5 ST UIntIn10 stVal 531 GGIO5 ST UIntIn11 q 532 GGIO5 ST UIntIn11 stVal 533 GGIO5 ST UIntIn12 q 534 GGIO5 S...

Page 475: ...ST UIntIn3 stVal 172 GGIO3 ST UIntIn4 q 173 GGIO3 ST UIntIn4 stVal 174 GGIO3 ST UIntIn5 q 175 GGIO3 ST UIntIn5 stVal 176 GGIO3 ST UIntIn6 q 177 GGIO3 ST UIntIn6 stVal 178 GGIO3 ST UIntIn7 q 179 GGIO3...

Page 476: ...second reg ister indicates input output state with bits 0 to 15 corresponding to input output state 17 to 32 if required The third register indicates input output state with bits 0 to 15 corresponding...

Page 477: ...French 2 Chinese 3 Russian F600 UR_UINT16 FLEXANALOG PARAMETER Corresponds to the Modbus address of the value used when this parameter is selected Only certain values may be used as Flex Analogs basi...

Page 478: ...FLEXINTEGER PARAMETER This 16 bit value corresponds to the Modbus address of the selected FlexInteger paramter Only certain values may be used as FlexIntegers Enumeration Remote DPS input status 0 Int...

Page 479: ...ring Message Specification MMS at the upper application layer for transfer of real time data This protocol has been in existence for several of years and provides a set of services suitable for the tr...

Page 480: ...d for SOE logs since the buffering capability reduces the chances of missing data state changes Unbuffered reporting should generally be used for local status display C 2 3 GGIO2 DIGITAL CONTROL VALUE...

Page 481: ...wer factor MMXU1 MX Hz frequency MMXU1 MX PPV phsAB phase AB voltage magnitude and angle MMXU1 MX PPV phsBC phase BC voltage magnitude and angle MMXU1 MX PPV phsCA Phase CA voltage magnitude and angle...

Page 482: ...This value originates in the fault locator function The XCBR logical node is directly associated with the breaker control feature XCBR1 ST Loc This is the state of the XCBR1 local remote switch A set...

Page 483: ...of the last change of either the value or quality flags of the data item To accomplish this functionality all IEC 61850 data items must be regularly scanned for data changes and the timestamp updated...

Page 484: ...ion for greater than two minutes the connection will be aborted by the C60 This frees up the con nection to be used by other clients Therefore when using IEC 61850 reporting clients should configure r...

Page 485: ...wo pre defined data structures named DNA and UserSt Each DNA and UserSt item is referred to as a bit pair GSSE messages are transmit ted in response to state changes in any of the data points containe...

Page 486: ...OOSE data transfer between UR series IEDs and devices from other manufacturers Fixed GOOSE is recommended for applications that require GOOSE data transfer between UR series IEDs IEC 61850 GOOSE messa...

Page 487: ...value and a floating point ana log value This matches the transmission dataset configuration above 2 Configure the GOOSE service settings by making the following changes in the INPUTS OUTPUTS REMOTE D...

Page 488: ...t Thus if the local MAC address is 00 A0 F4 01 02 03 then the destination MAC address will be 01 A0 F4 01 02 03 C 4 6 GSSE ID AND GOOSE ID SETTINGS GSSE messages contain an identifier string used by r...

Page 489: ...tion process for IEC 61850 BDA Basic Data Attribute that is not structured DAI Instantiated Data Attribute DO Data Object type or instance depending on the context 842790A1 CDR Ethernet System configu...

Page 490: ...SCD to set communication configuration parame ters that is required addresses reception GOOSE datasets IDs of incoming GOOSE datasets etc for the IED The IED configurator functionality is implemented...

Page 491: ...ors we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD and strictly within EnerVista UR Setup software or the front panel display access through the Settings Prod...

Page 492: ...node contains the address parameters of the access point The GSE node provides the address element for stat ing the control block related address parameters where IdInst is the instance identificatio...

Page 493: ...taSet name Other DataSet elements FCDA fc doName daName IdInst prefix InClass InInst Other FCDA elements DOI name SDI name Val Text Other DOI elements GSEControl name datSet type confRev appID LN InTy...

Page 494: ...The attribute DA has a func tional constraint and can either have a basic type be an enumeration or a structure of a DAType The DAType is built from BDA elements defining the structure elements which...

Page 495: ...rocedure is pretty much the same First a substation project must be created either as an empty template or with some system information by importing a system specification file SSD Then IEDs are added...

Page 496: ...le and its version and specifies options for the mapping of names to signals The Substation node describes the substation parameters Figure 0 7 SCD FILE STRUCTURE SUBSTATION NODE 842791A1 CDR SCL Head...

Page 497: ...tedAP node describes the IED access point connected to this sub network The Address node contains the address parameters of the access point The GSE node provides the address element for stat ing the...

Page 498: ...te the C60 with the new configuration from an SCD file with the EnerVista UR Setup software 1 Right click anywhere in the files panel and select the Import Contents From SCD File item 2 Select the sav...

Page 499: ...ne GE Multilin IED defined in the SCD file the software prompt the user to save a UR series set tings file for each IED 4 After the URS file is created modify any settings if required 5 To update the...

Page 500: ...SM IEC 61850 9 2 used B24 SCSM other GENERIC SUBSTATION EVENT MODEL GSE B31 Publisher side O Yes B32 Subscriber side Yes TRANSMISSION OF SAMPLED VALUE MODEL SVC B41 Publisher side O B42 Subscriber sid...

Page 501: ...a set name M8 5 data reference M8 6 BufTm M8 7 IntgPd M8 8 GI Logging O M9 Log control O M9 1 IntgPd M10 Log O M11 Control M Yes IF GSE B31 32 IS SUPPORTED GOOSE O Yes M12 1 entryID M12 2 DataReflnc M...

Page 502: ...hange qchg S24 3 data update dupd S25 GetBRCBValues TP c6 Yes S26 SetBRCBValues TP c6 Yes UNBUFFERED REPORT CONTROL BLOCK URCB S27 Report TP c6 Yes S27 1 data change dchg Yes S27 2 qchg change qchg S2...

Page 503: ...C CLAUSE 16 MULTICAST SVC S45 SendMSVMessage MC c10 S46 GetMSVCBValues TP O S47 SetMSVCBValues TP O UNICAST SVC S48 SendUSVMessage MC c10 S49 GetUSVCBValues TP O S50 SetUSVCBValues TP O CONTROL CLAUSE...

Page 504: ...nge of frequency PHAR Harmonic restraint PHIZ Ground detector PIOC Instantaneous overcurrent Yes PMRI Motor restart inhibition PMSS Motor starting time supervision POPF Over power factor PPAM Phase an...

Page 505: ...oltage control M LOGICAL NODES FOR METERING AND MEASUREMENT MDIF Differential measurements MHAI Harmonics or interharmonics MHAN Non phase related harmonics or interharmonic MMTR Metering MMXN Non pha...

Page 506: ...y ZBSH Bushing ZCAB Power cable ZCAP Capacitor bank ZCON Converter ZGEN Generator ZGIL Gas insulated line ZLIN Power overhead line ZMOT Motor ZREA Reactor ZRRC Rotating reactive component ZSAR Surge a...

Page 507: ...t V 24 V 28 Recommended if 1200 bits s Balanced Interchange Circuit X 24 X 27 100 bits sec 200 bits sec 300 bits sec 600 bits sec 1200 bits sec 2400 bits sec 4800 bits sec 9600 bits sec 2400 bits sec...

Page 508: ...used in standard direction not used cannot be selected in IEC 60870 5 104 standard Process information in monitor direction 4 1 Single point information M_SP_NA_1 2 Single point information with time...

Page 509: ...equipment with time tag CP56Time2a M_EP_TE_1 40 Packed output circuit information of protection equipment with time tag CP56Time2a M_EP_TF_1 4 45 Single command C_SC_NA_1 46 Double command C_DC_NA_1...

Page 510: ...ry select file call file call section F_SC_NA_1 123 Last section last segment F_LS_NA_1 124 Ack file ack section F_AF_NA_1 125 Segment F_SG_NA_1 126 Directory blank or X available only in monitor stan...

Page 511: ...C_SE_NA_1 49 C_SE_NB_1 50 C_SE_NC_1 51 C_BO_NA_1 58 C_SC_TA_1 X X X X X 59 C_DC_TA_1 60 C_RC_TA_1 TYPE IDENTIFICATION CAUSE OF TRANSMISSION NO MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 20 to 36 37 to 41...

Page 512: ...ME_NC_1 X X X 113 P_AC_NA_1 120 F_FR_NA_1 121 F_SR_NA_1 122 F_SC_NA_1 123 F_LS_NA_1 124 F_AF_NA_1 125 F_SG_NA_1 126 F_DR_TA_1 TYPE IDENTIFICATION CAUSE OF TRANSMISSION NO MNEMONIC 1 2 3 4 5 6 7 8 9 10...

Page 513: ...ME_TF_1 Station interrogation Clock synchronization 4 Clock synchronization optional see Clause 7 6 Command transmission 4 Direct command transmission Direct setpoint command transmission 4 Select and...

Page 514: ...ences of events Transmission of sequences of recorded analog values File transfer in control direction Transparent file Background scan Background scan Acquisition of transmission delay Acquisition of...

Page 515: ...by the Internet Architecture Board IAB It offers a broad spectrum of actual standards used in the Inter net The suitable selection of documents from RFC 2200 defined in this standard for given project...

Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...

Page 517: ...addition to the Highest DNP Levels Supported the complete list is described in the attached table Binary Inputs Object 1 Binary Input Changes Object 2 Binary Outputs Object 10 Control Relay Output Bl...

Page 518: ...tputs 4 Never Always Sometimes Configurable SELECT OPERATE Never 4 Always Sometimes Configurable DIRECT OPERATE Never 4 Always Sometimes Configurable DIRECT OPERATE NO ACK Never 4 Always Sometimes Con...

Page 519: ...rable Only certain objects Sometimes attach explanation 4 ENABLE DISABLE unsolicited Function codes supported Sends Static Data in Unsolicited Responses 4 Never When Device Restarts When Status Flags...

Page 520: ...7 28 index 3 Binary Input Change with Relative Time 1 read 06 no range or all 07 08 limited quantity 10 0 Binary Output Status Variation 0 is used to request default variation 1 read 00 01 start stop...

Page 521: ...ation 0 is used to request default variation 1 read 06 no range or all 07 08 limited quantity 1 32 Bit Counter Change Event 1 read 06 no range or all 07 08 limited quantity 129 response 130 unsol resp...

Page 522: ...nse 130 unsol resp 17 28 index 3 32 Bit Analog Change Event with Time 1 read 06 no range or all 07 08 limited quantity 129 response 130 unsol resp 17 28 index 4 16 Bit Analog Change Event with Time 1...

Page 523: ...ose 30 abort 5b free format 129 response 130 unsol resp 5b free format 5 File transfer 1 read 2 write 5b free format 129 response 130 unsol resp 5b free format 6 File transfer status 129 response 130...

Page 524: ...performed on a binary counter point the frozen value is available in the corresponding frozen counter point BINARY INPUT POINTS Static Steady State Object Number 1 Change Event Object Number 2 Reques...

Page 525: ...al Input 15 15 Virtual Input 16 16 Virtual Input 17 17 Virtual Input 18 18 Virtual Input 19 19 Virtual Input 20 20 Virtual Input 21 21 Virtual Input 22 22 Virtual Input 23 23 Virtual Input 24 24 Virtu...

Page 526: ...eze and clear noack 22 assign class Static Variation reported when variation 0 requested 1 32 Bit Binary Counter with Flag Change Event Variation reported when variation 0 requested 1 32 Bit Counter C...

Page 527: ...l Analog Input points are in the same units as the Analog Input quantity For example an Analog Input quantity measured in volts has a corresponding deadband in units of volts This is in conformance wi...

Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...

Page 529: ...February 2003 URC 036 1601 0100 C6 3 1x 11 February 2003 URC 037 1601 0100 D1 3 2x 11 February 2003 URC 039 1601 0100 D2 3 2x 02 June 2003 URX 084 1601 0100 E1 3 3x 01 May 2003 URX 080 1601 0100 E2 3...

Page 530: ...Update Updated DISCONNECT SWITCHES section 5 89 5 91 Update Updated FLEXLOGIC OPERANDS table 5 108 5 110 Update Updated BREAKER FAILURE section 5 125 5 127 Update Updated PHASE INSTANTANEOUS OVERCURRE...

Page 531: ...Updated INTER RELAY COMMUNICATIONS specifications section 3 7 3 7 Update Updated REAR TERMINAL LAYOUT section 3 46 Add Added ETHERNET SWITCH SELF TEST ERRORS section 7 4 7 5 Update Updated MINOR SELF...

Page 532: ...on Table F 8 MAJOR UPDATES FOR C60 MANUAL REVISION R2 PAGE R1 PAGE R2 CHANGE DESCRIPTION Title Title Update Manual part number to 1601 0100 R2 Table F 9 MAJOR UPDATES FOR C60 MANUAL REVISION R1 Sheet...

Page 533: ...o include disturbance detector information 5 71 5 72 Update Updated FLEXLOGIC OPERANDS table 6 17 6 17 Update Updated TRACKING FREQUENCY section 6 18 Add Added IEC 61850 GOOSE ANALOG VALUES section 7...

Page 534: ...et FDL Fault Detector low set FLA Full Load Current FO Fiber Optic FREQ Frequency FSK Frequency Shift Keying FTP File Transfer Protocol FxE FlexElement FWD Forward G Generator GE General Electric GND...

Page 535: ...l Unit RX Rx Receive Receiver s second S Sensitive SAT CT Saturation SBO Select Before Operate SCADA Supervisory Control and Data Acquisition SEC Secondary SEL Select Selector Selection SENS Sensitive...

Page 536: ...it is returned with all transportation charges prepaid to an authorized service centre or the factory Repairs or replacement under war ranty will be made without charge Warranty shall not apply to an...

Page 537: ...RE 7 6 BINARY INPUT POINTS E 8 BINARY OUTPUT POINTS E 9 BLOCK DIAGRAM 1 3 BLOCK SETTING 5 5 BREAKER ARCING CURRENT actual values 6 23 clearing 5 14 7 2 FlexLogic operands 5 91 logic 5 177 measurement...

Page 538: ...12 CURVES definite time 5 124 5 135 FlexCurves 5 82 5 124 I2T 5 124 IAC 5 123 IEC 5 122 IEEE 5 121 inverse time undervoltage 5 135 types 5 120 D DATA FORMATS MODBUS B 58 DATA LOGGER clearing 5 14 7 2...

Page 539: ...5 135 FlexCurve 5 124 I t curves 5 124 IAC curves 5 123 IEC curves 5 122 IEEE curves 5 121 EQUIPMENT MISMATCH ERROR 7 5 ETHERNET actual values 6 7 configuration 1 8 error messages 7 7 Modbus registers...

Page 540: ...r GROUND TOC GROUND TOC FlexLogic operands 5 93 logic 5 133 Modbus registers B 28 settings 5 133 specifications 2 9 GROUPED ELEMENTS 5 109 GSSE 5 193 5 194 5 195 6 6 H HALF DUPLEX B 1 HTTP PROTOCOL 5...

Page 541: ...lues B 3 settings 5 17 5 36 store multiple settings B 5 store single setting B 4 supported function codes B 3 user map 5 36 B 10 B 24 MODEL INFORMATION 6 24 MODIFICATION FILE NUMBER 6 24 MODULE FAILUR...

Page 542: ...SE TOC FlexLogic operands 5 93 logic 5 126 Modbus registers B 26 settings 5 125 specifications 2 9 PHASE UNDERVOLTAGE FlexLogic operands 5 93 logic 5 137 Modbus registers B 30 settings 5 136 specifica...

Page 543: ...5 94 5 109 5 146 B 28 B 29 SETTINGS TEMPLATES description 4 4 8 6 editing 4 4 8 6 enabling 4 4 8 6 Modbus registers B 57 password protection 4 5 8 7 removing 4 7 8 9 viewing 4 6 8 8 SETTINGS CHANGING...

Page 544: ...E DISPLAYS example 5 59 invoking and scrolling 5 57 Modbus registers B 18 B 24 settings 5 57 5 59 specifications 2 11 USER PROGRAMMABLE LEDs custom labeling 4 22 defaults 4 16 description 4 15 4 16 Mo...

Reviews: